5.4 Panel setup tab
Refer to Appendix C for the menu structure of the Panel
Setup tab.
5.4.1 Language
Eight (8) languages are offered as standard: English, French,
Italian, Spanish, Portuguese, Polish, Dutch, and Turkish.
Refer to Appendix C for programming.
5.4.2 Set time
Factory set to Mountain Standard Time (MST). This menu
item allows the user to adjust the time in a 24-hour format.
5.4.3 Set date
Factory set but allows the user to adjust if needed.
5.4.4 Set day of the week
Factory set but allows the user to adjust if needed.
5.4.5 Auto shutdown
The automatic shutdown mode is user selectable; factory
disabled. If the automatic shutdown mode is disabled, the
pump engine must be stopped via the local stop pushbutton
or switching to OFF mode whether or not the engine
started via an automatic start. If the automatic shutdown
mode is enabled, the controller will stop the pump engine
automatically after all starting causes have been returned to
normal (stop pressure has been achieved) and the running
period timer elapsed.
5.4.6 Source voltage
Factory set. Used to set the nominal system voltage. This
value will also be used to determine any under voltage or
overvoltage conditions.
5.4.7 Battery voltage
The user can select the voltage level of the battery
configuration on the engine. This value will also be used to
determine any under voltage or overvoltage conditions.
5.4.8 Battery type
The user can select the type of batteries used on
the engine.
5.4.9 Common alarm settings
The user can enable or disabled specific conditions that will
trigger the Common Alarm relay. The user can also enable
or disable the audible alarm for specific conditions through
this same menu.
5.4.10 Notification area settings
The user can enable or disable specific events from
showing in the notification area on the HOME tab. The color
of the simulated LED’s can be selected from the following:
green, red, blue, yellow, orange, and purple. The user can
select whether the simulated LED for a specific event
should flash while active in the notification area.
5.4.11 Foam controller
This should be enabled if the controller will be used on
a foam additive system. Certain inputs will automatically
change, and the pressure transducer will be disabled once
this item is enabled.
5.4.12 Menu password
If enabled, the controller will prompt the user to enter
the password when attempting to navigate through the
controller menus.
5.4.13 Controller serial number
Factory set. Used to set the controller serial number. The
controller serial number will be located on the nameplate
which is located on the main door.
5.4.14 Pump serial number
Used to set the pump serial number. The pump serial
number will be located on the nameplate which can typically
be found on the pump housing.
5.4.15 Save configuration to USB
The controller’s configuration can be saved onto a USB
drive. The configuration can then be used on other
controllers that require the same configuration setup. The
configuration will not adjust functionality settings.
5.4.16 Load configuration to usb
A configuration file will be uploaded to the controller from
a USB drive. The data located in the configuration file will
change specific programmed setpoints in the controller.
5.4.17 Save settings as factory default
The current controller settings can be saved as
the factory default for the controller. To change the
factory default settings, the user will have to contact
the factory. This should only be completed by authorized
service representatives.
5.4.18 Restore factory default settings
Controller will be returned to the programmed Factory
Default configuration.