112
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
7.5.2
Enable Energy Saver System Mode from the UPS Command Menu
To enable Energy Saver System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System
Status screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The
UPS Control Command
screen is displayed.
4.
On the UPS Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Energy Saver
System mode.
The Online status indicator is illuminated. The UPS status indicates ESS. The
UPM status
indicates ONLINE. If the battery is not charging, the power module is off.
7.
5
.3
Disable Energy Saver System Mode from the UPS Command Menu
To disable Energy Saver System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is
displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control
Command
screen is displayed.
4.
On the UPS Control Command screen, select
DISABLE ENERGY SAVER
.
5.
Press the SELECT pushbutton on the UPS Command menu bar. The UPS transfers to
Battery mode
and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM
status
indicates ONLINE.
NOTE
•
The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Variable Module Management System mode is enabled, the Energy Saver System mode commands will not be
displayed.
•
NOTE
•
The Energy Saver System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the
Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
•
Содержание Power Xpert 9395P 250 kVA
Страница 1: ...User s and Installation Guide Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA...
Страница 2: ......
Страница 3: ...Power Xpert 9395P UPS 250 kVA 275 kVA 300 kVA User s and Installation Guide...
Страница 168: ......
Страница 169: ......
Страница 170: ...614 01919 00...