Technical Data
MVX9000 User Manual
A-5
Technical Data
Table A-3: MVX9000 460V Specifications
Voltage Class
460V Series
Model Number MVX_ _ _AO-4
001
002
003
005
007
010
Max. Applicable Motor Output (kW)
0.75
1.5
2.2
3.7
5.5
7.5
Max. Applicable Motor Output (hp)
1
2
3
5
7-1/2
10
Output Rating
Rated Output Capacity
(kVA)
2.3
3.1
3.8
6.2
9.9
13.7
Rated Output Current (A)
3
4
5
8.2
13
18
Max. Output Voltage (V)
Proportional to input voltage
Rated Frequency (Hz)
0.1 to 400 Hz
Input Rating
Rated Voltage
342 to 528V AC
Frequency Tolerance
50/60 Hz ± 5%
3-phase Rated Input
Current
4.2
5.7
6
8.5
14
23
Control
Characteristics
Control System
SPWM (Sinusoidal Pulse Width Modulation)
Output Frequency
Resolution
0.1Hz
Overload Endurance
150% of rated current for 1 minute
Acceleration/Deceleration
Time
0.01 to 600.00 seconds
Torque Characteristics
Including the auto-torque, auto-slip compensation; starting
torque can be 150% at 1 Hz in vector, 3 Hz in V/F
V/F Pattern
Adjustable V/F pattern or sensorless vector
Stall Prevention Level
Set to percentage of rated current
Operating
Characteristics
Frequency
Setting
Keypad
Set by UP, DOWN keys or potentiometer
External
Signal
Potentiometer-5 kW/0.5W, 0 to +10V DC or 0 to +5V (Input
impedance 47 kW), RS-485 interface, 4 to 20 mA (Input
impedance 250W), 1 to 7 step speeds, PID feedback
Operation
Setting
Signal
Keypad
Set by START, STOP, RIGHT and LEFT keys
External
Signal
FWD/STOP, REV/STOP (RUN/STOP, FWD/REV), 3-wire control,
serial communication
Digital Input Signal
Multi-step selections 1 to 7, Jog, acceleration/deceleration
inhibit, first/second acceleration/deceleration switch, counter,
External BB (Pause), PLC operation. Terminals have 5V
potential and must be brought to DC common to enable
(Sinking).
Digital Output Indication
Operating, Up to frequency, Desired frequency, Non-zero B.B.,
Abnormal indication, Local/Remote indication, PLC, Low
Voltage.
Analog Output Signal
Analog frequency/current signal output.
Содержание MVX9000 Series
Страница 2: ......
Страница 4: ...ii MVX9000 User Manual This page intentionally left blank ...
Страница 16: ...xiv MVX9000 User Manual This page intentionally left blank ...
Страница 124: ...Group 90 Communications 5 76 MVX9000 User Manual Descriptions of Parameter Settings This page intentionally left blank ...
Страница 133: ...MVX9000 User Manual A 1 Technical Data Appendix A Inside this chapter Technical Data Technical Data A 2 ...
Страница 139: ...MVX9000 User Manual B 1 Parameter Tables Appendix B Inside this chapter Parameter Tables MVX9000 Parameter Listing B 2 ...
Страница 168: ...Extension Input Output P N MVXEIO C 14 MVX9000 User Manual Accessories This page intentionally left blank ...
Страница 169: ...MVX9000 User Manual D 1 Dimensions Appendix D Inside this chapter Dimensions Digital Keypad D 2 Drives D 4 ...
Страница 174: ...D 6 MVX9000 User Manual Dimensions This page intentionally left blank ...
Страница 178: ...E 4 MVX9000 User Manual Declaration of Conformity This page intentionally left blank ...
Страница 179: ......