5
Hardware description
DPCT IOM InsTruCTIOn OPeraTIOn Manual
MN124018EN January 2023 www.eaton.com
To select 24 Volt battery charging with Lead Acid batteries,
set DIP switch 3 to the ON position and all other DIP
switches to the OFF position.
3.1.6.2 NiCad
To select 12 Volt battery charging with NiCad batteries, set
DIP switch 6 to the ON position and all other DIP switches
to the OFF position.
To select 24 Volt battery charging with NiCad batteries, set
DIP switches 3 and 6 to the ON position and all other DIP
switches to the OFF position.
3.1.7 Forced charging
There is provision for the battery chargers to provide
a forced charge to the batteries. The Forced Charge
function will only activate immediately after applying
power to the charger with DIP Switch 8 in the ON
position and a battery connected.
When the charger is in the forced charge mode, it will
attempt to recover a battery by delivering 10 amps. If the
battery does not reach the minimum battery voltage (8 Volts
for a 12 Volt system; 16 Volts for a 24 Volt system) within
5 minutes, the recovery attempt will terminate. Once the
battery reaches its minimum battery voltage, the normal
charge sequence will commence.
Forced charging will only occur once per battery charger
power cycle.
3.1.8 Battery charger specifications
Voltage Input:100 - 240VAC - Auto detect
Voltage Output: 12-24VDC-DIP switch selectable
Supply Frequency: 50 or 60Hz
3.2 User interface touch screen
The user interface touch screen is accessible from the front
door of the DPCT fire pump controller. The touch screen
provides access to:
•
Alert the user to specific conditions
•
Program the controller
•
Set and monitor the operating parameters
•
Perform a manual start of the engine
3.2.1 Memory
The EPCT has non-volatile memory which allows the
recording and storage of up to 65,000 events.
3.2.2 Battery backup
A ten (10) year, replaceable lithium battery allows a clock to
be kept during power failures. Removal of the battery does
not affect programming.
3.2.3 Color touchscreen specifications
Aspect Ratio: 5:3
Resolution: 800x480 WQVGA
Type: LCD display
Viewing Area: 7 inches diagonal
Rating: Type 4/4X
3.2.4 USB port
The USB port located on the door is meant for downloading
the controller message history, statistics, diagnostics, start
up, and configuration files. The controller firmware can
be uploaded, and the controller configuration can be both