MIB Objects
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
66
Eaton Pulsar MIB
This section contains an overview of MIB definitions for the following MIB files:
l
Eaton Pulsar MIB (MGE MIB)
l
Eaton Pulsar MIB (MGE MIB) for an Environmental Monitoring Probe (EMP)
The Network Card-MS implements the reduced Eaton Pulsar MIB (MGE MIB); only the objects listed in
Table 23 and Table 24are managed. The entire MIB description is available at www.eaton.com/powerquality.
Table 24 lists objects that are managed if there is an optional EMP installed. The Eaton Pulsar MIB trap access
path is 1.3.6.1.4.1.705.1.
xupsTopoMachineCode
Integer
{13.2.0}
xupsTopoUnitNumber
Integer
{13.3.0}
xupsTopoPowerStrategy
Integer
{13.4.0}
Table 23. Eaton Pulsar MIB (MGE MIB) Objects
MIB Object
SNMP Format
Add.path
upsmgIdentFamilyName
String
{1,1,0}
upsmgIdentModelName
String
{1,2,0}
upsmgIdentFirmwareVersion
String
{1,4,0}
upsmgIdentSerialNumber
String
{1,7,0}
upsmgConfigLowBatteryTime
seconds
{4,7,0}
upsmgConfigLowBatteryLevel
%
{4,8,0}
upsmgConfigAutoRestart
1 (yes), 2 (no)
{4,9,0}
upsmgConfigVARating
VA
{4,12,0}
upsmgBatteryRemainingTime
seconds
{5,1,0}
upsmgBatteryLevel
%
{5,2,0}
upsmgBatteryVoltage
deciVolts
{5,5,0}
upsmgBatteryCurrent
deciAmps
{5,6,0}
upsmgBatteryFaultBattery
1 (yes), 2 (no)
{5,9,0}
upsmgBatteryReplacement
1 (yes), 2 (no)
{5,11,0}
upsmgBatteryLowBattery
1 (yes), 2 (no)
{5,14,0}
upsmgBatteryChargerFault
1 (yes), 2 (no)
{5,15,0}
upsmgBatteryLowCondition
1 (yes), 2 (no)
{5,16,0}
upsmgInputPhaseNum
—
{6,1,0}
mginputVoltage_1
DeciVolts
{6,2,1,2,1,0}
mginputVoltage_2
DeciVolts
{6,2,1,2,2,0}
mginputVoltage_3
DeciVolts
{6,2,1,2,3,0}
mginputFrequency_1
DeciHz
{6,2,1,3,1,0}
mginputFrequency_2
DeciHz
{6,2,1,3,2,0}
mginputFrequency_3
DeciHz
{6,2,1,3,3,0}
mginputMinimumVoltage
—
{6,2,1,4,0}
mginputMaximumVoltage
—
{6,2,1,5,0}
Table 22. PowerMIB Objects (Continued)
MIB Object
SNMP Format
Add.path
Содержание Network Card-MS
Страница 1: ...Eaton Network Card MS User s Guide...