20
Programming
DPCT IOM InsTruCTIOn OPeraTIOn Manual
MN124018EN January 2023 www.eaton.com
onto a USB storage device. The statistics can be cleared by
pressing the “Clear All Controller Statistics” button. Please
refer to Table
for the statistical values that are recorded.
Table 5.
DPCT Controller Statistics
statistics
Total Powered Time
Total Engine Run Time
Last Engine Run Time
Calls to Start
Engine Starts
Minimum AC Voltage
Maximum AC Voltage
Minimum Battery #1 Voltage
Minimum Battery #2 Voltage
Maximum Battery #1 Voltage
Maximum Battery #2 Voltage
Minimum Battery #1 Amperage
Minimum Battery #2 Amperage
Maximum Battery #1 Amperage
Maximum Battery #2 Amperage
Minimum System Pressure
Maximum System Pressure
Last System Startup
Last Engine Start
Last Engine Test
Last Engine Test
Last Overspeed
Last Low Oil Pressure
Last High Engine Temperature
Last ECM In Alternate
Last Fuel Injection Malfunction
Last ECM Warning
Last ECM Failure
Last High Raw Water Temperature
Last Low Raw Water Temperature
Last Low Engine Temperature
Last Fail to Start
Last Low Fuel
Last High Fuel
Last Fuel Spill
Last Charger #1 Failure
Last Charger #2 Failure
Last Battery #1 Failure
Last Battery #2 Failure
Last Starter Coil #1 Failure
Last Starter Coil #2 Failure
Last AC Power Failure Alarm
Last DC Failure
5.10.3 Controller diagnostics
The DPCT controller will display a number of diagnostic
values that can be viewed on the user interface touch
screen or saved onto a USB storage device.
The main diagnostic page will display the firmware version,
supply voltages, and transducer information.
The input status page will display the state of each input
contact. Pressing the input buttons, the controller will
override the state of that input for one minute. If the button
is depressed a second time, the input will resume normal
operation. If the screen is exited, the input will resume
normal operation.
The output status page will display the state of each output
relay on the I/O board, solenoid valve, and alarm. Pressing
the output buttons, the controller will override the state
of that output for one minute. If the button is depressed a
second time, the output will resume normal operation. If the
screen is exited, the output will resume normal operation.
The audible alarm can be silenced for a period of ten (10)
minutes that will not reset by leaving the screen.
The controller is equipped with on-board communication
diagnostics. The last page in the Controller Diagnostic menu
allows the user to test the transfer and receive functions of
the display board. The screen will provide a prompt that the
test successfully passed or failed.
5.10.4 Start up information
This screen will display all events that were logged while in
the START UP tab.
5.10.5 Save to USB
Data can be saved to an external USB memory device via
the USB port located on the controller door. When a valid
USB device is inserted, the button text will change from
“INSERT USB” to “PRESS TO SAVE”. Once the data has
been saved to the USB, the display will prompt the user to
remove the USB device.
Message history, statistics, diagnostics, configuration,
and the start up file will be saved onto the USB in comma
separated value (CSV) format.