Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
83
Table 4. Switch Default Settings
Switching – Fast Settings
Switching – Selectors
Parameter
Value
Switch
Value
High Limit
120%
Mode
VSS
Low Limit
80%
Retransfer
Yess
Delay
0 Samples
Ratchet
2%
Switching – Retransfer
Parameter
Value
Switching – Slow Settings
Delay
10 seconds
Parameter
Value
High Limit
110%
Low Limit
90%
Delay
256 Samples
Ratchet
0