InsulGard System Installation and Start Up Guideline
10
RS485 network (if used) should be connected to inputs A (+) and B (-). Don't use terminals G (insulated ground) and
+5 (ins5V).
USB port "Device" is used for communication with PC. Port "Host" is not used now.
Figure 1-8
Wires connection to green plugs for power voltage, relays and RS485 interface port.
1.2 Installation of the InsulGard Sensors
Monitored object and InsulGard must be de-energized.
The best way to de-energize InsulGard is to de-energize
the incoming power supply line. On a panel mount InsulGard open the fuse located on the DIN-Rail.
All sensors have default cable length of 65’ (20m). Custom lengths may be specified at the time of order entry.
Install all sensors in accordance with their manuals
in “InsulGard Sensors Manual”.
1) PD sensors and features of their installation
IPDS
RTD-6-PD
RFCT
Figure 1-9
PD sensors