Instruction for the 

Cutler-Hammer Type MPCV

Network Protection Relay

Characteristic Line

Straight Line (Standard) — Used on typical loaded system.

Circular — Used on lightly loaded system.

Pump Protection

This feature shall protect the network protector from exces-

sive close-trip (pumping) operation within a given time.  When 

the protector number of operations is equal or greater than 

the breaker cycles within the pump time setting, the relay 

shall initiate a trip and lock open to inhibit a close 

operation until the reset time expires.

Manual (Remote) Close

Initiated via PowerNet by a PRC (Protective Remote Close) 

command. The relay will relax the close criteria by effectively 

setting the ML to near zero volts and expand the phasing 

line(s) to the setpoint boundary for up to 10 seconds or until 

closure is initiated. Upon expiration of the 10-second PRC 

window or closure initiation, the original ML and PL pro-

grammed settings are restored.  The Anti-Pump Protection 

must be off to complete the PRC operation.

Dead Network

The relay shall initiate an instantaneous closure when the net-

work voltage is equal or less than the Dead Network setting.

Communication

Medium

INCOM with 1500 volt isolation via 3-pin connector and a 

twisted pair cable.

Standard pendant via DB9 connector.

Protocol

INCOM — a Master/Slave two-way communication system.  

The master (PC that has an RS-232c communication port) 

requires the use of a MINT (Master INCOM Network Translator) 

to convert the 33-bit binary messages to and from a 10 byte 

ASC

II

 encoded hexadecimal RS-232c messages.

Modulation: Carrier Based, FSK

Frequency: 115.2 KHz logical “one”, 92.16 KHz logical “zero”.

Message: 33 bits.

Start Bit: 2 bits.

Control Bit: 1 bit.

Data: 24 bits.

BHC Check: 5 bits code.

Safety

The relay shall not permit any closure in automatic mode when:

1. Line-to-Ground fault is detected in any of the transformer 

or network terminals.

2. Line-to-Line fault is detected between the transformer 

terminals or network terminals.

3. Crossed-phase is detected in the transformer terminals or 

in the network terminals.

4. Incorrect phase sequence is detected.

5. Rolled phase is detected.

6. Any one phase is dead in the transformer or network 

terminals.

Table 5. Trip Amperage as a Function of Percent of CT Primary, 

from .05 – 5%

Note: This table represents only that region from .05 – 5% of the CT 

primary. The relay can be adjusted up to the 5% level if desired. The 

ampere values listed are based upon the standard rating of current 

transformers being applied to the appropriate rating of network 

protector.

MPCV Relay

Addendum to IB-35-581B

The following set points are additions to IB-35-581B dated 

October, 1997.

These set points appear on the pendant screen between the 

INCOM ADR and YEAR set points, but were not noted on 

Page 8 of IB-35-581B.

INCOME CODE=1999

If the INCOM CODE displays 1999, this indicates that the 

relay is communications ready. If a hexadecimal value 

appears, this indicates that relay communications have been 

turned off.

Note: If a MPCV Relay is provided with communications turned off, 

communications can be activated in the field by a qualified Eaton ser-

vice representative.

INCOM SETPT=ON

The default setting is ON with the capability to change to 

OFF. If the INCOM SETPT=OFF, this prevents a user from 

remotely changing set points through the IMPACC Series 

III

 

or PowerNet software.

INCOM OPEN=ON

The default setting is ON with the capability to change to 

OFF. If the INCOM OPEN=OFF, this prevents a user from 

remotely opening the breaker through the IMPACC Series 

III

 

or PowerNet software. This also effectively disables the set 

point download as well, as the breaker must be ROBO’d 

(Remote Open, Blocked Open) before any set points can suc-

cessfully be downloaded. 

INCOM CLOSE=ON

If the INCOM CLOSE=ON, this permits a protected remote 

close status which reduces the ML value to its operational 

lowest point for a time period of 10 seconds. This requires 

PowerNet software to enable this feature. Changing this 

setting to OFF locks out the remote close feature.

For more information on Cutler-Hammer Network Protectors, 

please contact us at 1-800-525-6821.

Percent

of CT 

Primary

Network Protector Rating
800

1200

1600/

1875

2000/

2250

2500/

2825

3000/

3500

.05

.07

.1

0.4

0.56

0.8

0.60

0.84

1.20

0.80

1.12

1.60

  1.00

  1.40

  2.00

  1.25

  1.75

  2.50

  1.50

  2.10

  3.00

.2

.3

.4

.5

1.6

2.4

3.2

4.0

2.40

3.60

4.80

6.00

3.20

4.80

6.40

8.00

  4.00

  6.00

  8.00

10.00

  5.00

  7.50

10.00

12.50

  6.00

  9.00

12.00

15.00

Trip Amperage

Содержание MPCV Series

Страница 1: ... more information visit www EatonElectrical com Instruction for the Cutler Hammer Type MPCV Network Protection Relay Instruction Bulletin Supersedes I B 35 581B Pages 1 28 dated October 1997 MPCV Communications Relay for Cutler Hammer Westinghouse Network Protectors Rear View MPCV Communications Relay for General Electric Network Protectors Rear View ...

Страница 2: ...RED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES If further information is required the Eaton Corporation should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED ...

Страница 3: ... controlled relays are designed to replace the Type CN 33 electromechanical master relay the Type CNJ electromechanical phasing relay and the Type BN electromechanical desensitizing relay The MPC series relays use the same voltage and current inputs as do the electromechanical equivalent They also continually moni tor voltage across an open breaker and current through a closed breaker and perform ...

Страница 4: ...lose if V1N is less than 1 P U and V2N is less than 06 P U and V1P exceeds 8 P U Note that as stated before if V2P exceeds 2 P U then the trip contact will close indicating crossed phases on either the transformer side or the network side Also note that if the phases are crossed on both the transformer and the net work side V2P could be very close to or equal to zero but the trip contact will clos...

Страница 5: ...ckwise system then the selection must be changed to CBA ON This can be changed by entering the large up or down arrow keys Make your selection and enter the NEXT key to view the next line Note If the wrong sentence is selected the relay upon power up will give a trip indication CT RATIO This refers to the current transformer CT primary rating For example an 1875 ampere network protector will have ...

Страница 6: ...ping Sets relay to respond on RT set ting only 2 TD 0 25 to 300 seconds This is selectable in 20 sec ond increments when using the large up and down arrow keys and is selectable in 0 25 second increments when using the small up and down arrow keys This represents time delay on tripping in seconds Sets the relay to respond on RT setting with Time Delay and respond instantaneously to OC setting 3 TD...

Страница 7: ...nter the NEXT key to view the next line Note If a MPCV Relay is provided with communications turned OFF communications can be activated in the field by a qualified Eaton ser vice representative INCOM SETPT ON The default setting is ON with the capability to change to OFF If the INCOM SETPT OFF this prevents a user from remotely changing set points through the IMPACC Series III or PowerNet software...

Страница 8: ...int de press the large or small up or down arrow keys for large or small increment adjustments until the desired value appears on the dis play e Once the desired value is obtained de press the NEXT key The program will automatically step to the next set point to be set f Continue to adjust each set point by repeating Steps d and e above until all the set points have been satisfied Note The startin...

Страница 9: ...accomplished by changing the WV set point from OFF to ON D Proceed to Section II of the MPCV D instructions calibration section Refer to Page 8 Note For CM 22 or CMR breakers which have been rewired to accept the MPCV phase 4 or phase 5 relay the Type MPCV 2X is a direct replacement Style Number is 6417C83G03 Table 3 Terminal Configurations Figure 3 Cutler Hammer Relay Note For Communication with ...

Страница 10: ...struc tions given in Note 1 of the time delay installation notes For General Electric Network Protectors manufactured after October 1982 the Type CAN or CHN master relay was replaced by the Type SSNPR analog solid state relay and the above four wiring changes will have been made Once the MPCV GE Relay has been installed and all of the wiring changes have been performed and or confirmed proceed to ...

Страница 11: ...ug is necessary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground 3 Watt var function is incorporated within the MPCV Relay When applying an MPCV Relay with or without watt var function add...

Страница 12: ...ary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground MG14 277 480 V with Time Delay 1 For delayed sensitive operation using electromechanical relays Type CHN CHL add TD device and jumpers ...

Страница 13: ...ted OFF when no trip condition is detected CLOSE Indicator ON until phasing voltage no longer satisfies the ML PL settings OFF when no close condition is detected FLOAT Indicator Flashes when pendant is active ON when the relay is energized and not commanding a Trip nor Close FAIL Indicator ON when micro controller is not operating properly Trip and Close Contacts Rating The relay contacts are cap...

Страница 14: ...ary Input Enable On Off Enable Disable Contact NO Normally Open NC Normally Closed Tolerances The relay shall operate within the tolerance shown while operating over the normal temperature range of 20 C to 110 C and the normal network voltage range of 12 to 190 Vac Sensitive Trip 5 of setting or 0 5 mA whichever is greater Instantaneous Trip 5 of setting or 0 1 A whichever is greater Insensitive T...

Страница 15: ...ected in the transformer terminals or in the network terminals 4 Incorrect phase sequence is detected 5 Rolled phase is detected 6 Any one phase is dead in the transformer or network terminals Table 5 Trip Amperage as a Function of Percent of CT Primary from 05 5 Note This table represents only that region from 05 5 of the CT primary The relay can be adjusted up to the 5 level if desired The amper...

Страница 16: ...an cause damage to those device or devices the relay an injury or a fire Make sure that each designated wire is connected to the correct terminal Re check the CT connections after installing the relay and before energizing the breaker When operating the breaker without the relay terminate each pair of the disconnected CT wires by shorting the ends and securing this from any other energized wires U...

