Chapter 9
UPS Maintenance
The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and
assemblies are located for easy removal, with very little disassembly. This design allows authorized service
personnel to perform routine maintenance and servicing quickly.
You must schedule periodic performance checks of your UPS system to keep it running properly. Regular
routine checks of operation and system parameters enable your system to function efficiently for many
trouble–free years.
9.1
Important Safety Instructions
Remember that your UPS system is designed to supply power
EVEN WHEN DISCONNECTED FROM THE
UTILITY POWER
. The UPS module interiors are unsafe until the DC power source is disconnected and the
electrolytic capacitors are discharged. After disconnecting the utility power and the DC power, authorized
service personnel should wait at least five minutes for capacitor bleed off before attempting internal access to
the UPS module.
WARNING
l
Servicing and maintenance should be performed by qualified service personnel only.
l
LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open or
protective panels removed. Do not make any assumptions about the electrical state of any cabinet in
the UPS system.
Because each battery string is an energy source in itself, opening the battery circuit breaker does not
de-energize the voltage within the battery string.
DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF
THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING.
If
you suspect that a battery string needs service, contact an Eaton service representative.
If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery
maintenance or contact an Eaton service representative.
Observe these precautions when working on or around batteries:
l
Remove watches, rings, or other metal objects.
l
Use tools with insulated handles.
l
Wear rubber gloves and boots.
l
Do not lay tools or metal parts on top of batteries or battery cabinets.
l
Disconnect the charging source prior to connecting or disconnecting terminals.
l
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with
any part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such
grounds are removed during installation and maintenance.
l
When replacing batteries, use the same number of sealed, lead–acid batteries.
l
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
l
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
l
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Содержание Power Xpert 9395 550/275
Страница 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 27: ...Section 1 Installation...
Страница 28: ......
Страница 100: ...1 2 Power Xpert TM 9395 550 275 UPS 225 550 kVA Installation and Operation Manual 164201716 Rev 8...
Страница 207: ......
Страница 208: ...164201716 8 164201716 8...