FEATURES

DESCRIPTION

APPEARANCE

ی  Staircase lighting control,
ی  operating  time  adjustment  from  10 

sec to 10 min,

ی  cooperation  with  monostable  push-

buttons  equipped  with  illumination 

lamps,

ی  cooperation with 3-wire or 4-wire in-

stallation,

ی  cable connection 0,5 m long,
ی  hermetic casing (IP 65),
ی  voltage relay output max 16 A capa-

city.

The  staircase  lighting  time  delay 

switch ASH-01 is used to control lighting 

devices on staircases and corridors. After 

releasing  the  system  it  switches  on  the 

lighting  for  the  preset  time  by  the  user. 

After  that  it  switches  off  automatically. 

The operating time can be adjusted from 

10 sec to 10 min by means of a potentio-

meter. The  staircase  lighting  time  delay 

switch ASH-01 can be used as standard 

time  delay  relay.  The  hermetic  casing 

(IP65) secures the device functioning in 

unfavorable weather conditions.

The device is designed 

for  single-phase  instal-

lation  and  must  be  in-

stalled in accordance 

with  standards  valid  in 

a particular country. The 

device  should  be  con-

nected according to the details included 

in  this  operating  manual.  Installation, 

connection and control should be car-

ried out by a qualified electrician staff, 

who  act  in  accordance  with  the  servi-

ce  manual  and  the  device  functions. 

Disassembling  of  the  device  is  equal 

with a loss of guarantee and can cause 

electric shock. Before installation make 

sure the connection cables are not un-

der voltage. The cruciform head screw-

driver 3,5 mm should be used to instal 

the  device.  Improper  transport,  stora-

ge, and use of the device influence its 

wrong functioning. It is not advisable to 

instal the device in the following cases: 

if any device part is missing or the de-

vice is damaged or deformed. In case 

of  improper  functioning  of  the  device 

contact the producer.

CAUTION

TECHNICAL PARAMETERS

ASH-01

Power supply cables: L (black), N (blue)

Input rated voltage: 230 V~

Input voltage tolerance: from -15 to +10 %

Nominal frequency: 50 / 60 Hz

Rated power consumption: 48 mA

Release / output (load) cables: brown, grey (connected inside)

Time adjustment range: from 10 sec to 10 min

Time accuracy adjustment: ±10 %

Time repeatability adjustment: ±5 %

Time adjustment: rotational potentiometer

Output relay parameters: 16 A / 250 V AC1 4000 VA

Number of switch cables: 4

Section of connecting cables: 4 x 1,50 mm

2

Connecting cable length: 0,5 m

Ambient temperature range: from -20 to +45 

o

C

Operating position: vertical, pointed down

Mounting: 2x stretcher 5x(3x30)

Protection degree: IP65 (PN-EN 60529)

Protective class: II

Overvoltage category: II

Pollution degree: 2

Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5)

Dimensions: 69 x 56 x 27 mm

Weight: 101 g

Reference standards: PN-EN 60669-1

PN-EN 60669-2-1

PN-EN 61000-4-2,3,4,5,6,11

black

brown

grey

blue

Power supply cable (N)

Power supply cable (L)

Time adjustment

Release / output (load)