EATON CORPORATION Cutler-Hammer

 Pow-R-Command 750 LCD Display  Instruction Leaflet IL01412018E  

©

Copyright 2009

11

Symptom 4:

 I have a 30-circuit panelboard, and my Smart Breaker 

positions on the left side are not numbered correctly from within 
the LCD.

Cause: 

The controller needs to be configured to represent the type of 

panelboard that it is controlling (i.e., 42 circuit, 30 circuit, etc.).

Solution: 

The controller needs to be configured to represent the type 

of panelboard that it is controlling. In this case, the controller needs to 
be configured to control a 30-circuit panelboard. All controllers default 
to control a 42-circuit panelboard. To adjust this setting, the following 
steps need to be taken:  

1. From the 

MAIN MENU

, scroll down and highlight, but don’t 

select, 

BYPASS LOADS ON/OFF

. Hold the 

BACK

 button for about 

5 seconds.  

2. An 

ADVANCED MENU

 item will appear. Scroll down and select 

ADVANCED MENU

.  

3. Scroll down and select 

SUBPANEL CONFIGURATION

. Here, you 

should see a list of BCBs and their addresses. (If nothing shows 
up on the BCB list, please stop and go through the steps 
depicted in Symptom 2 above and then continue.)  

4. The BCBs should be split into left and right for each panelboard. 

Highlight the first BCB that needs to be configured for a 30-
circuit panelboard. Press 

SEL

.  

5. Scroll down to 

TYPE

 and press 

SEL

. If this BCB is a left side 

BCB, then 

SEL

 LEFT-30. If it is a right side BCB, then 

SEL

 

RIGHT-30.  

6. Repeat for the remainder of BCBs that need to be configured for 

30-circuit panelboards.

Indicator Lights/LEDS

The LEDs on the controller and BCBs can be used to help diagnose 
an issue with the current setup of the system. 

Symptom 1:

 Power LED not lit on controller when the power switch 

is toggled on.

Causes:

1. No ac voltage to the controller transformer.

2. Incorrect voltage to the control transformer.

3. No 24 Vac voltage to controller unit.

4. Blown fuse within the controller.

Solutions:

1. Make sure there is ac voltage to the control transformer, and it is 

the correct amount.

2. Controllers are available in various voltages. Check the trans-

former label for the correct input voltage.

3. Press the reset on the transformer, there will be a noticeable 

click if it resets. The transformer may have tripped, if the trip 
state continues after resets this is a sign of other issues. Make 
sure no wires are pinched or shorted coming from the controller. 
If none found, please contact technical support.

4. Check the plug on the right side of the controller for proper con-

nection of the 24 Vac from the transformer. If plugged in, check 
for 24 Vac at the plug.

5. Check the internal fuse in the unit. It is located behind the face-

plate. Four screws must be removed to gain access to the fuse. 
Check the status of the fuse in the lower right hand corner of the 
unit. If this fuse is blown, it needs to be replaced.

Symptom 2:

 Power LED lit on the controller but not lit on BCB when 

the controller power switch is toggled on. 

Causes:

1. No connection from the controller to BCB.

2. Incorrect wiring on the BCB from the controller.

3. Problem with the output voltage from the controllers.

Solutions:

1. Check the plug on the BCB and the controller for proper 

connection.

2. Check for correct wiring of the BCB; see the side of the control-

ler and BCB for proper connections. Also, the connections are 
included in the Instruction Manual.

3. Check for 24 Vac from the controller; see the label on the side of 

the controller for the correct pins of the 4-pin connector. If volt-
age is not present, please contact PRC Technical Support Line at 
1-888-252-6286, Option 3.

Symptom 3:

  The “POWER” LED and the “LAN” LED are lit, and the 

“RUN” LED blinks twice every few seconds on the BCB.

Cause: 

There is a communication failure between the controller and 

BCB caused by incorrect wiring of the BCB.

Solution: 

Check wiring (L+ and L- may be crossed or 24V~ and COM 

may be crossed from the controller to the BCB).

Symptom 4:

 The “POWER” LED is lit, and the “LAN” LED flickers 

every so often with the “RUN” LED blinking twice every few 
seconds on the BCB.

Cause: 

There is a communication failure between the controller and 

BCB caused by incorrect wiring of the BCB.

Solution: 

Check wiring; L- may be disconnected.

Содержание Cutler-Hammer Pow-R-Command 750

Страница 1: ... SEL Generally BACK is used to cancel a selection or to move back up through the menu hierarchy UP DOWN are used to scroll through selections on a menu or to change values SEL is used to choose a menu item or to enter a setting Some menu screens will have an arrow symbol in the lower right corner This indicates there are additional menu items for this screen Use the UP DOWN keys to scroll down to ...

