20
Threshholds:
High 3.5 to 28 VDC, low 0 to 1.9 VDC
Response:
25 msec max. (5 V signal)
ACCESSORY POWER OUTPUT
Voltage:
12 VDC +10%/-13%
Current:
75 mA max.
Protection:
Short circuit protected
OPTIONAL OUTPUTS
Relay Board
Number of relays:
2
Contact type:
1 set form C per relay
Contact rating:
5A, 250 VAC or 30 VDC
Isolation dielectric strength: 2300 VAC
Analog Retransmission
Output signals:
4-20 mA (<750
W
) and 0-10 V (>2500
W
)
Accuracy:
0.13% full scale and 100 PPM /°C (and 0.07%
full scale change over 4-20 mA load ranges
Isolation dielectric strength: 2300 VAC to signal inputs, relays, and AC power
inputs, 500 VAC to RS 485 and DC power inputs
RS 485 Serial Communications
Baud Rate:
1200, 2400, 4800, 9600, or 19,200, programmable
Parity:
Even, odd, or no parity
Address Range:
00 to 99 decimal
Protocol:
Opto 22
®
compatible
Isolation Dielectric Strength: 2300 VAC to signal inputs, relays, and AC power
inputs, 500 VAC to analog outputs and DC
power inputs
ENVIRONMENTAL
Operating Environment:
Indoor use to 2000 meters
Temperature:
Operating:
0 to 50°C
Storage:
-20 to 70°C
Humidity:
0 to 85% RH, non-condensing
Vibration:
2.5 gs, 30 to 200 Hz
Shock:
30 gs, 11 msec half sinewave
EMC:
Immunity to EN 50082-2 (Heavy Industrial)
Emissions to EN 50081-2 (Heavy Industrial)
Front Panel:
NEMA 4X when mounted with gasket provided
Agency Approval: UL, cUL listed, CE marked
CE EMC immunity and emissions requirements were met using
shielded wiring on the RS-485, analog output and pulse input/
power lines. The shields were connected to earth ground at the
Eclipse end of the shields.
Pollution Degree 2
Overvoltage category II
SPECIFICATIONS cont.