Configuring the Card
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
39
System Settings
Select
System
from the menu bar to customize the information that displays on the UPS Properties page
(see “UPS Properties” on page 16). The System Settings page opens (see Figure 31).
Figure 31. System Settings Page
Configurable system settings are:
l
UPS Contact:
Enables users to enter the name of the person responsible for UPS administration at IT network
level and/or electrical maintenance. This text field is limited to 49 characters. This field does not appear on
any other Web page. By default, the value is
Computer Room Manager
.
l
UPS Location:
Enables users to enter a description (limited to 31 characters) of the physical location of the
UPS in your installation (for example, Computer Room E1-C066). This text displays on the home page. By
default, its value is
Computer Room
.
l
Default Language:
Enables initialization of the browser language at card connection. Select one of the
available languages (English, French, German, Italian, Spanish, Portuguese, Chinese Simplified, Japanese,
Korean, Chinese Traditional, Russian, or Czech). To change the language of the Web interface pages, restart
your browser after modification.
l
History log interval (sec):
Enables users to specify a measurement save period. Values are from 5 to
99999 seconds, 60 seconds by default.
l
Environment log interval (sec):
Enables users to specify the temperature and humidity measurement save
period. Values are from 60 to 99999 seconds, 300 seconds by default.
l
Save:
Saves any modifications.
l
Reset Communication:
Enables users to perform a remote reboot of the card without modifying the
configuration. Specifying this action is required for any changes you made on the Network Settings page. To
ensure security, this operation requires admin user name and password.
l
Factory Reset:
Enables users to restore the default configuration of all the card’s parameters.
If the
Keep TCP/IP parameters
checkbox is selected, the IP address, subnet mask, gateway, and BOOTP/DHCP
retain their values.
To ensure security, this operation requires admin user name and password. By default, user name and
password are both
admin
.