Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
NOTE 1
The High Alert mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
START HIGH ALERT
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS starts High Alert mode with the UPMs online supplying the critical load. After
one hour the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
HIGH ALERT
. The UPM status
indicates
ONLINE
. The power module is on.
77..44..1122 EEnnaabbllee V
Vaarriiaabbllee M
Moodduullee M
Maannaaggeem
meenntt S
Syysstteem
m M
Mooddee ffrroom
m tthhee B
Byyppaassss C
Coom
mm
maanndd M
Meennuu
To enable Variable Module Management System mode:
NOTE 1
The Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
ENABLE VAR MODULE MANAGEMENT
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Variable Module Management System mode. In approximately
twenty seconds the UPS calculates the required number of UPMs needed to support the load.
The Online status indicator is illuminated. The UPS status indicates
VMMS
. The UPM status
indicates
ONLINE
.
77..44..1133 D
Diissaabbllee V
Vaarriiaabbllee M
Moodduullee M
Maannaaggeem
meenntt S
Syysstteem
m M
Mooddee ffrroom
m tthhee B
Byyppaassss C
Coom
mm
maanndd M
Meennuu
To disable Variable Module Management System mode:
NOTE 1
The Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...