Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
175
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
GO TO BYPASS
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
The UPS transfers to Bypass mode and the critical load is immediately supplied by the bypass source. If
the bypass source is not available, the power module remains on and an alarm sounds.
The
BYPASS
status indicator is illuminated. The Bypass status indicates
ON
. The UPM status indicates
READY
. The power module remains on.
Power is present inside the UPS cabinet.
77..33..1188 TTrraannssffeerr ffrroom
m B
Byyppaassss ttoo O
Onnlliinnee M
Mooddee
To transfer the critical load to Online mode:
1.
If not already closed, close the battery breaker.
2.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
3.
On the System Status screen, select the
UPS
command.
4.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
5.
On the UPS Control Command screen, select
GO TO ONLINE
.
6.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Online mode. If the power module is not available, the system remains on bypass
and an alarm sounds.
The
ONLINE
status indicator is illuminated. The UPS status indicates
ONLINE
. The UPM status indicates
ONLINE
.
77..33..1199 TTrraannssffeerr ffrroom
m O
Onnlliinnee ttoo B
Byyppaassss M
Mooddee aanndd S
Shhuutt D
Doow
wnn U
UP
PM
Mss
To transfer the critical load to Bypass mode and shut down the UPMs:
1.
Transfer the critical load to bypass by performing the procedure in paragraph
Transfer from Online to Bypass Mode
.
2.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
3.
If UPM 4 (FI-UPM) is installed, proceed to Step 4; otherwise, proceed to Step 11.
4.
On the System Status screen, select the
UPM
command. The UPS Control Command screen is displayed.
5.
On the UPS Control Command screen, select the
UPM 1
command.
6.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The UPM 1 Control
Command screen is displayed.
7.
Proceed to Step 10.
8.
On the System Status screen, select the
UPM
command.
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...