background image

 

EATON CORPORATION Cutler-Hammer

 

 Pow-R-Command 750 LCD Display  Instruction Leaflet IL01412018E  

 

©

 

Copyright 2009

 

3

 

5. Set Date/Time/DST/Location

 

From the 

 

MAIN MENU

 

, select 

 

Configure Date/Time

 

. The 

following menu will be displayed:

Use 

 

UP/DOWN

 

 to select 

 

Change Date

 

. Use 

 

SEL

 

 to move through 

the date digits. Use 

 

UP/DOWN

 

 to set the month, day and year, 

respectively. After setting the year, hit 

 

SEL

 

 one more time. The 

new values will be displayed in the PRC750.  

Use 

 

UP/DOWN

 

 to highlight 

 

Change Time

 

. Use 

 

SEL

 

 to move through 

the 

 

time digits

 

. Use 

 

UP/DOWN

 

 to set the 

 

hour, minute

 

 and 

 

AM/

PM

 

, respectively. After setting the 

 

AM/PM

 

, hit SEL one more time.  

The new values will be displayed on the PRC750.  

Use 

 

UP/DOWN

 

 to highlight 

 

Change DST

 

. Use 

 

SEL

 

 to start editing the 

DST setting. Use 

 

UP/DOWN

 

 to choose 

 

NONE, AUTO

 

 or 

 

MANUAL

 

. If 

 

MANUAL

 

 is chosen, settings for start and end date will appear. Hit 

 

SEL

 

 

to jump to the 

 

start date

 

. Use 

 

UP/DOWN

 

 to set the 

 

month

 

 and 

 

day

 

 

values. Use 

 

SEL

 

 to move through the digits. After setting the 

 

DST

 

 

setting (or dates for 

 

MANUAL

 

), hit 

 

SEL

 

 one more time. The new values 

will be displayed on the PRC750.  

Use 

 

UP/DOWN

 

 to highlight 

 

Change ASTRO Locate

 

. Hit 

 

SEL

 

 to start 

editing the location. The following screen will be displayed:

Use 

 

UP/DOWN

 

 to set the latitude (LAT) value in degrees. The latitude 

range is -90 (South) to +90 (North).

CONFIGURE DATE/TIME

Change Time  11:37 AM

Change DST   MANUAL

 St: mm/dd End: mm/dd

Change Astro Loc.

ASTRO LAT: 

33.00

      LON: 84.00

    TIMEZONE: 5

RISE 06:30 SET 07:00

Note: 

Sunrise/sunset calculations lose accuracy outside the -62 to 

+62 range. Hit 

SEL

 to move to the longitude setting. Use 

UP/DOWN

 

to set the longitude value in degrees. The longitude range is +180 
(Alaska) to -180 (Western Pacific). Hit 

SEL

 to move to the 

TIMEZONE

 

setting. Use 

UP/DOWN

 to set the 

TIMEZONE

 value in hours. The 

TIMEZONE

 range is +12 hours (west of GMT) to -12 hours (east of 

GMT). After setting the 

TIMEZONE

, hit 

SEL

 one more time. The new 

values will be displayed on the PRC750. The 

RISE

 and 

SET

 times will 

update with the new values calculated from the input latitude and lon-
gitude and the screen will return to the 

Configure Date/Time

 

menu. Use 

BACK

 to return to the 

MAIN MENU

.

6. Configure Breaker Group A

From the 

MAIN MENU

, select 

Configure Groups

. The following 

screen will be displayed:

The 

group

 is shown, followed by its 

current status

 (

OFF

 in 

this example). The next line is the 

group description

, if it 

exists (

GROUP A LIGHTS

 in this example), followed by the 

number 

of loads (breakers)

 that has been associated with this group 

(15 in this example).  Another group can be selected by using the 

UP/DOWN

 arrows.

Hit 

SEL

 to select 

Group A

. The following menu is displayed:

A. Associate Loads With the Group

Hit 

SEL

 to select 

Associate Loads

. The following screen is 

displayed:

SELECT GROUP

    TO CONFIGURE:

Group A  GRPA    OFF

 GROUP A LIGHTS

 15 loads in group.

Use up/down/sel to

  change selection

  CONFIGURE GROUP A

Group A  GRPA    ON

 OFFICE LIGHTING

Associate Loads______

Associate Inputs

Modify Schedules

Modify Description

Associate Loads

  With Group A

Select loads for this
  group individually

Add all loads which
  are currently ON

Clear all loads from 
  this group

Содержание Cutler-Hammer Pow-R-Command 750

Страница 1: ... SEL Generally BACK is used to cancel a selection or to move back up through the menu hierarchy UP DOWN are used to scroll through selections on a menu or to change values SEL is used to choose a menu item or to enter a setting Some menu screens will have an arrow symbol in the lower right corner This indicates there are additional menu items for this screen Use the UP DOWN keys to scroll down to ...

