UPS System Installation
4-18
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
Terminal TB2
Name
Description
1
Pull Chain
Output: Backup control for parallel operation.
2
Pull Chain Common
3
Alarm Relay NC
Output: General purpose normally-closed (NC) relay contact.
4
Alarm Relay Common
5
Alarm Relay NO
Output: General purpose normally-open (NO) relay contact.
6
Alarm Relay Common
7
Not Used
8
Not Used
9
Not Used
10
Not Used
Terminal TB3
Name
Description
1
Building Alarm 1
Input: Programmable UPS alarm, activated by a remote dry contact closure.
2
Building Alarm 1 Return
3
Building Alarm 2
Input: Programmable UPS alarm, activated by a remote dry contact closure.
4
Building Alarm 2 Return
5
Building Alarm 3
Default: Charger Off
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default function
set for charger off.
6
Building Alarm 3 Return
7
Building Alarm 4
Default: On Generator
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default function
set for on generator.
8
Building Alarm 4 Return
9
Building Alarm 5
Default: Maintenance Bypass
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default function
set for maintenance bypass.
10
Building Alarm 5 Return
NOTE “Return”
indicates connection to electronics circuit ground. “Common”
indicates connection to common side of isolated relay contact.
Table 4-1. TB1, TB2, and TB3 Interface Connections (Continued)
Содержание Power Xpert 9395 550/275
Страница 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 27: ...Section 1 Installation...
Страница 28: ......
Страница 100: ...1 2 Power Xpert TM 9395 550 275 UPS 225 550 kVA Installation and Operation Manual 164201716 Rev 8...
Страница 207: ......
Страница 208: ...164201716 8 164201716 8...