manualshive.com logo in svg
background image

8

Instruction Booklet 

IB02402001E

December 2010

Instructions for the Eaton Type

MPCV Network Protection Relay

EaToN CoRPoRaTIoN www.eaton.com

For more information visit: www.EatonElectrical.com

IB02402001E

Instruction Bulletin

Page

 8

Effective:  September 2004

Instruction for the 

Cutler-Hammer Type MPCV

Network Protection Relay

Instructions for the Type MPCV-D Relay used on 

Type CMD, 216 Volt, Network Protectors

I. Installation

a. Remove the CN-33 master relay and the CNJ phasing 

relay, as well as the BN relay. Install a BN dummy or 

jack plate if a BN relay was removed. If there is no BN 

relay, but the position is taken by a BN dummy plate 

or BN jack plate. DO NOT REMOVE THE BN DUMMY 

OR JACK PLATE.

b. Install Style No. 508B559G01 phasing jumper plate in 

the location of the CNJ phasing relay.

c. Install the Type “MPCV”, Style No. 6417C82G01, in 

location of the CN-33 master relay.

If the network protector is wired for an electromechanical 

watt-var relay, the wiring must be changed over to the watt 

trip characteristic. Refer to l.B. 35-552, Pages 36 – 37. The 

MPCV can be set for a watt or watt-var trip characteristic. 

Although its input is connected as a watt characteristic, the 

change to watt-var is accomplished by changing the “WV” 

set point from OFF to ON.

II. Calibration

a. Connect a network protector portable test kit to the 

network protector. Specific instructions for performing 

this task are contained in I.B 35-556.

b. Power-up the test kit in the relay test mode. Set the 

test kit to zero phasing volts, either in phase or at 60 

degrees. Once the test set is powered with zero phas-

ing volts, (the Variac set to zero), the MPCV Relay will 

advance to float. This indicates that the power-up 

mode of the relay is correct. Connect the setting 

pendant to the relay, by plugging the setting pendant 

into the exposed 9 pin “D” connector.

Note: Note the connector and plug are polarized to prevent improper 

connection.

c. De-press the EDIT key to begin the “Edit” mode.

Note: At this point, the amber float light will begin to flash and the 

first set point, with its loaded value, will appear on the display of the 

pendant. While in this mode, the relay will not change state and is 

effectively inoperable for normal relay functions.

d. To change a set point, de-press the large or small, 

up or down arrow keys for large or small increment 

adjustments until the desired value appears on the dis-

play.

e. Once the desired value is obtained, de-press the NEXT 

key. The program will automatically step to the next 

set point to be set.

f. Continue to adjust each set point by repeating Steps d 

and e above until all the set points have been 

satisfied.

Note: The starting set point is HZ=60. Refer to the settings on Page 5.

Note: When setting the master line values on a 216 volt relay being 

used on a 480 volt system, the phasing voltage necessary to close 

the relay is not directly indicated. The relay calibration on this 

system is determined by multiplying the master line setting by 2.2. 

Refer to Table 2.

Table 2. Overvoltage Close Values for 480 Volt Units Using Potential 

Transformers

Approximate phasing volts required to close the relay 

contacts, in phase, equals 2.2 times the “MPC” relay setting,

Note: If the BN time delay is not required, make certain that the time 

delay is set to zero (TD=0).

g. Once ALL the set points have been set, de-press the 

SAVE key. The display will go blank and the float light 

will remain constantly ON.

Note: If changing only one or two of the set points, the entire menu 

need not be reviewed prior to de-pressing the SAVE key.

h. Remove the pendant from the relay; the relay 

calibration is now complete.

Note: On all 216 volt units, the master line (ML) value equals the 

phasing volts required to close the relay contacts, in phase.

 

WARNING

BEFORE PROCEEDING FURTHER, MAKE CERTAIN THAT THE 

NETWORK PROTECTOR IS DE-ENERGIZED AND IS 

WITHDRAWN FROM THE ENCLOSURE ON THE EXTENSION 

RAILS. SPECIFIC INSTRUCTIONS FOR PERFORMING THESE 

TASKS ARE CONTAINED IN THE LATEST REVISION OF 

INSTRUCTION BOOK 1.B. 35-552. THOSE INSTRUCTIONS 

MUST BE CONSULTED AND FOLLOWED.

Overvoltage Close Value Desired

Master Line (ML)

Setting

At 60 Degrees

In Phase

  .70 V

1.45 V

2.13 V

  .45 V

  .90 V

1.32 V

ML =   .20

ML =   .40

ML =   .60

2.85 V

3.55 V

4.28 V

1.75 V

2.20 V

2.60 V

ML =   .80

ML = 1.00

ML = 1.20

5.00 V

5.70 V

6.40 V

3.05 V

3.50 V

4.00 V

ML = 1.40

ML = 1.60

ML = 1.80

 

WARNING

DO NOT FUNCTIONALLY OPERATE (TRIP AND CLOSE) THE 

NETWORK PROTECTOR BREAKER WITH THE SETTING 

PENDANT CONNECTED INTO THE RS-232 PORT. 

CALIBRATION OF THE MPCV MUST BE MADE WITH THREE-

PHASE POTENTIAL AND ONLY AFTER THE FLOAT LIGHT IS 

ILLUMINATED. AT THE END OF THE CALIBRATION 

SEQUENCE, THE PENDANT MUST BE REMOVED PRIOR TO 

OPERATION OF THE BREAKER.

Содержание MPCV Series

Страница 1: ... more information visit www EatonElectrical com Instruction for the Cutler Hammer Type MPCV Network Protection Relay Instruction Bulletin Supersedes I B 35 581B Pages 1 28 dated October 1997 MPCV Communications Relay for Cutler Hammer Westinghouse Network Protectors Rear View MPCV Communications Relay for General Electric Network Protectors Rear View ...

Страница 2: ...RED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES If further information is required the Eaton Corporation should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED ...

Страница 3: ... controlled relays are designed to replace the Type CN 33 electromechanical master relay the Type CNJ electromechanical phasing relay and the Type BN electromechanical desensitizing relay The MPC series relays use the same voltage and current inputs as do the electromechanical equivalent They also continually moni tor voltage across an open breaker and current through a closed breaker and perform ...

Страница 4: ...lose if V1N is less than 1 P U and V2N is less than 06 P U and V1P exceeds 8 P U Note that as stated before if V2P exceeds 2 P U then the trip contact will close indicating crossed phases on either the transformer side or the network side Also note that if the phases are crossed on both the transformer and the net work side V2P could be very close to or equal to zero but the trip contact will clos...

Страница 5: ...ckwise system then the selection must be changed to CBA ON This can be changed by entering the large up or down arrow keys Make your selection and enter the NEXT key to view the next line Note If the wrong sentence is selected the relay upon power up will give a trip indication CT RATIO This refers to the current transformer CT primary rating For example an 1875 ampere network protector will have ...

Страница 6: ...ping Sets relay to respond on RT set ting only 2 TD 0 25 to 300 seconds This is selectable in 20 sec ond increments when using the large up and down arrow keys and is selectable in 0 25 second increments when using the small up and down arrow keys This represents time delay on tripping in seconds Sets the relay to respond on RT setting with Time Delay and respond instantaneously to OC setting 3 TD...

Страница 7: ...nter the NEXT key to view the next line Note If a MPCV Relay is provided with communications turned OFF communications can be activated in the field by a qualified Eaton ser vice representative INCOM SETPT ON The default setting is ON with the capability to change to OFF If the INCOM SETPT OFF this prevents a user from remotely changing set points through the IMPACC Series III or PowerNet software...

Страница 8: ...int de press the large or small up or down arrow keys for large or small increment adjustments until the desired value appears on the dis play e Once the desired value is obtained de press the NEXT key The program will automatically step to the next set point to be set f Continue to adjust each set point by repeating Steps d and e above until all the set points have been satisfied Note The startin...

Страница 9: ...accomplished by changing the WV set point from OFF to ON D Proceed to Section II of the MPCV D instructions calibration section Refer to Page 8 Note For CM 22 or CMR breakers which have been rewired to accept the MPCV phase 4 or phase 5 relay the Type MPCV 2X is a direct replacement Style Number is 6417C83G03 Table 3 Terminal Configurations Figure 3 Cutler Hammer Relay Note For Communication with ...

Страница 10: ...struc tions given in Note 1 of the time delay installation notes For General Electric Network Protectors manufactured after October 1982 the Type CAN or CHN master relay was replaced by the Type SSNPR analog solid state relay and the above four wiring changes will have been made Once the MPCV GE Relay has been installed and all of the wiring changes have been performed and or confirmed proceed to ...

Страница 11: ...ug is necessary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground 3 Watt var function is incorporated within the MPCV Relay When applying an MPCV Relay with or without watt var function add...

Страница 12: ...ary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground MG14 277 480 V with Time Delay 1 For delayed sensitive operation using electromechanical relays Type CHN CHL add TD device and jumpers ...

Страница 13: ...ted OFF when no trip condition is detected CLOSE Indicator ON until phasing voltage no longer satisfies the ML PL settings OFF when no close condition is detected FLOAT Indicator Flashes when pendant is active ON when the relay is energized and not commanding a Trip nor Close FAIL Indicator ON when micro controller is not operating properly Trip and Close Contacts Rating The relay contacts are cap...

Страница 14: ...ary Input Enable On Off Enable Disable Contact NO Normally Open NC Normally Closed Tolerances The relay shall operate within the tolerance shown while operating over the normal temperature range of 20 C to 110 C and the normal network voltage range of 12 to 190 Vac Sensitive Trip 5 of setting or 0 5 mA whichever is greater Instantaneous Trip 5 of setting or 0 1 A whichever is greater Insensitive T...

Страница 15: ...ected in the transformer terminals or in the network terminals 4 Incorrect phase sequence is detected 5 Rolled phase is detected 6 Any one phase is dead in the transformer or network terminals Table 5 Trip Amperage as a Function of Percent of CT Primary from 05 5 Note This table represents only that region from 05 5 of the CT primary The relay can be adjusted up to the 5 level if desired The amper...

