Table 4.
DPCT Programmable Output Alarms
Programmable output alarms
Engine Run
Low Fuel
High Fuel
Fuel Spill
Battery #1 Failure
Battery #2 Failure
Charger #1 Failure
Charger #2 Failure
Coil #1 Failure
Coil #2 Failure
Low Oil Pressure
Overspeed Shutdown
Speed Switch Fault
Fail to Start
Low Engine Temperature
High Engine Temperature
Low Raw Water Flow
High Raw Water Temperature
ECM in Alternate
ECM Warning
ECM Failure
Fuel Injection Malfunction
Below Start Pressure
Start Above Pressure
Pressure Below
Pressure Above
Low Pressure Alarm
High Pressure Alarm
Remote Manual Start
Remote Auto Start
Remote Manual Start/Stop
Remote Manual Stop
Deluge Valve Start
Manual Start
Engine Test Running
Engine Test Failure
Weekly Engine Test Run
Weekly Engine Test Fail
Interlock On
Auto Mode
Manual Mode
Off Mode
Fuel Stop
Crank Battery #1
Crank Battery #2
Low Suction
Low Foam Level
Dump Valve
Low Reservoir
High Reservoir
Reservoir Empty
Relief Valve Discharge
Low Room Temperature
High Room Temperature
AC Power Failure Alarm
AC Power Failure Start
Common alarm
Hardware Fault
Transducer Failure
Pump Room Trouble
Engine Room Trouble
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Disabled
5.10 History stats diag. Tab (history/
statistics/diagnostics)
5.10.1 Message History
The DPCT controller will record a number of items in its
memory to assist with troubleshooting of the system and/
or the fire pump controller. The controller will record up to
65,000 alarm/status messages in its memory that can be
viewed on the main user interface touchscreen or saved to
a USB storage device. Up to ten (10) events can be viewed
on the Message History screen. Event dates and times are
also displayed.
Pressing the Up or Down arrow buttons will advance
through messages saved in the memory one at a time.
Pressing the Page up or Page down arrow buttons will
advance through messages saved in the memory 10
messages at a time.
Pressing and holding the Up, Down, Page Up or Page Down
arrows, allows the messages to scroll continuously through
all messages saved in the memory; The longer that the
button is held the scrolling speed will increase.
Message History data is stored in a comma separated value
(CSV) format.
5.10.2 Controller Statistics
The DPCT controller will record several statistical values that
can be viewed on the user interface touch screen or saved