UPS Installation Plan and Unpacking
3-2
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
3.2.2
Installation Considerations
The UPS system installation must meet the following guidelines:
l
The system must be installed on a level floor suitable for computer or electronic equipment.
l
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
l
The cabinet can be installed in
line-up-and-match
or
standalone
configurations.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 3-1 and the
size requirements shown in Figure 3-1 through Figure 3-7. Dimensions are in millimeters (inches).
For Field Installed UPM (FI-UPM) weights and dimensions, refer to the
Power Xpert 9395 Field Installed UPM
Mechanical Installation Manual
, listed in paragraph 1.7.
Table 3-1 Includes the weights of the heaviest cabinet configuration. Actual weights may be less due to
installed configuration. Weights are in kilograms (pounds).
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in Table 3-2. Dimensions are in
millimeters (inches).
The basic environmental requirements for operation of the UPS are:
l
Ambient Temperature Range: 0–40ºC (32–104ºF)
l
Recommended Operating Range: 20–25ºC (68–77ºF)
l
Maximum Relative Humidity: 95%, non-condensing
CAUTION
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supercede the UPS requirements. Operating temperatures above the recommended
range will result in decreased battery life and performance, and will reduce or void the battery warranty.
Refer to Eaton’s
Terms and Conditions of Sale with Battery Replacement Coverage
and the
Battery
Replacement Price Book
for more information. These documents can be found at www.eaton.com/
powerquality or contact an Eaton service representative to obtain copies.
The UPS ventilation requirements are shown in Table 3-3.
Table 3-1. UPS Cabinet Maximum Weights
Model
Maximum Weight
kg (lb)
Shipping
Installed
Power Xpert 9395-550/275
930 (2050)
903 (1990)
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18”) minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36”) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
Содержание Power Xpert 9395 550/275
Страница 1: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Power Xpert 9395 UPS 550 275 UPS 225 550 kVA Installation and Operation Manual...
Страница 27: ...Section 1 Installation...
Страница 28: ......
Страница 100: ...1 2 Power Xpert TM 9395 550 275 UPS 225 550 kVA Installation and Operation Manual 164201716 Rev 8...
Страница 207: ......
Страница 208: ...164201716 8 164201716 8...