Instruction for the 

Cutler-Hammer Type MPCV

Network Protection Relay

PowerNet Reason Descriptions on MPCV Relay Status

Table 7 provides descriptions of all of the possible Status 

and Reason states as reported by the MPCV Relay via Pow-

erNet. Note that the status is a function of the Aux_B input 

contact to the MPCV in combination with any Trip or Close 

control from the MPCV and time. The first column shows 

network protector status based on the AUX B input contact, 

where “C” denotes the network protector is sensed to be 

CLOSED (physical Aux B contact is open). Similarly, an “O” 

indicates an OPEN protector (Aux B contact is closed).

It indicates that all of the following TRIP descriptions imply 

that the network protector has been sensed to be OPEN, 

prior to which a protective TRIP control was issued to the 

protector by the MPCV. The associated PowerNet Reason 

String attempts to detail what power system condition 

caused the MPCV to command a trip. The descriptions 

provided for the Trip states are also applicable for 

Time-Stamped Trip Events.

Note: Alarm Status has higher priority than Trip, Open or Close in 

Table 7 below.

Table 7. PowerNet Reason Descriptions on MPCV Relay Status

NWP 

Status

Relay

Status

Reason

Description

C

Closed

Normal

Sensed in the CLOSED position, Normal

O

Open

Normal

Sensed in the OPEN position, Normal

O

Open

Remote Open

Block Open

Sensed in the OPEN position, and MPCV was Remotely commanded to be Open/ Blocked Open (ROBO)

O

Trip

Phase Reversal

Typically indicative of a reversed phase condition on the network side. An improper CBA rotation set point will 

also generate this reason. Bus voltages and the bus connections to the MPCV should also be verified.

O

Trip

Rolled Phase

Typically indicative of a rolled phased power system condition. Bus voltages and the bus connections to the 

MPCV should also be verified.

O

Trip

Per Unit 

Voltage

Indicative of a reversed phase condition on the transformer, or a rolled phase on the transformer, or a rolled 

phase on the network. Bus voltages and the bus connections to the MPCV should also be verified.

O

Trip

Sensitive

Reverse current exceeded RT set point for at least 2 power cycles (instantaneous), Watt Trip characteristic 

(WV=OFF), TD=0.

O

Trip

Time Delayed 

Sensitive

Reverse current exceeded RT set point for the duration of the non-zero TD setting, Watt Trip characteristic 

(WV=OFF).

O

Trip

De-energized

The magnitudes of the positive sequence network voltage AND the positive sequence phasing voltage 

indicates a de-energized network and feeder system condition. Bus voltages and the bus connections to the 

MPCV should be verified.

O

Trip

Var Trip

Reverse current exceeded RT set point for at least 2 power cycles (instantaneous), Watt-Var Trip characteristic 

(WV=ON), TD=0, and the reverse current phasor fell in the var region (60 degree portion) of the overall Watt-Var 

Trip curve.

O

Trip

Breaker

Pumping

Pump Protection is enabled, and the protector has cycled the programmed number of cycles within the pump 

time setting. The MPCV will continue to command a TRIP to protector, until expiration of the Reset Timer or a 

Remote command to clear the pumping fault.

O

Trip

Overcurrent

Reverse current exceeded OC set point for at least 2 power cycles, Watt Trip characteristic (WV=OFF). 

Overcurrent OC is strictly an “instantaneous” setting.

O

Trip

Non-Sensitive

Technically refers to the “Sensitive Plus Non-Sensitive” trip mode of the MPCV Relay. This mode is selected by 

setting TD=0, and OC>0, resulting in a trip characteristic with an intentional non-trip dead band region. This 

mode is NOT recommended for most applications.

O

Trip

Watt Trip

Reverse current exceeded RT set point for at least 2 power cycles (instantaneous), Watt-Var Trip characteristic 

(WV=ON), TD=0, and the reverse current phasor fell in the Watt region (-5 deg portion) of the overall Watt-Var 

Trip curve.

O

Trip

Time Delayed

Watt Trip

Reverse current exceeded RT set point for the duration of the non-zero TD setting, Watt-Var Trip characteristic 

(WV=ON).

O

Trip

Overcurrent

Watt Trip

Reverse current exceeded OC set point for at least 2 power cycles, Watt-Var Trip characteristic (WV=ON). 

Overcurrent OC is strictly an “instantaneous” setting.

O

Trip

Set Point

MPCV has detected a checksum problem with the programmed set points in non-volatile memory. 

Protector will trip and relay should be replaced.

O

Trip

RAM

MPCV has detected a RAM memory problem on power-up. Protector will trip (for CH FW version V.1.016 and 

GE FW version V1.017 or newer) and relay should be replaced.

(C)

Alarm

Failed to Open

MPCV has tried to TRIP the protector, but did NOT sense that the Aux B input contact closed within 10 seconds. 

May be a problem in the protector trip circuit or wiring of the Aux B contact.

(O)

Alarm

Failed to Close

MPCV has tried to CLOSE the protector, but did NOT sense that the Aux B input contact opened within 10 

seconds. May be a problem in the protector close circuitry or wiring of the Aux B contact

?

Alarm

Auxiliary 2

Alarm

Auxiliary Channel 2 has been activated, has been set to alarm on activation, and the channel is currently in the 

active state.

?

Alarm

Auxiliary 3

Alarm

Auxiliary Channel 3, as Aux 2 above.

?

Alarm

Auxiliary 4

Alarm

Auxiliary Channel 4, as Aux 2 above.

?

?

Not responding

Possible loss of power, communication error, the relay is out of service or the wiring has been compromised.

Содержание MPCV Series

Страница 1: ... more information visit www EatonElectrical com Instruction for the Cutler Hammer Type MPCV Network Protection Relay Instruction Bulletin Supersedes I B 35 581B Pages 1 28 dated October 1997 MPCV Communications Relay for Cutler Hammer Westinghouse Network Protectors Rear View MPCV Communications Relay for General Electric Network Protectors Rear View ...

Страница 2: ...RED TO BE ALL INCLUSIVE OR COVERING ALL CONTINGENCIES If further information is required the Eaton Corporation should be consulted NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS DESCRIPTIONS AND SAFETY NOTATIONS CONTAINED ...

Страница 3: ... controlled relays are designed to replace the Type CN 33 electromechanical master relay the Type CNJ electromechanical phasing relay and the Type BN electromechanical desensitizing relay The MPC series relays use the same voltage and current inputs as do the electromechanical equivalent They also continually moni tor voltage across an open breaker and current through a closed breaker and perform ...

Страница 4: ...lose if V1N is less than 1 P U and V2N is less than 06 P U and V1P exceeds 8 P U Note that as stated before if V2P exceeds 2 P U then the trip contact will close indicating crossed phases on either the transformer side or the network side Also note that if the phases are crossed on both the transformer and the net work side V2P could be very close to or equal to zero but the trip contact will clos...

Страница 5: ...ckwise system then the selection must be changed to CBA ON This can be changed by entering the large up or down arrow keys Make your selection and enter the NEXT key to view the next line Note If the wrong sentence is selected the relay upon power up will give a trip indication CT RATIO This refers to the current transformer CT primary rating For example an 1875 ampere network protector will have ...

Страница 6: ...ping Sets relay to respond on RT set ting only 2 TD 0 25 to 300 seconds This is selectable in 20 sec ond increments when using the large up and down arrow keys and is selectable in 0 25 second increments when using the small up and down arrow keys This represents time delay on tripping in seconds Sets the relay to respond on RT setting with Time Delay and respond instantaneously to OC setting 3 TD...

Страница 7: ...nter the NEXT key to view the next line Note If a MPCV Relay is provided with communications turned OFF communications can be activated in the field by a qualified Eaton ser vice representative INCOM SETPT ON The default setting is ON with the capability to change to OFF If the INCOM SETPT OFF this prevents a user from remotely changing set points through the IMPACC Series III or PowerNet software...

Страница 8: ...int de press the large or small up or down arrow keys for large or small increment adjustments until the desired value appears on the dis play e Once the desired value is obtained de press the NEXT key The program will automatically step to the next set point to be set f Continue to adjust each set point by repeating Steps d and e above until all the set points have been satisfied Note The startin...

Страница 9: ...accomplished by changing the WV set point from OFF to ON D Proceed to Section II of the MPCV D instructions calibration section Refer to Page 8 Note For CM 22 or CMR breakers which have been rewired to accept the MPCV phase 4 or phase 5 relay the Type MPCV 2X is a direct replacement Style Number is 6417C83G03 Table 3 Terminal Configurations Figure 3 Cutler Hammer Relay Note For Communication with ...

Страница 10: ...struc tions given in Note 1 of the time delay installation notes For General Electric Network Protectors manufactured after October 1982 the Type CAN or CHN master relay was replaced by the Type SSNPR analog solid state relay and the above four wiring changes will have been made Once the MPCV GE Relay has been installed and all of the wiring changes have been performed and or confirmed proceed to ...

Страница 11: ...ug is necessary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground 3 Watt var function is incorporated within the MPCV Relay When applying an MPCV Relay with or without watt var function add...

Страница 12: ...ary except for a jumper across terminals 1 and 2 wire No 6 6A Lifting wire 6A and attaching to terminal wire 6 can accomplish this All field units previously having Type CHN CHL relays also require the addition of a wire from master relay plug terminal 4 to ground MG14 277 480 V with Time Delay 1 For delayed sensitive operation using electromechanical relays Type CHN CHL add TD device and jumpers ...

Страница 13: ...ted OFF when no trip condition is detected CLOSE Indicator ON until phasing voltage no longer satisfies the ML PL settings OFF when no close condition is detected FLOAT Indicator Flashes when pendant is active ON when the relay is energized and not commanding a Trip nor Close FAIL Indicator ON when micro controller is not operating properly Trip and Close Contacts Rating The relay contacts are cap...

Страница 14: ...ary Input Enable On Off Enable Disable Contact NO Normally Open NC Normally Closed Tolerances The relay shall operate within the tolerance shown while operating over the normal temperature range of 20 C to 110 C and the normal network voltage range of 12 to 190 Vac Sensitive Trip 5 of setting or 0 5 mA whichever is greater Instantaneous Trip 5 of setting or 0 1 A whichever is greater Insensitive T...

Страница 15: ...ected in the transformer terminals or in the network terminals 4 Incorrect phase sequence is detected 5 Rolled phase is detected 6 Any one phase is dead in the transformer or network terminals Table 5 Trip Amperage as a Function of Percent of CT Primary from 05 5 Note This table represents only that region from 05 5 of the CT primary The relay can be adjusted up to the 5 level if desired The amper...

Страница 16: ...an cause damage to those device or devices the relay an injury or a fire Make sure that each designated wire is connected to the correct terminal Re check the CT connections after installing the relay and before energizing the breaker When operating the breaker without the relay terminate each pair of the disconnected CT wires by shorting the ends and securing this from any other energized wires U...

Страница 17: ... key FSK technology and has the following benefits 1 Devices are easily daisy chained with inexpensive shielded twisted pair cable 2 Noise immunity and signal integrity verification to ensure reliable data transfer 3 Up to 1 000 devices are supported on Main Network 4 Up to 99 devices are supported in Subnetwork 5 Up to 1 000 devices may be monitored and controlled from a single location 6 Distanc...

Страница 18: ...or 5 CD ROM for CD ROM installation 6 High density 3 5 inch disk drive Monitoring PowerNet provides energy management operational and equipment status information and offer the user the capa bility of 1 Real time information 2 Data printout 3 Internal environment of the network protector enclosure 4 Vault environment Control PowerNet provides multiple network protectors controlled from a remote lo...

Страница 19: ...Supports up to 10 000 feet distance and 1 000 relays NetLink a computer based device that 1 Translate INCOM into Standard Ethernet TCP IP messages or ModBus RTU 2 Acts as a data logger to store events and trend information Commercial Translators There are devices available in the market that can translate INCOM protocol format to 1 SES92 format 2 DNP3 format System Capacity The Master PC device se...

Страница 20: ... The SUBMASTER is the only device on a subnetwork which issues command signals It appears as a single device to the Main Network and responds to commands by the MASTER The NODE is an IMPACC compatible device that receives commands from the MASTER and or SUBMASTER and executes the command The MAIN RUN is a length of cable more than 200 feet 61 m on which the MASTER or SUBMASTER resides The EOLTR an...

Страница 21: ...l or less than 64 3 There are three levels of subtaps allowed with a restriction of 4 feet 1 2 m on the third level Figure 10 Complex Tap The MAIN NETWORK consist of the Main Run connected to a MASTER as well as all the cabling in Simple Taps and Complex Taps connected to the Main Run The SUBNETWORK consist of the Main Run connected to a SUBMASTER as well as all the cabling in Simple Taps and Comp...

Страница 22: ...CV Network Protection Relay The CABLE STAR is created when the MASTER or SUBMASTER is connected to more than one Main Run Figure 12 Cable Star The CABLE BRANCH is created when splitting one or more Main Runs Figure 13 Cable Branch Master EOLTR EOLTR Simple Tap Main Run Main Run EOLTR EOLTR Simple Tap Main Run Main Run Node 4 Node 3 Node 1 Node 2 Node 5 Node 6 Node N Node 7 EOLTR Simple Tap Main Ru...

Страница 23: ...inal blocks when splicing All devices EOLTR Simple Taps and Complex Taps should be placed in parallel across the cable 5 Cable Shielding Cable shielding and outer jacket should not be stripped longer than 1 1 2 inches 38 1 mm Use the three pole terminal blocks at tap points to ensure a continuous metallic shield ground path Mechanically crimp sleeves on to the two shield path drain wires The cable...

Страница 24: ...oltage AND the positive sequence phasing voltage indicates a de energized network and feeder system condition Bus voltages and the bus connections to the MPCV should be verified O Trip Var Trip Reverse current exceeded RT set point for at least 2 power cycles instantaneous Watt Var Trip characteristic WV ON TD 0 and the reverse current phasor fell in the var region 60 degree portion of the overall...

Страница 25: ...place Note Kit 8231A80G07 is available for converting from 480 V Electromechanical Relays and includes the relay CNJ Jumper Plate Wiring Kit Instruction Book and 3 Phase Potential Transformer Note Units with energized CTs can be changed to GRD Y connected CTs based on instructions noted in Relay Conversion Guidelines on Page 26 Table 11 MPCV GE 216 V Relay 6417C84G01 Kit 8231A80G06 For use in GE M...

Страница 26: ...ditional lengths of AWG 16 Teflon coated wire One wire should go to GROUND and the other wire should be connected to terminal 5 on the relay connector Note If the relay responds during test in a close mode at 180 degrees reverse current or a trip mode in phase or at 60 degrees then the CTs are connected in reverse polarity Reverse the CT connections on all three phases to correct this situation En...

Страница 27: ...on Relay eaton corporation www eaton com IB02402001E For more information visit www EatonElectrical com Instruction Bulletin Effective September 2004 Page 27 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Curve Drawings Figure 14 Straight Closing Curve Phasing Line ML 0 270 90 180 ...

Страница 28: ...ction Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 28 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 15 Circular Closing Curve L H M L PHASING LINE 0 270 90 180 M L ...

Страница 29: ...region by additional 10 degrees to compensate for CT phase angle error during fault conditions and high trans former X to R ratios allowing the relay to trip whenever the positive sequence component of the current leads the positive sequence line to ground volt age by more than 85 degrees In com parison the traditional watt trip characteristic would allow closure only if this angle is more than 95...

Страница 30: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 31: ...Protection Relay eaton corporation www eaton com For more information visit www EatonElectrical com IB02402001E Instruction Bulletin Page 30 Effective September 2004 Instruction for the Cutler Hammer Type MPCV Network Protection Relay Figure 17 Watt Trip with Non Sensitive Range 0 270 90 180 A ...

Страница 32: ... agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL...

Отзывы: