EATON CORPORATION Cutler-Hammer

 

 Pow-R-Command 750 LCD Display  Instruction Leaflet IL01412018E  Effective: February 2009

 

LCD Programming Procedure

 

1. Press the SEL key to begin. The Eaton logo will be displayed.

 

After a few seconds, the 

 

INITIAL STATUS

 

 screen will be displayed.  

If the screen’s contrast is not adjusted properly, you can press and 
hold the 

 

UP

 

 button to lighten the screen and press and hold the 

 

DOWN

 

 

button to darken the screen.

 

2. Login

 

If user passwords have been created on your system by your distrib-
utor/installer, you will see the following screen. Use 

 

UP/DOWN

 

 to 

enter the letters of your password/access code and the 

 

SEL

 

 key to 

advance to the next letter. Advance the cursor past the end of the 
blanks to submit the password/access code.

If this LCD tool has just been powered up, it will have to download a 
database from the PRC750 controller. You may see the following 
screen with the progress indicator:

The database may take about 10 to 20 seconds to download during 
initial startup. Afterward, the 

 

MAIN MENU

 

 will be displayed. To bypass 

the 

 

REFRESHING DATABASE

 

 screen, press the 

 

BACK

 

 

 

key. The 

refresh continues in the background.  

 

Note: 

 

In doing this, the load status table and group data will not be 

refreshed until the refresh is complete.

Jan 10, 2008 11:28A

Group Status:

ON:  ABC          N

OFF:    DEFGHIJKLM  OP

Press SEL for menu

Jan 10, 2008 11:28A

Please Enter

Access Code

Jan 10, 2008 11:28A

Refreshing Database

Please wait... 57%

      MAIN MENU

Command Groups ON/OFF

Panel Status Screen

Configure Groups

Configure Date/Time       _

  Group Status:

ON:  ABC          N  

OFF:    DEFGHIJKLM OP

 

3. Verification of Hardware

 

Verify that the Breaker Control Buses (BCBs) are properly addressed 
and all necessary communication wiring has been terminated. Please 
reference the PRC750 Installation Guide (IL01412008E.pdf) for fur-
ther directions on how to address the BCBs and properly connect 
them to the PRC750 controller.

 

4. Discover Breakers

 

Discover breakers is located in the main menu. The first time the 
Pow-R-Command Control Unit is powered up, it automatically 
“discovers” the breakers that are connected to it through the Breaker 
Control Buses (BCBs). This assumes that the addresses on the BCBs 
have been set correctly (please see Step 3 above). Upon startup, a 
good practice is to bypass all of the breakers ON and then OFF to 
ensure proper communication and discovery. If the breakers have not 
been discovered or the BCBs have not been addressed correctly, 
then some or none of the intended breakers will operate. These sim-
ple steps can be performed in two ways: manually and through the 
LCD display via the 

 

ADVANCED MENU

 

.

 

MANUAL

 

When the LCD face is removed from the PRC control unit, the inner 
circuitry and contacts are exposed to plain sight. Referencing the 
drawing below shows the location of 5 pushbuttons that, when 
depressed and held for 5 seconds each, perform various control 
functions.

From left to right, the buttons are 

 

RESET, BYPASS ON, BYPASS 

OFF, BYPASS CLEAR

 

 and 

 

FIND LOADS

 

 respectively. Before testing 

the breakers and communication, press and hold the 

 

FIND LOADS

 

 

(furthermost right) button for 5 seconds. After which, the 

 

BYPASS 

ON

 

 and 

 

OFF

 

 buttons can be pressed and held for testing purposes. 

Should there be any problems, to check for proper operation of all 
breakers, each breaker has a red indicator for ON, check the wiring 
and communication cables, as well as the BCB addressing. Upon a 
successful test, make sure the 

 

BYPASS CLEAR

 

 button (2nd from 

right) is pressed and held for 5 seconds to relinquish the overridden 
state to the direction of the control unit once again. 

 

Note: 

 

When any load in the panelboard has been 

 

BYPASSED ON

 

 or 

 

BYPASSED OFF

 

, a green bypass LED on the front of the controller will 

be lit. When loads are bypassed, they will not follow schedule and/or 
switch commands.

Содержание Cutler-Hammer Pow-R-Command 750

Страница 1: ... SEL Generally BACK is used to cancel a selection or to move back up through the menu hierarchy UP DOWN are used to scroll through selections on a menu or to change values SEL is used to choose a menu item or to enter a setting Some menu screens will have an arrow symbol in the lower right corner This indicates there are additional menu items for this screen Use the UP DOWN keys to scroll down to ...

Страница 2: ...pdf for fur ther directions on how to address the BCBs and properly connect them to the PRC750 controller 4 Discover Breakers Discover breakers is located in the main menu The first time the Pow R Command Control Unit is powered up it automatically discovers the breakers that are connected to it through the Breaker Control Buses BCBs This assumes that the addresses on the BCBs have been set correc...

Страница 3: ...06 30 SET 07 00 Note Sunrise sunset calculations lose accuracy outside the 62 to 62 range Hit SEL to move to the longitude setting Use UP DOWN to set the longitude value in degrees The longitude range is 180 Alaska to 180 Western Pacific Hit SEL to move to the TIMEZONE setting Use UP DOWN to set the TIMEZONE value in hours The TIMEZONE range is 12 hours west of GMT to 12 hours east of GMT After se...

Страница 4: ...Maint NO Input DI 1 OFF Delay 00 00 Up Down SEL to Change Press BACK when Done The Input Select screen displays the type of input the input that is associated and the Exit time delay Use the UP DOWN to highlight TYPE and press Select An input type list is displayed The list of input types extends beyond one page Use UP DOWN to scroll through the list and highlight the correct switch type Hit Selec...

Страница 5: ...sired group in this case A Use UP to turn the group ON and DOWN to turn the group OFF Verify that the correct set of breakers is turned ON and OFF with the group If not repeat Step 6A Configure Breaker Group A Associate Loads With the Group If there is an associated input for this group turn the group OFF again with the COMMAND GROUPS screen Use the actual input switch motion detector etc to trip ...

Страница 6: ...K when done PICK SCHEDULE DAYS Weekdays____________ Weekends Clear All Days Pick specific days Yes No SMTWTFSH ENTER SCHEDULE DETAIL For GROUP B Days Weekday Start time 12 00 AM End time 12 00 PM Clear Schedule Press BACK when done Use UP DOWN to advance the hours column to the correct hourly starting time Hit SEL to move to the minutes column Use UP DOWN to advance the minutes column to the corre...

Страница 7: ...r module three actions are available for the respective group a Stay Stay in the present state last recorded before loss of communication with the master unit b On Change to the ON state when loss of communication with the master unit occurs c Off Change to the OFF state when loss of communication with the master unit occurs 7 Run Cycle Displays the running count of the number of times the group h...

Страница 8: ...0 character description describing the respective breaker b Name Field The name field allows the user to modify the default 4 character load identifier used with the respective breaker c Address Field Each unit can have a unique address numbered from 1 to 120 for networking purposes This field allows the user to assign an address to the unit d Bypass ON Bypasses ALL loads ON e Bypass ON Bypasses A...

Страница 9: ...f breakers per panelboard 9 18 30 or 42 where 42 circuit is the default a Panelboard List 1 8 1 Panelboard Configuration a Panelboard Number Allows the user to specify a unique numerical address to associate with the panelboard b Panelboard Name Allows the user to alter the default 4 character identifier for the panelboard c Panelboard Type Allows the user to pick the configuration of the panelboa...

Страница 10: ... show up in configure groups after completing these steps please call the PRC Technical Support Line at 1 888 252 6286 Option 3 Documents to Reference 1 Instruction Leaflet IL01412012E Symptom 3 After completing the above steps one or more Smart Breakers are not responding to issued commands Note Make sure all the above steps have been completed before proceeding Causes 1 The Smart Breaker s has h...

Страница 11: ...correct amount 2 Controllers are available in various voltages Check the trans former label for the correct input voltage 3 Press the reset on the transformer there will be a noticeable click if it resets The transformer may have tripped if the trip state continues after resets this is a sign of other issues Make sure no wires are pinched or shorted coming from the controller If none found please ...

Страница 12: ... Location Latitude 90 to 90 __ degrees__ Longitude 180 to 180 __degrees__ Time zone 12hrs to 12hrs __hrs 4 Breaker Groups Mark the groups each circuit is part of Copy this page as needed for additional panelboards GROUPS CIRCUIT A B C D E F G H I J K L M N O P CIRCUIT A B C D E F G H I J K L M N O P 1 22 2 23 3 24 4 25 5 26 6 27 7 28 8 29 9 30 10 31 11 32 12 33 13 34 14 35 15 36 16 37 17 38 18 39 ...

Страница 13: ...__ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays...

Страница 14: ...14 EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Effective February 2009 Notes ...

Страница 15: ...EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Copyright 2009 15 Notes ...

Страница 16: ...E Z7732 February 2009 Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township PA 15108 United States 877 ETN CARE 877 386 2273 Eaton com PowerChain Management Pow R Command Cutler Hammer and Smart Breakers are registered trademarks and trademarks of Eaton Corporation ...

Отзывы: