94
Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
The first column also displays a text interpretation of the point’s status, such as
OK
,
Low
, or
Not Alarm
.
To set parameters for a point, use the scroll bar to highlight a point. Then touch one of these buttons below the
panel:
•
Set High
sets the upper bound on acceptable measurements
•
Set Low
sets the lower bound on acceptable measurements
•
Calibration
to calibrate the measurement
Clr TX
button clears the transfer counter on the
Home
page, resetting it to zero.
•
Touch
Clear TX
once to clear transfer counter since last
Clear TX
. This is the same as the
Clear
button on
Home
screen
Transfers
panel. The counter is stored in
Xfrs Since Clr
, a point in the Analog Points list.
•
Touch
Clear TX
a second time to clear the cumulative total transfers counter, stored in
Xfers Total
in the
Analog Points list.
Clr PK
clears the peak value measurement for each analog point. Each peak value will be immediately replaced
on the point’s next measurement.
1133..22
EEvveennttss,, A
Allaarrm
mss,, aanndd W
Waavveeffoorrm
m P
Plloottss
All events are recorded in the
Event Log
, such changes of state in a point, a transfer, user login, or an alarm.
The Event Log has 512 entries.
Alarms are specific events listed on the
Alarms
screen and recorded in the
Event Log
.
The STS also records input and output waveforms for selected events, such as transfers or outages, which can
be viewed in the
Plots
screen.
In case of power loss, the STS can continue recording events for approximately 15 seconds, providing
diagnostic information.
1133..22..11 A
Allaarrm
mss
An alarm is signaled when any monitored condition is out of normal specification. Active alarms are signaled in
several ways:
•
The
Home
screen shows Alarm status and gives an alarm count.
•
The Voice Unit of the STS states, “Static Switch, new alarm.”
•
A summary alarm can be signaled when any alarm occurs by one or more of these means:
–
Dry contact
–
SNMP trap
–
Email notification
•
The
Alarms
screen lists a new alarm.
•
The
Event Log
screen adds an alarm.
•
The
Alarms
or
Log
web page shows a new alarm.
1133..22..22 A
Allaarrm
mss S
Sccrreeeenn
Touch the
Alarms
button on the
Home
or other screens to display the
Alarms
screen. When there are alarms
indicated, view the
Alarms
screen at the unit (
) or in a web browser.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...