78
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
NOTE
Battery Cable Routing Requirements using Conduit
:
•
* Each conduit must have a Positive, Negative, and Ground conductor
•
* There must be an equal number of positive and negative conductors in a single
conduit. Only one ground conductor is required in each conduit.
•
Battery Cable Routing Requirements using Raceway:
•
* Positive and negative battery cables must be run side by side in the raceway in an
alternating pattern (+ - + - + - + -).
•
* There must be a ground cable running in the raceway with the battery cables.
1.
Route the battery cables between the ISBM section and the battery system or battery disconnect. See
,
, and
or
for wiring access information and terminal locations.
2.
If wiring the UPS for a common battery, proceed to Step 3; if wiring for a separate battery, proceed to Step
5.
3.
Using hardware from the external wiring terminal hardware kit (see
), connect the positive,
negative, and ground DC power wiring from the battery system or disconnect to the ISBM section battery
and ground terminals. Use both sets of terminals shown in
as needed. See paragraph
UPS System Power Wiring Preparation
for wiring and termination requirements.
4.
Proceed to Step 6.
5.
Using hardware from the external wiring terminal hardware kit (see
), connect the positive,
negative, and ground DC power wiring from the battery systems or disconnects to the ISBM section
battery and ground terminals. Use one set of terminals for each UPM as shown in
. See
paragraph
UPS System Power Wiring Preparation
for wiring and termination requirements.
6.
After wiring the UPS system to the facility power and critical load, be sure to ground the system according
to local and/or national electrical wiring codes.
7.
If wiring interface connections, proceed to paragraph
Installing Interface Connections
; otherwise,
proceed to Step 8.
8.
When all wiring is complete, reinstall the top and bottom safety shield panels removed in paragraph
External Power Wiring Installation
, Step 2. Secure with the retained hardware.
9.
Reinstall the left front panel removed in paragraph
External Power Wiring Installation
, Step 1 and
secure with the retained hardware.
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...