Страница 2: ...pdf for fur ther directions on how to address the BCBs and properly connect them to the PRC750 controller 4 Discover Breakers Discover breakers is located in the main menu The first time the Pow R Command Control Unit is powered up it automatically discovers the breakers that are connected to it through the Breaker Control Buses BCBs This assumes that the addresses on the BCBs have been set correc...

Страница 3: ...06 30 SET 07 00 Note Sunrise sunset calculations lose accuracy outside the 62 to 62 range Hit SEL to move to the longitude setting Use UP DOWN to set the longitude value in degrees The longitude range is 180 Alaska to 180 Western Pacific Hit SEL to move to the TIMEZONE setting Use UP DOWN to set the TIMEZONE value in hours The TIMEZONE range is 12 hours west of GMT to 12 hours east of GMT After se...

Страница 4: ...Maint NO Input DI 1 OFF Delay 00 00 Up Down SEL to Change Press BACK when Done The Input Select screen displays the type of input the input that is associated and the Exit time delay Use the UP DOWN to highlight TYPE and press Select An input type list is displayed The list of input types extends beyond one page Use UP DOWN to scroll through the list and highlight the correct switch type Hit Selec...

Страница 5: ...sired group in this case A Use UP to turn the group ON and DOWN to turn the group OFF Verify that the correct set of breakers is turned ON and OFF with the group If not repeat Step 6A Configure Breaker Group A Associate Loads With the Group If there is an associated input for this group turn the group OFF again with the COMMAND GROUPS screen Use the actual input switch motion detector etc to trip ...

Страница 6: ...K when done PICK SCHEDULE DAYS Weekdays____________ Weekends Clear All Days Pick specific days Yes No SMTWTFSH ENTER SCHEDULE DETAIL For GROUP B Days Weekday Start time 12 00 AM End time 12 00 PM Clear Schedule Press BACK when done Use UP DOWN to advance the hours column to the correct hourly starting time Hit SEL to move to the minutes column Use UP DOWN to advance the minutes column to the corre...

Страница 7: ...r module three actions are available for the respective group a Stay Stay in the present state last recorded before loss of communication with the master unit b On Change to the ON state when loss of communication with the master unit occurs c Off Change to the OFF state when loss of communication with the master unit occurs 7 Run Cycle Displays the running count of the number of times the group h...

Страница 8: ...0 character description describing the respective breaker b Name Field The name field allows the user to modify the default 4 character load identifier used with the respective breaker c Address Field Each unit can have a unique address numbered from 1 to 120 for networking purposes This field allows the user to assign an address to the unit d Bypass ON Bypasses ALL loads ON e Bypass ON Bypasses A...

Страница 9: ...f breakers per panelboard 9 18 30 or 42 where 42 circuit is the default a Panelboard List 1 8 1 Panelboard Configuration a Panelboard Number Allows the user to specify a unique numerical address to associate with the panelboard b Panelboard Name Allows the user to alter the default 4 character identifier for the panelboard c Panelboard Type Allows the user to pick the configuration of the panelboa...

Страница 10: ... show up in configure groups after completing these steps please call the PRC Technical Support Line at 1 888 252 6286 Option 3 Documents to Reference 1 Instruction Leaflet IL01412012E Symptom 3 After completing the above steps one or more Smart Breakers are not responding to issued commands Note Make sure all the above steps have been completed before proceeding Causes 1 The Smart Breaker s has h...

Страница 11: ...correct amount 2 Controllers are available in various voltages Check the trans former label for the correct input voltage 3 Press the reset on the transformer there will be a noticeable click if it resets The transformer may have tripped if the trip state continues after resets this is a sign of other issues Make sure no wires are pinched or shorted coming from the controller If none found please ...

Страница 12: ... Location Latitude 90 to 90 __ degrees__ Longitude 180 to 180 __degrees__ Time zone 12hrs to 12hrs __hrs 4 Breaker Groups Mark the groups each circuit is part of Copy this page as needed for additional panelboards GROUPS CIRCUIT A B C D E F G H I J K L M N O P CIRCUIT A B C D E F G H I J K L M N O P 1 22 2 23 3 24 4 25 5 26 6 27 7 28 8 29 9 30 10 31 11 32 12 33 13 34 14 35 15 36 16 37 17 38 18 39 ...

Страница 13: ...__ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays...

Страница 14: ...14 EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Effective February 2009 Notes ...

Страница 15: ...EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Copyright 2009 15 Notes ...

Страница 16: ...E Z7732 February 2009 Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township PA 15108 United States 877 ETN CARE 877 386 2273 Eaton com PowerChain Management Pow R Command Cutler Hammer and Smart Breakers are registered trademarks and trademarks of Eaton Corporation ...

Отзывы: