EATON CORPORATION Cutler-Hammer
Pow-R-Command 750 LCD Display Instruction Leaflet IL01412018E
©
Copyright 2009
5
The list of
predefined descriptions
is several pages long. Use
UP/DOWN
and
SEL
to scroll through the screens and choose a
pre-
defined description
or choose
Enter Characters
(at the end
of the list) to enter a custom description:
Use
UP/DOWN
to scroll up or down through the alphabet and
SEL
to
enter one letter at a time. Continue hitting
SEL
until the end of the
line is reached to enter the description.
Hit
BACK
once (or twice for custom descriptions) to return to the
CONFIGURE GROUP A
screen.
D. Test Group
The group has now been configured and is ready to be tested. Verify
that all breaker primary handles have been returned to the ON posi-
tion. Hit
BACK
to return to the
MAIN MENU
:
Use
UP/DOWN
and
SEL
to select
Command Groups ON/OFF
.
The
COMMAND GROUPS
screen will be shown:
ENTER DESCRIPTION
_ <
MAIN MENU
Command Groups ON/OFF
Panel Status Screen
Configure Groups
Configure Date/Time
Group Status:
ON: ABC N
OFF: DEFGHIJKLM OP
COMMAND GROUPS
ON:
A
BC N
OFF:
_
DEFGHIJKLM OP
GRPA ON
Cleaning Lights
Use BACK/SEL to select
UP - ON, DOWN - OFF
Use the
BACK
and
SEL
to highlight the
desired group
(in this case,
A). Use
UP
to turn the group ON and
DOWN
to turn the group OFF.
Verify that the correct set of breakers is turned ON and OFF with
the group. If not, repeat
Step 6A — Configure Breaker Group A —
Associate Loads With the Group
. If there is an associated input for
this group, turn the group OFF again with the
COMMAND GROUPS
screen. Use the actual input — switch, motion detector, etc., to trip
the input. Verify that the proper group is turned ON. If not,
repeat
Step 6B — Configure Breaker Group A — Associate Inputs With
the Group.
Verify that the
group description
on the fifth line of the
COMMAND
GROUPS
screen is the correct description for this group. If not, repeat
Step 6C — Configure Breaker GROUP A — Set Group Description.
7. Repeat Step 6 for each Group B through P
8. Schedule Groups
The final step in initial setup is to enter the schedules for each group.
From the
MAIN MENU
, select
Configure Groups
. The following
screen will be displayed:
Hit
SEL
to select
Group A
. The following menu is displayed:
Select
Modify Schedules
. The following screen is displayed:
SELECT GROUP
TO CONFIGURE:
Group A GRPA OFF
GROUP A LIGHTS
15 loads in group.
Use up/down/sel to
change selection
CONFIGURE GROUP A
Group A GRPA ON
OFFICE LIGHTING
Associate Loads
Associate Inputs
Modify Schedules
Modify Description
Modify Schedules for
Group A OFFICE LIGHT
Use SEL to edit sch.
Days --ON-- --OFF-
(Add New Schedule)