Страница 2: ...pdf for fur ther directions on how to address the BCBs and properly connect them to the PRC750 controller 4 Discover Breakers Discover breakers is located in the main menu The first time the Pow R Command Control Unit is powered up it automatically discovers the breakers that are connected to it through the Breaker Control Buses BCBs This assumes that the addresses on the BCBs have been set correc...

Страница 3: ...06 30 SET 07 00 Note Sunrise sunset calculations lose accuracy outside the 62 to 62 range Hit SEL to move to the longitude setting Use UP DOWN to set the longitude value in degrees The longitude range is 180 Alaska to 180 Western Pacific Hit SEL to move to the TIMEZONE setting Use UP DOWN to set the TIMEZONE value in hours The TIMEZONE range is 12 hours west of GMT to 12 hours east of GMT After se...

Страница 4: ...Maint NO Input DI 1 OFF Delay 00 00 Up Down SEL to Change Press BACK when Done The Input Select screen displays the type of input the input that is associated and the Exit time delay Use the UP DOWN to highlight TYPE and press Select An input type list is displayed The list of input types extends beyond one page Use UP DOWN to scroll through the list and highlight the correct switch type Hit Selec...

Страница 5: ...sired group in this case A Use UP to turn the group ON and DOWN to turn the group OFF Verify that the correct set of breakers is turned ON and OFF with the group If not repeat Step 6A Configure Breaker Group A Associate Loads With the Group If there is an associated input for this group turn the group OFF again with the COMMAND GROUPS screen Use the actual input switch motion detector etc to trip ...

Страница 6: ...K when done PICK SCHEDULE DAYS Weekdays____________ Weekends Clear All Days Pick specific days Yes No SMTWTFSH ENTER SCHEDULE DETAIL For GROUP B Days Weekday Start time 12 00 AM End time 12 00 PM Clear Schedule Press BACK when done Use UP DOWN to advance the hours column to the correct hourly starting time Hit SEL to move to the minutes column Use UP DOWN to advance the minutes column to the corre...

Страница 7: ...r module three actions are available for the respective group a Stay Stay in the present state last recorded before loss of communication with the master unit b On Change to the ON state when loss of communication with the master unit occurs c Off Change to the OFF state when loss of communication with the master unit occurs 7 Run Cycle Displays the running count of the number of times the group h...

Страница 8: ...0 character description describing the respective breaker b Name Field The name field allows the user to modify the default 4 character load identifier used with the respective breaker c Address Field Each unit can have a unique address numbered from 1 to 120 for networking purposes This field allows the user to assign an address to the unit d Bypass ON Bypasses ALL loads ON e Bypass ON Bypasses A...

Страница 9: ...f breakers per panelboard 9 18 30 or 42 where 42 circuit is the default a Panelboard List 1 8 1 Panelboard Configuration a Panelboard Number Allows the user to specify a unique numerical address to associate with the panelboard b Panelboard Name Allows the user to alter the default 4 character identifier for the panelboard c Panelboard Type Allows the user to pick the configuration of the panelboa...

Страница 10: ... show up in configure groups after completing these steps please call the PRC Technical Support Line at 1 888 252 6286 Option 3 Documents to Reference 1 Instruction Leaflet IL01412012E Symptom 3 After completing the above steps one or more Smart Breakers are not responding to issued commands Note Make sure all the above steps have been completed before proceeding Causes 1 The Smart Breaker s has h...

Страница 11: ...correct amount 2 Controllers are available in various voltages Check the trans former label for the correct input voltage 3 Press the reset on the transformer there will be a noticeable click if it resets The transformer may have tripped if the trip state continues after resets this is a sign of other issues Make sure no wires are pinched or shorted coming from the controller If none found please ...

Страница 12: ... Location Latitude 90 to 90 __ degrees__ Longitude 180 to 180 __degrees__ Time zone 12hrs to 12hrs __hrs 4 Breaker Groups Mark the groups each circuit is part of Copy this page as needed for additional panelboards GROUPS CIRCUIT A B C D E F G H I J K L M N O P CIRCUIT A B C D E F G H I J K L M N O P 1 22 2 23 3 24 4 25 5 26 6 27 7 28 8 29 9 30 10 31 11 32 12 33 13 34 14 35 15 36 16 37 17 38 18 39 ...

Страница 13: ...__ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays S M T W T F S H Start__ __ AM PM End __ __ AM PM Group Weekends Weekdays...

Страница 14: ...14 EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Effective February 2009 Notes ...

Страница 15: ...EATON CORPORATION Cutler Hammer Pow R Command 750 LCD Display Instruction Leaflet IL01412018E Copyright 2009 15 Notes ...

Страница 16: ...E Z7732 February 2009 Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township PA 15108 United States 877 ETN CARE 877 386 2273 Eaton com PowerChain Management Pow R Command Cutler Hammer and Smart Breakers are registered trademarks and trademarks of Eaton Corporation ...

Отзывы: