176
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
9.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The UPM 1 Control
Command screen is displayed.
10. On the UPM 1 Control Command screen, select
UPM OFF
.
11. Press the
SELECT
pushbutton on the UPM 1 Command menu bar.
The UPM status indicates
READY
. The input, output, and battery contactors open, and the power module
remains on.
12. To turn off the power module, press the
CONTROLS
pushbutton on the UPS Control Command menu bar.
The UPM 1 Control Command screen is displayed.
13. On the UPM 1 Control Command screen, select
UPM OFF
.
14. Press the
SELECT
pushbutton on the UPM 1 Command menu bar.
The UPM status indicates
SHUTDOWN
. The power module is turned off.
Logic power remains on.
15. If UPM 4 (FI-UPM) is installed, repeat Steps 5 through 14 selecting
UPM 4
to shut down UPM 4.
Power is present inside the UPS cabinet.
77..33..2200 S
Siinnggllee U
UP
PM
M S
Shhuuttddoow
wnn
To shut down a single UPM:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7.
3.
On the System Status screen, select the
UPM
command. The UPS Control Command screen is displayed.
4.
On the UPS Control Command screen, select the UPM to shut down.
5.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The UPM Control Command
screen is displayed.
6.
Proceed to Step 9.
7.
On the System Status screen, select the
UPM
command.
8.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The UPM Control
Command screen is displayed.
9.
On the UPM Control Command screen, select
UPM OFF
.
10. Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM status indicates
READY
. The input, output, and battery contactors open, and the power module
remains on. The remaining UPMs supply the critical load.
11. To turn off the power module, press the
CONTROLS
pushbutton on the UPS Control Command menu bar.
The UPM Control Command screen is displayed.
12. On the UPM Control Command screen, select
UPM OFF
.
13. Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM status indicates SHUTDOWN. The power module is turned off. The remaining UPMs continue to
supply the critical load.
Logic power remains on.
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...