UPS Operating Instructions
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
7-7
Firmware Versions
The Versions screen provides the firmware version numbers installed on the UPS. Select
VERSIONS
from the System Setup Level 0 menu to display the Versions screen. To scroll through the firmware
types, press the up or down arrow pushbutton on the menu bar. To return to the System Setup screen,
press the
ESC
pushbutton
.
Identification
The Unit Type screen provides the model, and serial numbers of the UPS unit. Select
UNIT TYPE
from
the System Setup Level 0 menu to display the Unit Type screen. To return to the System Setup screen,
press the
ESC
pushbutton
.
Language
The Language Setup screen allows the display menu language to be set. Select
LANGUAGE SETUP
from the System Setup Level 0 menu to display the Language Setup screen. Use the up or down arrow
pushbutton to highlight the desired language, then press the
SELECT
pushbutton
.
To return to the
System Setup screen, press the
ESC
pushbutton
.
Energy Saver System
The Energy Saver System Setup screen allows the Energy Saver function to be configured. Select
ENERGY SAVER SYSTEM SETUP
from the System Setup Level 0 menu to display the Energy Saver
System Setup screen. Use the up or down arrow pushbutton to highlight the desired function, then
press the
SELECT
pushbutton
.
To return to the System Setup screen, press the
ESC
pushbutton
.
Storm Detection Counter
The Storm Detection Counter screen sets the number of power line disturbances that can occur before
the UPS locks into Normal mode. Select
STORM DETECTION COUNTER
from the Energy Saver
System Setup screen to display the Storm Detection Counter screen. Use the up or down arrow
pushbutton to set the counter. Press
SAVE
or
ABORT
. Once the action is completed, the Energy
Saver System Setup screen is displayed.
Storm Detection Timer
The Storm Detection Timer screen sets the length of time that power line disturbances are monitored.
The time can be set in 10 minute increments from 0 to 990 minutes. Select
STORM DETECTION
TIMER
from the Energy Saver System Setup screen to display the Storm Detection Timer screen. Use
the up or down arrow pushbutton to set the time. Press
SAVE
or
ABORT
. Once the action is
completed, the Energy Saver System Setup screen is displayed.
High Alert Timer
The High Alert Timer screen sets the length of time the UPS remains in Normal mode before
transferring back to Energy Saver System mode. The time can be set in 10 minute increments from 0
to 990 minutes. Select
HIGH ALERT TIMER
from the Energy Saver System Setup screen to display
the High Alert Timer screen. Use the up or down arrow pushbutton to set the time. Press
SAVE
or
ABORT
. Once the action is completed, the Energy Saver System Setup screen is displayed.
Variable Module Management
System
The Module Management System Setup screen allows the Variable Module Management System
function to be configured. Select
MODULE MANAGEMENT SYSTEM SETUP
from the System
Setup Level 0 menu to display the Module Management System Setup screen. Use the up or down
arrow pushbutton to highlight the desired function, then press the
SELECT
pushbutton
.
To return to
the System Setup screen, press the
ESC
pushbutton
.
VMMS Load Limit
The VMMS Load Limit screen sets the maximum load that can be drawn from a UPM before
additional UPMs are activated. Select
APM LOAD LIMIT
from the Module Management System
Setup screen to display the VMMS Load Limit screen. Use the up or down arrow pushbutton to set the
load limit. Press
SAVE
or
ABORT
. Once the action is completed, the Module Management System
screen is displayed.
VMMS UPM Redundancy
The VMMS UPM Redundancy screen sets the number of UPMs to remain active to maintain
redundancy. Select
VMMS UPM REDUNDANCY
from the Module Management System Setup
screen to display the VMMS UPM Redundancy screen. Use the up or down arrow pushbutton to set
the number of UPMs. Press
SAVE
or
ABORT
. Once the action is completed, the Module
Management System Setup screen is displayed.
Table 7-3. Display Menu Operation (Continued)
Function
Subfunction
Operation
Содержание Power Xpert 9395 550/275
Страница 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 27: ...Section 1 Installation...
Страница 28: ......
Страница 100: ...1 2 Power Xpert TM 9395 550 275 UPS 225 550 kVA Installation and Operation Manual 164201716 Rev 8...
Страница 207: ......
Страница 208: ...164201716 8 164201716 8...