![Eaton MVX9000 Series Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/eaton/mvx9000-series/mvx9000-series_user-manual_3986462043.webp)
Fuses and Circuit Breakers
MVX9000 User Manual
4-7
Start-Up
Procedures
Fuses and Circuit Breakers
The MVX9000 does not provide branch short circuit protection. This product
should be installed with either input fuses or an input circuit breaker. National
and local industrial safety regulations and/or electrical codes may determine
additional requirements for these installations.
Note:
To guard against personal injury and/or equipment damage caused by
improper fusing or circuit breaker selection, use only the recommended line
fuses/circuit breakers specified in this section.
Fusing
The MVX9000 has been UL tested and approved for use with input fuses. The
ratings in
Table 4-2
are the minimum recommended values for use with each
drive rating. The devices listed in this table are provided to serve as a guide.
Other devices which meet the requirements of UL508C and UL489 with similar
trip characteristics may be used in order to meet local or national electrical
codes.
Manual Motor Starters/UL489 Circuit Breakers
When using manual motor starters or UL489 rated circuit breakers, follow
manufacturer’s recommended guidelines for installation.
Table 4-2: Fuse Specification Chart
Model
Input
Current
(A)
Output
Current
(A)
Line Fuse
MMP Catalog
Number
Recommended
Contactor
Catalog Number
I(A)
Buss
F25A0-1
6
1.6
15
JJN-15
XTPR010BC1
XTCE009B_
F50A0-1 9
2.5
30
JJN-30
XTPR016BC1
XTCE012B_
001A0-1
16
4.2
50
JJN-50
XTPR020BC1
XTCE025C_
F50A0-2 (1p)
6.3
2.5
25
JJN-25
XTPR6P3BC1
XTCE009B_
F50A0-2 (3p)
3.2
2.5
10
JJN-10
XTPR004BC1
XTCE009B_
001A0-2 (1p)
11.5
5
45
JJN-45
XTPR016BC1
XTCE012B_
001A0-2 (3p)
6.3
5
20
JJN-20
XTPR010BC1
XTCE009B_
002A0-2 (1p)
15.7
7
60
JJN-60
XTPR020BC1
XTCE025C_
002A0-2 (3p)
9
7
25
JJN-25
XTPR016BC1
XTCE012B_
003A0-2 (1p)
27
10
100
JJN-100
XTPR032BC1
XTCE032C_
003A0-2 (3p)
15
10
40
JJN-40
XTPR010BC1
XTCE018C_
005A0-2
19.6
17
60
JJN-60
XTPR025BC1
XTCE025C_
007A0-2
28
25
100
JJN-100
XTPR032BC1
XTCE032C_
001A0-4
4.2
3
10
JJS-10
XTPR004BC1
XTCE009B_
002A0-4
5.7
4
15
JJS-15
XTPR6P3BC1
XTCE009B_
003A0-4
6
5
20
JJS-20
XTPR010BC1
XTCE009B_
Содержание MVX9000 Series
Страница 2: ......
Страница 4: ...ii MVX9000 User Manual This page intentionally left blank ...
Страница 16: ...xiv MVX9000 User Manual This page intentionally left blank ...
Страница 124: ...Group 90 Communications 5 76 MVX9000 User Manual Descriptions of Parameter Settings This page intentionally left blank ...
Страница 133: ...MVX9000 User Manual A 1 Technical Data Appendix A Inside this chapter Technical Data Technical Data A 2 ...
Страница 139: ...MVX9000 User Manual B 1 Parameter Tables Appendix B Inside this chapter Parameter Tables MVX9000 Parameter Listing B 2 ...
Страница 168: ...Extension Input Output P N MVXEIO C 14 MVX9000 User Manual Accessories This page intentionally left blank ...
Страница 169: ...MVX9000 User Manual D 1 Dimensions Appendix D Inside this chapter Dimensions Digital Keypad D 2 Drives D 4 ...
Страница 174: ...D 6 MVX9000 User Manual Dimensions This page intentionally left blank ...
Страница 178: ...E 4 MVX9000 User Manual Declaration of Conformity This page intentionally left blank ...
Страница 179: ......