Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
Figure 11. Installing on Floor Stand with Side and Rear Brackets
44..22
P
Poow
weerr C
Coonnnneeccttiioonnss
All wiring must comply with NEC and local codes.
Installers are responsible for selecting appropriate wiring.
44..22..11
U
Uppssttrreeaam
m C
Ciirrccuuiitt B
Brreeaakkeerr P
Prrootteeccttiioonn
Customers must provide upstream circuit breaker protection for the input wires to the TFA STS as required by
the National Electric Code (NEC). For additional information, refer to your local codes and the NEC.
44..22..22
P
Poow
weerr S
Soouurrcceess
The two input feeds for the TFA STS should be from separate and independent sources to avoid a common
source failure. The input feeds should nominally be of the same voltage and phase rotation. The input power
wire size should be based on the upstream over current protection device, conforming to NEC and local codes.
Customer ground and phase power connections are made in the bottom left half of the unit. All connections are
made from the front.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...