Configuring the Card
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
50
Environment Settings
On the Environment Settings page, you can set the temperature and humidity thresholds that trigger a
notification and a graceful shutdown of the protected systems (see Figure 40).
The EMP measures temperature and humidity, and gives the status of the two contacts (used for door,
alarms, or generator unit).
Figure 40. Environment Settings Page (Advanced Parameters Shown)
Configurable environment settings are:
l
Sensor name:
The name given to the EMP. Eaton recommends using a name that identifies the location of
the EMP.
l
Temperature:
Choice of the temperature unit (°C or °F) from the selection box.
l
High threshold (temperature):
If the temperature exceeds the set threshold, a notification is triggered if
enabled. The default value is 40°C / 104°F.
l
Low threshold (temperature):
If the temperature falls below the set threshold, a notification is triggered if
enabled. The default value is 5°C / 41°F.
l
Hysteresis (temperature):
Hysteresis must be set to prevent multiple notifications if temperature fluctuates
around a threshold. The default value is 2°C / -3.6°F.
The high alarm disappears when the value drops below the high threshold minus hysteresis value.
The low alarm disappears when the value returns above the low threshold plus the hysteresis value.
NOTE
If you are not already logged on, you will be prompted to enter your user name and
password before accessing this page.