Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P-164001113—Rev 01
129
–
Low limit = 90% of rated voltage
S
Soouurrccee 22 IInnppuutt A
Allaarrm
mss
•
Voltage phase-phase (A-B, B-C, C-A):
–
High limit = 110% of rated voltage
–
Low limit = 90% of rated voltage
S
STTS
S O
Ouuttppuutt A
Allaarrm
mss
•
Voltage phase-phase (A-B, B-C, C-A):
–
High limit = 110% of rated voltage
–
Low limit = 90% of rated voltage
•
Current by phase (A, B, C):
–
High limit = 80% rated amperage
•
kVA by phase (A, B, C)
–
High limit = 80% of rated phase kVA
•
kVA Total
–
High limit = 80% of rated total kVA