Страница 17: ... key FSK technology and has the following benefits 1 Devices are easily daisy chained with inexpensive shielded twisted pair cable 2 Noise immunity and signal integrity verification to ensure reliable data transfer 3 Up to 1 000 devices are supported on Main Network 4 Up to 99 devices are supported in Subnetwork 5 Up to 1 000 devices may be monitored and controlled from a single location 6 Distanc...

Страница 18: ...or 5 CD ROM for CD ROM installation 6 High density 3 5 inch disk drive Monitoring PowerNet provides energy management operational and equipment status information and offer the user the capa bility of 1 Real time information 2 Data printout 3 Internal environment of the network protector enclosure 4 Vault environment Control PowerNet provides multiple network protectors controlled from a remote lo...

Страница 19: ...Supports up to 10 000 feet distance and 1 000 relays NetLink a computer based device that 1 Translate INCOM into Standard Ethernet TCP IP messages or ModBus RTU 2 Acts as a data logger to store events and trend information Commercial Translators There are devices available in the market that can translate INCOM protocol format to 1 SES92 format 2 DNP3 format System Capacity The Master PC device se...

Страница 20: ... The SUBMASTER is the only device on a subnetwork which issues command signals It appears as a single device to the Main Network and responds to commands by the MASTER The NODE is an IMPACC compatible device that receives commands from the MASTER and or SUBMASTER and executes the command The MAIN RUN is a length of cable more than 200 feet 61 m on which the MASTER or SUBMASTER resides The EOLTR an...

Страница 21: ...l or less than 64 3 There are three levels of subtaps allowed with a restriction of 4 feet 1 2 m on the third level Figure 10 Complex Tap The MAIN NETWORK consist of the Main Run connected to a MASTER as well as all the cabling in Simple Taps and Complex Taps connected to the Main Run The SUBNETWORK consist of the Main Run connected to a SUBMASTER as well as all the cabling in Simple Taps and Comp...

Страница 22: ...CV Network Protection Relay The CABLE STAR is created when the MASTER or SUBMASTER is connected to more than one Main Run Figure 12 Cable Star The CABLE BRANCH is created when splitting one or more Main Runs Figure 13 Cable Branch Master EOLTR EOLTR Simple Tap Main Run Main Run EOLTR EOLTR Simple Tap Main Run Main Run Node 4 Node 3 Node 1 Node 2 Node 5 Node 6 Node N Node 7 EOLTR Simple Tap Main Ru...

Страница 23: ...inal blocks when splicing All devices EOLTR Simple Taps and Complex Taps should be placed in parallel across the cable 5 Cable Shielding Cable shielding and outer jacket should not be stripped longer than 1 1 2 inches 38 1 mm Use the three pole terminal blocks at tap points to ensure a continuous metallic shield ground path Mechanically crimp sleeves on to the two shield path drain wires The cable...

Страница 24: ...oltage AND the positive sequence phasing voltage indicates a de energized network and feeder system condition Bus voltages and the bus connections to the MPCV should be verified O Trip Var Trip Reverse current exceeded RT set point for at least 2 power cycles instantaneous Watt Var Trip characteristic WV ON TD 0 and the reverse current phasor fell in the var region 60 degree portion of the overall...

Страница 25: ...place Note Kit 8231A80G07 is available for converting from 480 V Electromechanical Relays and includes the relay CNJ Jumper Plate Wiring Kit Instruction Book and 3 Phase Potential Transformer Note Units with energized CTs can be changed to GRD Y connected CTs based on instructions noted in Relay Conversion Guidelines on Page 26 Table 11 MPCV GE 216 V Relay 6417C84G01 Kit 8231A80G06 For use in GE M...

Страница 26: ...ditional lengths of AWG 16 Teflon coated wire One wire should go to GROUND and the other wire should be connected to terminal 5 on the relay connector Note If the relay responds during test in a close mode at 180 degrees reverse current or a trip mode in phase or at 60 degrees then the CTs are connected in reverse polarity Reverse the CT connections on all three phases to correct this situation En...

Страница 27: ...on Relay eaton corporation www eaton com IB02402001E For more information visit www EatonElectrical com Instruction Bulletin Effective September 2004 Page 27 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Curve Drawings Figure 14 Straight Closing Curve Phasing Line ML 0 270 90 180 ...

Страница 28: ...ction Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 28 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 15 Circular Closing Curve L H M L PHASING LINE 0 270 90 180 M L ...

Страница 29: ...region by additional 10 degrees to compensate for CT phase angle error during fault conditions and high trans former X to R ratios allowing the relay to trip whenever the positive sequence component of the current leads the positive sequence line to ground volt age by more than 85 degrees In com parison the traditional watt trip characteristic would allow closure only if this angle is more than 95...

Страница 30: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 31: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 32: ... agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL...

Отзывы: