MVX9000 Parameter Listing
B-10
MVX9000 User Manual
Parameter T
ables
Table B-5: 60 — MOTOR CONTROL
Modbus Groups Page #
Description
Range
Default
User
Settings
0400H
60.01
5-50
Motor Rated Current
30 to 120%
FLA
0401H
60.02
5-50
Motor No-Load
Current
00 to 99%
0.4*
FLA
0402H
60.03
5-50
Motor Auto Tuning
00: Disable
00
01: DC test
02: DC test and no load test
0403H
60.04
5-50
Motor’s Stator
Resistance
(calculated via auto
tune or entered
manually)
00 to 65535 m Ohms
00
0404H
60.05
5-51
DC Braking Current
Level
00 to 100%
00
0405H
60.06
5-51
DC Braking Time
upon Start-up
0.0 to 5.0 sec
0.0
0406H
60.07
5-51
DC Braking Time
upon Stopping
0.0 to 25.0 sec
0.0
0407H
60.08
5-52
Frequency-point for
DC Braking
0.0 to 60.0 Hz
0.0
0408H
60.09
5-52
Torque
Compensation
00 to 10
00
0409H
60.10
5-53
Slip Compensation
0.00 to 10.00
0.0
040AH
60.11
5-53
PWM Carrier
Frequency
115V/230V/460V: 1 to 15 KHz
9
575V: 1 to 10 KHz
6
Содержание MVX9000 Series
Страница 2: ......
Страница 4: ...ii MVX9000 User Manual This page intentionally left blank ...
Страница 16: ...xiv MVX9000 User Manual This page intentionally left blank ...
Страница 124: ...Group 90 Communications 5 76 MVX9000 User Manual Descriptions of Parameter Settings This page intentionally left blank ...
Страница 133: ...MVX9000 User Manual A 1 Technical Data Appendix A Inside this chapter Technical Data Technical Data A 2 ...
Страница 139: ...MVX9000 User Manual B 1 Parameter Tables Appendix B Inside this chapter Parameter Tables MVX9000 Parameter Listing B 2 ...
Страница 168: ...Extension Input Output P N MVXEIO C 14 MVX9000 User Manual Accessories This page intentionally left blank ...
Страница 169: ...MVX9000 User Manual D 1 Dimensions Appendix D Inside this chapter Dimensions Digital Keypad D 2 Drives D 4 ...
Страница 174: ...D 6 MVX9000 User Manual Dimensions This page intentionally left blank ...
Страница 178: ...E 4 MVX9000 User Manual Declaration of Conformity This page intentionally left blank ...
Страница 179: ......