Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Installation or servicing should be performed by qualified service personnel knowledgeable of UPS and battery
systems, and required precautions. Keep unauthorized personnel away from equipment. Consider all warnings,
cautions, and notes before installing or servicing equipment.
DO NOT DISCONNECT the batteries while the
UPS is in Battery mode
.
•
Replace batteries with the same number and type of batteries as originally installed with the UPS.
•
Disconnect the charging source prior to connecting or disconnecting terminals.
•
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contacting any
part of a grounded battery can cause a risk of electric shock. An electric shock is less likely if you
disconnect the grounding connection before you work on the batteries.
•
Proper disposal of batteries is required. Refer to local codes for disposal requirements.
•
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
•
Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to protect
personnel from dangerous voltages inside the unit.
•
Do not install or operate the UPS system close to gas or electric heat sources.
•
The operating environment should be maintained within the parameters stated in this manual.
•
Keep surroundings uncluttered, clean, and free from excess moisture.
•
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
equipment.
To prevent damage to the wiring channel and wiring in the UPS cabinet base when lifting or moving the
cabinet:
•
Lift and move the cabinet using only the front or rear forklift slots.
•
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots. DO NOT
angle fork tips upward.
•
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
•
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are kept
in a horizontal position with no upward angling.
•
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
•
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...