EATON CORPORATION Cutler-Hammer

 Pow-R-Command 750 LCD Display  Instruction Leaflet IL01412018E  

©

Copyright 2009

5

The list of 

predefined descriptions

 is several pages long. Use 

UP/DOWN

 and 

SEL

 to scroll through the screens and choose a 

pre-

defined description

 or choose 

Enter Characters

 (at the end 

of the list) to enter a custom description:

Use 

UP/DOWN

 to scroll up or down through the alphabet and 

SEL

 to 

enter one letter at a time. Continue hitting 

SEL

 until the end of the 

line is reached to enter the description.

Hit 

BACK

 once (or twice for custom descriptions) to return to the 

CONFIGURE GROUP A

 screen.

D. Test Group

The group has now been configured and is ready to be tested. Verify 
that all breaker primary handles have been returned to the ON posi-
tion. Hit 

BACK

 to return to the 

MAIN MENU

:

Use 

UP/DOWN

 and 

SEL

 to select 

Command Groups ON/OFF

.  

The 

COMMAND GROUPS

 screen will be shown:

  ENTER DESCRIPTION

_                   <

      MAIN MENU

Command Groups ON/OFF

Panel Status Screen

Configure Groups

Configure Date/Time

  Group Status:

ON:  ABC          N  

OFF:    DEFGHIJKLM OP

   COMMAND GROUPS

ON:  

BC          N  

OFF: 

_

  DEFGHIJKLM OP

 GRPA      ON

 Cleaning Lights

Use BACK/SEL to select

UP - ON, DOWN - OFF

Use the 

BACK

 and 

SEL

 to highlight the 

desired group

 (in this case, 

A). Use 

UP

 to turn the group ON and 

DOWN

 to turn the group OFF. 

Verify that the correct set of breakers is turned ON and OFF with 
the group. If not, repeat 

Step 6A — Configure Breaker Group A — 

Associate Loads With the Group

. If there is an associated input for 

this group, turn the group OFF again with the 

COMMAND GROUPS

 

screen. Use the actual input — switch, motion detector, etc., to trip 
the input. Verify that the proper group is turned ON. If not, 

repeat 

Step 6B — Configure Breaker Group A — Associate Inputs With 
the Group.

Verify that the 

group description

 on the fifth line of the 

COMMAND 

GROUPS

 screen is the correct description for this group. If not, repeat 

Step 6C — Configure Breaker GROUP A — Set Group Description.

7. Repeat Step 6 for each Group B through P

8. Schedule Groups

The final step in initial setup is to enter the schedules for each group.  
From the 

MAIN MENU

, select 

Configure Groups

. The following 

screen will be displayed:

Hit 

SEL

 to select 

Group A

. The following menu is displayed:

Select 

Modify Schedules

. The following screen is displayed:

SELECT GROUP

    TO CONFIGURE:

Group A  GRPA    OFF

 GROUP A LIGHTS

 15 loads in group.

Use up/down/sel to

  change selection

  CONFIGURE GROUP A

Group A  GRPA    ON

 OFFICE LIGHTING

Associate Loads

Associate Inputs

Modify Schedules

Modify Description

Modify Schedules for

Group A OFFICE LIGHT

Use SEL to edit sch.

Days    --ON-- --OFF-

 (Add New Schedule)

Содержание Cutler-Hammer Pow-R-Command 750

Страница 1: ... SEL Generally BACK is used to cancel a selection or to move back up through the menu hierarchy UP DOWN are used to scroll through selections on a menu or to change values SEL is used to choose a menu item or to enter a setting Some menu screens will have an arrow symbol in the lower right corner This indicates there are additional menu items for this screen Use the UP DOWN keys to scroll down to ...

Страница 2: ...pdf for fur ther directions on how to address the BCBs and properly connect them to the PRC750 controller 4 Discover Breakers Discover breakers is located in the main menu The first time the Pow R Command Control Unit is powered up it automatically discovers the breakers that are connected to it through the Breaker Control Buses BCBs This assumes that the addresses on the BCBs have been set correc...

Страница 3: ...06 30 SET 07 00 Note Sunrise sunset calculations lose accuracy outside the 62 to 62 range Hit SEL to move to the longitude setting Use UP DOWN to set the longitude value in degrees The longitude range is 180 Alaska to 180 Western Pacific Hit SEL to move to the TIMEZONE setting Use UP DOWN to set the TIMEZONE value in hours The TIMEZONE range is 12 hours west of GMT to 12 hours east of GMT After se...

Страница 4: ...Maint NO Input DI 1 OFF Delay 00 00 Up Down SEL to Change Press BACK when Done The Input Select screen displays the type of input the input that is associated and the Exit time delay Use the UP DOWN to highlight TYPE and press Select An input type list is displayed The list of input types extends beyond one page Use UP DOWN to scroll through the list and highlight the correct switch type Hit Selec...

Страница 5: ...sired group in this case A Use UP to turn the group ON and DOWN to turn the group OFF Verify that the correct set of breakers is turned ON and OFF with the group If not repeat Step 6A Configure Breaker Group A Associate Loads With the Group If there is an associated input for this group turn the group OFF again with the COMMAND GROUPS screen Use the actual input switch motion detector etc to trip ...

Страница 6: ...K when done PICK SCHEDULE DAYS Weekdays____________ Weekends Clear All Days Pick specific days Yes No SMTWTFSH ENTER SCHEDULE DETAIL For GROUP B Days Weekday Start time 12 00 AM End time 12 00 PM Clear Schedule Press BACK when done Use UP DOWN to advance the hours column to the correct hourly starting time Hit SEL to move to the minutes column Use UP DOWN to advance the minutes column to the corre...

Страница 7: ...r module three actions are available for the respective group a Stay Stay in the present state last recorded before loss of communication with the master unit b On Change to the ON state when loss of communication with the master unit occurs c Off Change to the OFF state when loss of communication with the master unit occurs 7 Run Cycle Displays the running count of the number of times the group h...

Страница 8: ...0 character description describing the respective breaker b Name Field The name field allows the user to modify the default 4 character load identifier used with the respective breaker c Address Field Each unit can have a unique address numbered from 1 to 120 for networking purposes This field allows the user to assign an address to the unit d Bypass ON Bypasses ALL loads ON e Bypass ON Bypasses A...

Страница 9: ...f breakers per panelboard 9 18 30 or 42 where 42 circuit is the default a Panelboard List 1 8 1 Panelboard Configuration a Panelboard Number Allows the user to specify a unique numerical address to associate with the panelboard b Panelboard Name Allows the user to alter the default 4 character identifier for the panelboard c Panelboard Type Allows the user to pick the configuration of the panelboa...

Страница 10: ... show up in configure groups after completing these steps please call the PRC Technical Support Line at 1 888 252 6286 Option 3 Documents to Reference 1 Instruction Leaflet IL01412012E Symptom 3 After completing the above steps one or more Smart Breakers are not responding to issued commands Note Make sure all the above steps have been completed before proceeding Causes 1 The Smart Breaker s has h...

Страница 11: ...correct amount 2 Controllers are available in various voltages Check the trans former label for the correct input voltage 3 Press the reset on the transformer there will be a noticeable click if it resets The transformer may have tripped if the trip state continues after resets this is a sign of other issues Make sure no wires are pinched or shorted coming from the controller If none found please ...

Страница 12: ... Location Latitude 90 to 90 __ degrees__ Longitude 180 to 180 __degrees__ Time zone 12hrs to 12hrs __hrs 4 Breaker Groups Mark the groups each circuit is part of Copy this page as needed for additional panelboards GROUPS CIRCUIT A B C D E F G H I J K L M N O P CIRCUIT A B C D E F G H I J K L M N O P 1 22 2 23 3 24 4 25 5 26 6 27 7 28 8 29 9 30 10 31 11 32 12 33 13 34 14 35 15 36 16 37 17 38 18 39 ...

Страница 13: ...__ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays...

Страница 14: ...14 EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Effective February 2009 Notes ...

Страница 15: ...EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Copyright 2009 15 Notes ...

Страница 16: ...E Z7732 February 2009 Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township PA 15108 United States 877 ETN CARE 877 386 2273 Eaton com PowerChain Management Pow R Command Cutler Hammer and Smart Breakers are registered trademarks and trademarks of Eaton Corporation ...

Отзывы: