Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
25
Verify that all input power and control circuits are de-energized and locked out before making connections to
the input bus or other connections inside the unit.
Only a qualified electrician should install power or control wiring or torque the connections.
44..22..33
C
Caabbllee EEnnttrryy//EExxiitt
Cable entry/exit can be from the top or bottom of the unit.
The preferred cable entry/exit is from the bottom, which locates cables closer to the source and output power
busses and ground bus. For top cable entry/exit, cables can be run down along the inside rear of the unit.
Identical removable conduit panels are on the left side of the unit, top and bottom. There are no knock-outs in
the panels; installers must make their own conduit cut-outs. TFA STS units 250-600A can accommodate up to
(8) 4" conduits per conduit panel assuming 6" dia. area per conduit.