Страница 16: ...an cause damage to those device or devices the relay an injury or a fire Make sure that each designated wire is connected to the correct terminal Re check the CT connections after installing the relay and before energizing the breaker When operating the breaker without the relay terminate each pair of the disconnected CT wires by shorting the ends and securing this from any other energized wires U...

Страница 17: ... key FSK technology and has the following benefits 1 Devices are easily daisy chained with inexpensive shielded twisted pair cable 2 Noise immunity and signal integrity verification to ensure reliable data transfer 3 Up to 1 000 devices are supported on Main Network 4 Up to 99 devices are supported in Subnetwork 5 Up to 1 000 devices may be monitored and controlled from a single location 6 Distanc...

Страница 18: ...or 5 CD ROM for CD ROM installation 6 High density 3 5 inch disk drive Monitoring PowerNet provides energy management operational and equipment status information and offer the user the capa bility of 1 Real time information 2 Data printout 3 Internal environment of the network protector enclosure 4 Vault environment Control PowerNet provides multiple network protectors controlled from a remote lo...

Страница 19: ...Supports up to 10 000 feet distance and 1 000 relays NetLink a computer based device that 1 Translate INCOM into Standard Ethernet TCP IP messages or ModBus RTU 2 Acts as a data logger to store events and trend information Commercial Translators There are devices available in the market that can translate INCOM protocol format to 1 SES92 format 2 DNP3 format System Capacity The Master PC device se...

Страница 20: ... The SUBMASTER is the only device on a subnetwork which issues command signals It appears as a single device to the Main Network and responds to commands by the MASTER The NODE is an IMPACC compatible device that receives commands from the MASTER and or SUBMASTER and executes the command The MAIN RUN is a length of cable more than 200 feet 61 m on which the MASTER or SUBMASTER resides The EOLTR an...

Страница 21: ...l or less than 64 3 There are three levels of subtaps allowed with a restriction of 4 feet 1 2 m on the third level Figure 10 Complex Tap The MAIN NETWORK consist of the Main Run connected to a MASTER as well as all the cabling in Simple Taps and Complex Taps connected to the Main Run The SUBNETWORK consist of the Main Run connected to a SUBMASTER as well as all the cabling in Simple Taps and Comp...

Страница 22: ...CV Network Protection Relay The CABLE STAR is created when the MASTER or SUBMASTER is connected to more than one Main Run Figure 12 Cable Star The CABLE BRANCH is created when splitting one or more Main Runs Figure 13 Cable Branch Master EOLTR EOLTR Simple Tap Main Run Main Run EOLTR EOLTR Simple Tap Main Run Main Run Node 4 Node 3 Node 1 Node 2 Node 5 Node 6 Node N Node 7 EOLTR Simple Tap Main Ru...

Страница 23: ...inal blocks when splicing All devices EOLTR Simple Taps and Complex Taps should be placed in parallel across the cable 5 Cable Shielding Cable shielding and outer jacket should not be stripped longer than 1 1 2 inches 38 1 mm Use the three pole terminal blocks at tap points to ensure a continuous metallic shield ground path Mechanically crimp sleeves on to the two shield path drain wires The cable...

Страница 24: ...oltage AND the positive sequence phasing voltage indicates a de energized network and feeder system condition Bus voltages and the bus connections to the MPCV should be verified O Trip Var Trip Reverse current exceeded RT set point for at least 2 power cycles instantaneous Watt Var Trip characteristic WV ON TD 0 and the reverse current phasor fell in the var region 60 degree portion of the overall...

Страница 25: ...place Note Kit 8231A80G07 is available for converting from 480 V Electromechanical Relays and includes the relay CNJ Jumper Plate Wiring Kit Instruction Book and 3 Phase Potential Transformer Note Units with energized CTs can be changed to GRD Y connected CTs based on instructions noted in Relay Conversion Guidelines on Page 26 Table 11 MPCV GE 216 V Relay 6417C84G01 Kit 8231A80G06 For use in GE M...

Страница 26: ...ditional lengths of AWG 16 Teflon coated wire One wire should go to GROUND and the other wire should be connected to terminal 5 on the relay connector Note If the relay responds during test in a close mode at 180 degrees reverse current or a trip mode in phase or at 60 degrees then the CTs are connected in reverse polarity Reverse the CT connections on all three phases to correct this situation En...

Страница 27: ...on Relay eaton corporation www eaton com IB02402001E For more information visit www EatonElectrical com Instruction Bulletin Effective September 2004 Page 27 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Curve Drawings Figure 14 Straight Closing Curve Phasing Line ML 0 270 90 180 ...

Страница 28: ...ction Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 28 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 15 Circular Closing Curve L H M L PHASING LINE 0 270 90 180 M L ...

Страница 29: ...region by additional 10 degrees to compensate for CT phase angle error during fault conditions and high trans former X to R ratios allowing the relay to trip whenever the positive sequence component of the current leads the positive sequence line to ground volt age by more than 85 degrees In com parison the traditional watt trip characteristic would allow closure only if this angle is more than 95...

Страница 30: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 31: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 32: ... agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL...

Отзывы: