InsulGard System Installation and Start Up Guideline
16
2) Diagram of the main required connections to Insulgard
Figure 1-13 Main connection to InsulGard
3) IPDS sensors installation specifics
a) Be sure to install the capacitors on the HV Phase leads and not on the neutral side of the winding.
b) If a motor has surge capacitors, install the HV connection on the motor winding side of the surge capacitors.
See diagrams below.
InsulGard Enclosure
NEMA 4
Note:
Mount close to a motor main
terminal box and RTD
termination box to minimize
cable and conduits length
120 (230) VAC
10 amp
Power Source
1 - 2 conductor, twisted pair 22 AWG for RS485 Network
and/or 1- 2 conductor phone wire for modem remote
communications, if required.
1 - 2 conductor shielded wire for 4 - 20 ma output, if required
1 - 6 conductor cable suitable monitoring of dry contacts for
system status, low alarm and high alarm (minimum 2
conductors if contacts are connected in series or in parallel)
1" conduit
fitting
1 1/2"
conduit
fitting
Motor terminal box
3 coax cables from coupling
capacitors
1 - 3 wire shielded cable
AWG22 for Humidity sensor
(comes with the sensor)
1 - 2 wire shielded cable
AWG22 for Load sensor
(comes with the sensor)
1 - 3 wire shielded cable
AWG22 for the Temperature
sensor (if provided, comes
with the sensor)
RTD terminal box
1 coax cable per RTD
from RTD PD sensor(s)
1 - 3 wire shielded cable
AWG22 for winding RTD
(if provided)
Motor
Winding
Coupling
Cap
Surge
Cap
In
c
o
mi
n
g
P
o
w
e
r
Right
Motor
Winding
In
c
o
m
in
g
P
o
w
er
Coupling
Cap
Surge
Cap
Wrong
Motor
Winding
Coupling
Cap
Surge
Cap
In
c
o
mi
n
g
P
o
w
e
r
Wrong