5. Programming
5.1 Introduction
The DPCT controller is programmable from the user
interface touchscreen. Users can program set points as well
as other parameters. The time, date and set points can only
be changed from the menu system.
The menu system is broken down to tab systems. These
include Home, Startup, Panel Setup, Help, Pressure Settings,
Timer Values, Alarm Setpoints, Inputs/Outputs, History/
Statistics/Diagnostics, and Optional Output Card(s) (if equipped).
5.2 Navigation
In order to navigate through the DPCT operating system,
ensure that the controller is set to OFF mode then press
the tabs at the top of the screen to go through the menus.
If the main menu password is enabled, the user will be
prompted to enter the password to access any of the tabs
except for Help and History/Statistics/Diagnostics.
NOTICE
IT IS RECOMMENDED TO SET UP A MAIN MENU
PASSWORD TO HELP PREVENT ANY UNAUTHORIZED
ACCESS TO THE CONTROLLER. THIS WILL HELP PREVENT
REPROGRAMMING THE CONTROLLER THAT WILL
IMPEDE THE OPERATION OF THE FIRE
PUMP CONTROLLER.
The controller does come with the ability to “Lockout” the
display after thirty (30) minutes of inactivity to minimize
accidental inputs. This feature will not inhibit the normal
operation of the controller. To unlock the display, the user
will be prompted to enter in “DPCT”.
In order to increase the longevity of the display board,
the controller will activate the screensaver after thirty (30)
minutes of inactivity. The screen saver will turn the screen
black and will show a moving EATON logo. To deactivate the
screensaver simply press anywhere on the screen.
All DPCT controller programmable features and associated
set-point possibilities are presented
Table 2.
DPCT Programmable Features
Description
range
Panel setup
Language
English / French / Spanish /
Portuguese / Turkish / Italian / Polish /
Simplified Chinese / Dutch
Set Time
24 Hours
Set Date
Any valid date
Set Day of the Week
Any valid day of the week
Auto Shutdown
Enabled / Disabled
Source Voltage
120/240V
Battery Voltage
12VDC/24VDC
Battery Type
Lead Acid/NiCad
Foam Controller
Enabled / Disabled
Menu Password
Eight
(
8
) to
fifteen
(
15
) digits numeric / Disabled
Controller Serial Number
Standard keyboard entry with space for fifty
(50) digits - Numeric and/or Alphabetical -
Pump Serial Number
Standard keyboard entry with space for fifty
(50) digits - Numeric and/or Alphabetical
Save Configuration to USB
Load Configuration from USB
Save Current Settings as
Factory Default
Restore Controller to Factory
Default Settings
Screen Brightness
20%, 40%, 60%, 80%, 100%
Enable Welcome Screen
Enabled / Disabled
Screen Lock
Enable/Disable
Customer Service Contact
Enable Password Protection
Eight (8) to fifteen (15) digits numeric / Disabled
Company Name
Standard keyboard entry with space for fifty
(50) digits - Numeric and/or Alphabetical
Contact Name
Standard keyboard entry with space for fifty
(50) digits - Numeric and/or Alphabetical
Phone Number
Numeric entry with space for 15 digits
Standard keyboard entry with space for fifty
(50) digits - Numeric and/or Alphabetical
Service Message Trigger
Number of Hours Run
1-999 Hour
Number of Starts
1-999 Pump Runs
Specific Time and Date
24 Hours - Any valid date
De-energize Common Alarm
Enabled / Disabled
Pressure settings
Start Pressure
0-999 PSI / Disabled
Stop Pressure
0-999 PSI / Disabled
Stop Mode
Automatic/Manual
Start Above Pressure
0-999 PSI / Disabled
Pressure Variance Recording
1-999 PSI / Disabled
Hourly Pressure Recording
Enabled / Disabled
Low Suction Shutdown
Enabled / Disabled
Shutdown Delay
0-99 Seconds / Disabled
Reset Mode
Automatic / Manual
Automatic Reset Delay
0-99 Seconds / Disabled
Low Foam Shutdown
Enabled / Disabled
Shutdown Delay
0-99 Seconds / Disabled
Reset Mode
Automatic / Manual
Automatic Reset Delay
0-99 Seconds / Disabled