MVX9000 Parameter Listing
MVX9000 User Manual
B-7
Parameter T
ables
Table B-4: 50 — DRIVE CONTROL (Continued)
Modbus Groups Page #
Description
Range
Default
User
Settings
030BH
50.12
5-34
Acceleration Time 1
0.01 to d 600.0 sec
10.00
030CH
50.13
5-34
Deceleration Time 1
0.01 to d 600.0 sec
10.00
030DH
50.14
5-34
Acceleration Time 2
0.01 to d 600.0 sec
10.00
030EH
50.15
5-35
Deceleration Time 2
0.01 to d 600.0 sec
10.00
030FH
50.16
5-35
Transition Point for
Acceleration 1 to
Acceleration 2
0.0:Disable 0.0
Above min freq.: Enable, 0.0
to 400.0 Hz
0310H
50.17
5-36
Transition Point for
Deceleration 1 to
Deceleration 2
0.0:Disable 0.0
Above min freq.: Enable, 0.0
to 400.0 Hz
0311H
50.18
5-36
Acceleration S-curve
00 to 07
00
0312H
50.19
5-36
Deceleration S-curve
00 to 07
00
0313H
50.20
5-37
Jog Acceleration /
Deceleration Time
0.01 to d 600.0 sec
1.00
0314H
50.21
5-37
Jog Frequency
0.1 to 400.0 Hz
6.0
0315H
50.22
5-37
Reserve Operation
Enable
00: Enable Reverse Operation 00
01: Disable Reverse
Operation
0316H
50.23
5-38
Momentary Power
Loss (Ride Through)
00: Stop operation after
momentary power loss
00
01: Continue operation after
momentary power loss,
speed search from Speed
Reference
02: Continue operation after
momentary power loss,
speed search from Minimum
Speed
0317H
50.24
5-38
Maximum Allowable
Power Loss Time
0.3 to 5.0 sec
2.0
0318H
50.25
5-38
Pause Time after
Momentary Power
Loss
0.3 to 10.0 sec
0.5
0319H
50.26
5-39
Maximum Speed
Search Current Level
30 to 200%
150
031AH
50.27
5-39
Upper Limit of
Output Frequency
0.1 to 400.0 Hz
400.0
031BH
50.28
5-39
Lower Limit of
Output Frequency
0.0 to 400.0 Hz
0.0
031CH
50.29
5-40
Skip Frequency 1
0.0 to 400.0 Hz
0.0
031DH
50.30
5-40
Skip Frequency 2
0.0 to 400.0 Hz
0.0
031EH
50.31
5-40
Skip Frequency 3
0.0 to 400.0 Hz
0.0
031FH
50.32
5-40
Skip Frequency
Bandwidth
0.1 to 20.0 Hz (0.0 = Disable)
0.0
0320H
50.33
5-41
Auto Restart After
Fault
00 to 10
00
0321H
50.34
5-41
PID Set Point
Location
00: Disable
01: Keypad (based on 20.03
setting)
02: AI1 (external 0 – 10V)
03: AI2 (external 4 – 20 mA)
04: PID set point (50.43)
00
Содержание MVX9000 Series
Страница 2: ......
Страница 4: ...ii MVX9000 User Manual This page intentionally left blank ...
Страница 16: ...xiv MVX9000 User Manual This page intentionally left blank ...
Страница 124: ...Group 90 Communications 5 76 MVX9000 User Manual Descriptions of Parameter Settings This page intentionally left blank ...
Страница 133: ...MVX9000 User Manual A 1 Technical Data Appendix A Inside this chapter Technical Data Technical Data A 2 ...
Страница 139: ...MVX9000 User Manual B 1 Parameter Tables Appendix B Inside this chapter Parameter Tables MVX9000 Parameter Listing B 2 ...
Страница 168: ...Extension Input Output P N MVXEIO C 14 MVX9000 User Manual Accessories This page intentionally left blank ...
Страница 169: ...MVX9000 User Manual D 1 Dimensions Appendix D Inside this chapter Dimensions Digital Keypad D 2 Drives D 4 ...
Страница 174: ...D 6 MVX9000 User Manual Dimensions This page intentionally left blank ...
Страница 178: ...E 4 MVX9000 User Manual Declaration of Conformity This page intentionally left blank ...
Страница 179: ......