manualshive.com logo in svg
background image

6

Instruction Booklet 

IB02402001E

December 2010

Instructions for the Eaton Type

MPCV Network Protection Relay

EaToN CoRPoRaTIoN www.eaton.com

 

For more information visit: www.EatonElectrical.com

IB02402001E

 

Instruction Bulletin

 

Page

 

 6

 

Effective:  September 2004

 

Instruction for the 

Cutler-Hammer Type MPCV

Network Protection Relay

 

ST ML=ON

 

The ST ML=ON refers to the straight line master line setting. 

This is the traditional master line which has a slope of 7 to 

7.5 degrees (refer to 

 

Figure 14

 

). Entering the large arrow up 

and down key will change the ST ML=ON to ST ML=OFF. 

Selecting the straight master line to equal off changes the 

closing characteristics to the circular master line (refer to 

 

Figure 15

 

). The circular master line allows the relay to close 

at the same ML setting and at any angle between the LH MH 

and PL settings. It is useful in those areas where the network 

load is lighter than normal. This function permits the relay to 

call for a close at lower loads while assuring the watt flow 

will be into the network. Make your selection and enter the 

NEXT key to view the next line.

 

ML=1.00V

 

This is the overvoltage phasing voltage, which is the differ-

ence between the transformer and network line to ground 

voltages. This value represents the in-phase or 0 degree 

value. The Master Line value can be changed at 0.20 volt 

increments by entering the large up or down arrow keys. 

Adjustments of 0.10 volt can be obtained by entering the 

small up or down arrow key.

Make your selection and enter the NEXT key to view the 

next line.

 

PL=-5º

 

This refers to the Phasing Line adjustment (refer to 

 

Figure 14

 

 

and 

 

15

 

). The phasing line can be changed from +5 to -25 

degrees in 5-degree increments. Make your selection and 

enter the NEXT key to view the next line.

 

LH ML=90º

 

 (viewed only if ST ML=OFF)

The Left Hand Master Line can be viewed whenever the ST 

ML=OFF, or the circular master line is enabled. 

 

Figure 15

 

 

shows the Left-Hand Master Line adjustment region from 

+60 to +90 degrees. This is selectable by using the small 

arrow up and down keys in 5-degree increments for small 

arrow and 10-degree increments for large arrow. Make your 

selection and enter the NEXT key to view the next line.

 

RT=.20%

 

The Reverse Trip setting is calibrated at 180 degrees and is 

selectable in 0.20% increments when using the large up and 

down arrow keys and in 0.01% increments when using the 

small up and down arrow keys. Refer to 

 

Table 5

 

 Trip Amper-

age as a Function of CT Primary from .05 to 5% on 

 

Page 15

 

This table tabulates the most active trip region selections. 

The RT setting is referred to as the sensitive trip region. Make 

your selection and enter the NEXT key to view the next line.

 

TD=0

 

This represents the Time Delay setting which is divided into 

three separate areas.

 

1. TD=0 With a zero setting, there is no time delay 

associated with tripping. Sets relay to respond on RT set-

ting only.

2. TD=0.25 to 300 seconds. This is selectable in 20-sec-

ond increments when using the large up and down arrow 

keys and is selectable in 0.25-second increments when 

using the small up and down arrow keys. This represents 

time delay on tripping in seconds. Sets the relay to 

respond on RT setting with Time Delay and respond 

instantaneously to OC setting.

3. TD=INF This is selectable from the TD=0 mode by 

entering the small arrow down key. Sets the relay to non-

sensitive tripping and respond instantaneously to OC set-

ting only. It overrides the sensitive trip setting.

Make your selection and enter the NEXT key to view the 

next line.

OC=0

This represents the overcurrent (OC) instantaneous pickup 

point of the relay. There are two selections possible in this 

mode, which are:

1. OC=0

There is no instantaneous overcurrent pickup point 

selected. This can be the situation whenever the TD 

setting equals 0.

2. OC=1 to 250%

This is selectable in 20% increments by entering the 

large up and down arrow keys or in 1% increments by 

entering the small up and down arrow keys.

Note: If TD=INF or if TD=0.25 to 300 seconds, you will be directed 

to make an OC setting other than 0.

You can also select an OC setting other than 0 if just the sen-

sitive trip range (RT) is being used. The sensitive trip range 

spans from .05% to .5%. This can be further extended by 

engaging the OC setting. Make your selection and enter the 

NEXT key to view the next line.

WV=OFF

The relay can be selected to engage the watt-var trip charac-

teristic by entering the large up arrow key, changing the 

WV=OFF to WV=ON. The new “Boomerang Watt-Var” trip 

curve is shown in Figure 5. Note that the new curve permits 

balanced 3-phase tripping under reverse magnetizing condi-

tions, while at the same time can handle phase unbalanced 

conditions which can exist on overhead primary circuits. 

Again, the OC setting can be engaged which will add a 

non-sensitive trip region to the tripping characteristic.

Make your selection and enter the NEXT key to view the 

next line.

PUMP PROTEC= OFF

The MPCV relay incorporates an innovative system where by 

the operator can select to protect the network protector 

breaker from pumping. If the PUMP PROTEC=OFF, then 

there is no pump protection installed. Entering the large up 

and down arrow keys will change the PUMP PROTEC=ON. 

If the PUMP PROTEC=OFF, and the NEXT key is entered, the 

screen displays INCOM ADR, which starts the communication 

information. See below. If the PUMP PROTEC=ON and the 

NEXT key is entered, BRK CYCLES=3 is displayed. This is 

selectable from 3 to 20 cycles. If the NEXT key is entered, 

the next line displays PUMP TIME=30, which is selectable 

from 30 to 300 seconds. If the breaker opens and closes its 

contacts equal to or exceeding the BRK CYCLES in the speci-

fied number of seconds as defined by the PUMP TIME, the 

breaker will trip and lock open.

 

WARNING

THE TD=INF WILL DISABLE THE SENSITIVE TRIP MODE AND 

WILL ONLY PERMIT TRIPPING OF THE NETWORK PROTECTOR 

AT THE SELECTED OC VALUE.

Содержание MPCV Series

Страница 1: ... more information visit www EatonElectrical com Instruction for the Cutler Hammer Type MPCV Network Protection Relay Instruction Bulletin Supersedes I B 35 581B Pages 1 28 dated October 1997 MPCV Communications Relay for Cutler Hammer Westinghouse Network Protectors Rear View MPCV Communications Relay for General Electric Network Protectors Rear View ...

Страница 2: ...RED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES If further information is required the Eaton Corporation should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED ...

Страница 3: ... controlled relays are designed to replace the Type CN 33 electromechanical master relay the Type CNJ electromechanical phasing relay and the Type BN electromechanical desensitizing relay The MPC series relays use the same voltage and current inputs as do the electromechanical equivalent They also continually moni tor voltage across an open breaker and current through a closed breaker and perform ...

Страница 4: ...lose if V1N is less than 1 P U and V2N is less than 06 P U and V1P exceeds 8 P U Note that as stated before if V2P exceeds 2 P U then the trip contact will close indicating crossed phases on either the transformer side or the network side Also note that if the phases are crossed on both the transformer and the net work side V2P could be very close to or equal to zero but the trip contact will clos...

Страница 5: ...ckwise system then the selection must be changed to CBA ON This can be changed by entering the large up or down arrow keys Make your selection and enter the NEXT key to view the next line Note If the wrong sentence is selected the relay upon power up will give a trip indication CT RATIO This refers to the current transformer CT primary rating For example an 1875 ampere network protector will have ...

Страница 6: ...ping Sets relay to respond on RT set ting only 2 TD 0 25 to 300 seconds This is selectable in 20 sec ond increments when using the large up and down arrow keys and is selectable in 0 25 second increments when using the small up and down arrow keys This represents time delay on tripping in seconds Sets the relay to respond on RT setting with Time Delay and respond instantaneously to OC setting 3 TD...

Страница 7: ...nter the NEXT key to view the next line Note If a MPCV Relay is provided with communications turned OFF communications can be activated in the field by a qualified Eaton ser vice representative INCOM SETPT ON The default setting is ON with the capability to change to OFF If the INCOM SETPT OFF this prevents a user from remotely changing set points through the IMPACC Series III or PowerNet software...

Страница 8: ...int de press the large or small up or down arrow keys for large or small increment adjustments until the desired value appears on the dis play e Once the desired value is obtained de press the NEXT key The program will automatically step to the next set point to be set f Continue to adjust each set point by repeating Steps d and e above until all the set points have been satisfied Note The startin...

Страница 9: ...accomplished by changing the WV set point from OFF to ON D Proceed to Section II of the MPCV D instructions calibration section Refer to Page 8 Note For CM 22 or CMR breakers which have been rewired to accept the MPCV phase 4 or phase 5 relay the Type MPCV 2X is a direct replacement Style Number is 6417C83G03 Table 3 Terminal Configurations Figure 3 Cutler Hammer Relay Note For Communication with ...

Страница 10: ...struc tions given in Note 1 of the time delay installation notes For General Electric Network Protectors manufactured after October 1982 the Type CAN or CHN master relay was replaced by the Type SSNPR analog solid state relay and the above four wiring changes will have been made Once the MPCV GE Relay has been installed and all of the wiring changes have been performed and or confirmed proceed to ...

Страница 11: ...ug is necessary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground 3 Watt var function is incorporated within the MPCV Relay When applying an MPCV Relay with or without watt var function add...

Страница 12: ...ary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground MG14 277 480 V with Time Delay 1 For delayed sensitive operation using electromechanical relays Type CHN CHL add TD device and jumpers ...

Страница 13: ...ted OFF when no trip condition is detected CLOSE Indicator ON until phasing voltage no longer satisfies the ML PL settings OFF when no close condition is detected FLOAT Indicator Flashes when pendant is active ON when the relay is energized and not commanding a Trip nor Close FAIL Indicator ON when micro controller is not operating properly Trip and Close Contacts Rating The relay contacts are cap...

Страница 14: ...ary Input Enable On Off Enable Disable Contact NO Normally Open NC Normally Closed Tolerances The relay shall operate within the tolerance shown while operating over the normal temperature range of 20 C to 110 C and the normal network voltage range of 12 to 190 Vac Sensitive Trip 5 of setting or 0 5 mA whichever is greater Instantaneous Trip 5 of setting or 0 1 A whichever is greater Insensitive T...

Страница 15: ...ected in the transformer terminals or in the network terminals 4 Incorrect phase sequence is detected 5 Rolled phase is detected 6 Any one phase is dead in the transformer or network terminals Table 5 Trip Amperage as a Function of Percent of CT Primary from 05 5 Note This table represents only that region from 05 5 of the CT primary The relay can be adjusted up to the 5 level if desired The amper...

Страница 16: ...an cause damage to those device or devices the relay an injury or a fire Make sure that each designated wire is connected to the correct terminal Re check the CT connections after installing the relay and before energizing the breaker When operating the breaker without the relay terminate each pair of the disconnected CT wires by shorting the ends and securing this from any other energized wires U...

Страница 17: ... key FSK technology and has the following benefits 1 Devices are easily daisy chained with inexpensive shielded twisted pair cable 2 Noise immunity and signal integrity verification to ensure reliable data transfer 3 Up to 1 000 devices are supported on Main Network 4 Up to 99 devices are supported in Subnetwork 5 Up to 1 000 devices may be monitored and controlled from a single location 6 Distanc...

Страница 18: ...or 5 CD ROM for CD ROM installation 6 High density 3 5 inch disk drive Monitoring PowerNet provides energy management operational and equipment status information and offer the user the capa bility of 1 Real time information 2 Data printout 3 Internal environment of the network protector enclosure 4 Vault environment Control PowerNet provides multiple network protectors controlled from a remote lo...

Страница 19: ...Supports up to 10 000 feet distance and 1 000 relays NetLink a computer based device that 1 Translate INCOM into Standard Ethernet TCP IP messages or ModBus RTU 2 Acts as a data logger to store events and trend information Commercial Translators There are devices available in the market that can translate INCOM protocol format to 1 SES92 format 2 DNP3 format System Capacity The Master PC device se...

Страница 20: ... The SUBMASTER is the only device on a subnetwork which issues command signals It appears as a single device to the Main Network and responds to commands by the MASTER The NODE is an IMPACC compatible device that receives commands from the MASTER and or SUBMASTER and executes the command The MAIN RUN is a length of cable more than 200 feet 61 m on which the MASTER or SUBMASTER resides The EOLTR an...

Страница 21: ...l or less than 64 3 There are three levels of subtaps allowed with a restriction of 4 feet 1 2 m on the third level Figure 10 Complex Tap The MAIN NETWORK consist of the Main Run connected to a MASTER as well as all the cabling in Simple Taps and Complex Taps connected to the Main Run The SUBNETWORK consist of the Main Run connected to a SUBMASTER as well as all the cabling in Simple Taps and Comp...

Страница 22: ...CV Network Protection Relay The CABLE STAR is created when the MASTER or SUBMASTER is connected to more than one Main Run Figure 12 Cable Star The CABLE BRANCH is created when splitting one or more Main Runs Figure 13 Cable Branch Master EOLTR EOLTR Simple Tap Main Run Main Run EOLTR EOLTR Simple Tap Main Run Main Run Node 4 Node 3 Node 1 Node 2 Node 5 Node 6 Node N Node 7 EOLTR Simple Tap Main Ru...

Страница 23: ...inal blocks when splicing All devices EOLTR Simple Taps and Complex Taps should be placed in parallel across the cable 5 Cable Shielding Cable shielding and outer jacket should not be stripped longer than 1 1 2 inches 38 1 mm Use the three pole terminal blocks at tap points to ensure a continuous metallic shield ground path Mechanically crimp sleeves on to the two shield path drain wires The cable...

Страница 24: ...oltage AND the positive sequence phasing voltage indicates a de energized network and feeder system condition Bus voltages and the bus connections to the MPCV should be verified O Trip Var Trip Reverse current exceeded RT set point for at least 2 power cycles instantaneous Watt Var Trip characteristic WV ON TD 0 and the reverse current phasor fell in the var region 60 degree portion of the overall...

Страница 25: ...place Note Kit 8231A80G07 is available for converting from 480 V Electromechanical Relays and includes the relay CNJ Jumper Plate Wiring Kit Instruction Book and 3 Phase Potential Transformer Note Units with energized CTs can be changed to GRD Y connected CTs based on instructions noted in Relay Conversion Guidelines on Page 26 Table 11 MPCV GE 216 V Relay 6417C84G01 Kit 8231A80G06 For use in GE M...

Страница 26: ...ditional lengths of AWG 16 Teflon coated wire One wire should go to GROUND and the other wire should be connected to terminal 5 on the relay connector Note If the relay responds during test in a close mode at 180 degrees reverse current or a trip mode in phase or at 60 degrees then the CTs are connected in reverse polarity Reverse the CT connections on all three phases to correct this situation En...

Страница 27: ...on Relay eaton corporation www eaton com IB02402001E For more information visit www EatonElectrical com Instruction Bulletin Effective September 2004 Page 27 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Curve Drawings Figure 14 Straight Closing Curve Phasing Line ML 0 270 90 180 ...

Страница 28: ...ction Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 28 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 15 Circular Closing Curve L H M L PHASING LINE 0 270 90 180 M L ...

Страница 29: ...region by additional 10 degrees to compensate for CT phase angle error during fault conditions and high trans former X to R ratios allowing the relay to trip whenever the positive sequence component of the current leads the positive sequence line to ground volt age by more than 85 degrees In com parison the traditional watt trip characteristic would allow closure only if this angle is more than 95...

Страница 30: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 31: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 32: ... agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL...

Отзывы: