EFX48-xx Series with RM3-340/440 Installation and Operation Guide
106
Copyright © 2019 Eaton Corporation. All Rights Reserved.
IPN March 2019
User Access
The EFX48 allows for up to 8 user accessible and editable accounts with three levels of access
rights (Read only, Read/Write and Admin). When shipped the unit has one Admin account
configured with full access rights.
Read Only Users
The Read only users can read any configuration parameters or account information from the
unit (excluding passwords), but cannot change any parameters. They can back up the unit to
create a configuration file.
Read / Write Users
Read/Write users have similar read and backup access but may also change any configuration
parameters, but not account information.
Admin Users
Admin users have read/write access plus the ability to change account information and may
also restore (upload) configuration files and do firmware updates.
Whilst Admin users can edit any account information, they may not change their own account
access rights or disable their own account. This is to avoid an Admin user inadvertently
disabling the last Admin account in the unit.
Account Access
Each user account has a choice of access methods – either HTTP/HTTPS, SNMP or both. They
can only access the unit via the allowed method(s). An Admin user will have at least
HTTP/HTTPS access. Each user will have at least one access method.
SNMP V3
If SNMP-V3 traps are to be used then one of the user accounts must be defined as the SNMP-
Trap account and this is then the user name that any SNMP-V3 traps are sent from.
The SNMP-Trap account will have an additional ‘PRIV’ key option which is the pre-shared key
for SNMP-V3 communications. When shipped the default Admin account is configured as the
SNMP-Trap account with a default PRIV key set.
Account Names
The user account names may be up to 32 characters long and include any normal printable
characters without spaces. The user account passwords may be up to 20 characters long and
include any normal printable characters without spaces. The SNMP-PRIV key may be up to 20
characters long and include any normal printable characters without spaces.
The user account information can be summarised as below:
Setting Account Names
When setting up a new user, be sure to follow these steps carefully:-
•
Username - enter “Username”, press <enter> and be sure that the status box in the
upper right hand corner of the screen indicates “Update sent”, then “Refreshing”, and
the entry made remains in the “Username” box.
Содержание EFX48 e-Fuse Series
Страница 9: ......
Страница 50: ......
Страница 54: ......
Страница 88: ......
Страница 103: ...EFX48 e Fuse System Operation Copyright 2019 Eaton Corporation All Rights Reserved IPN March 2019 103...
Страница 156: ...Appendix D Menu Map Copyright 2019 Eaton Corporation All Rights Reserved IPN March 2019 156 Menu Map...
Страница 157: ...Menu Map Copyright 2019 Eaton Corporation All Rights Reserved IPN March 2019 157...