Parameter
Accuracy
Current (
<
5 amps)
±
.5% of Full Scale
Current (
>
5 amps)
±
.5% of Reading
Voltage, line-to-line
±
.5% of Full Scale
Voltage, line-to-neutral
±
.5% of Full Scale
Watts (
<
5 amps)
±
1% of Full Scale
Watts (
>
5 amps)
±
1% of Reading
vars (
<
5 amps)
±
1% of Full Scale
vars (
>
5 amps)
±
1% of Reading
VA (
<
5 amps)
±
1% of Full Scale
VA (
>
5 amps)
±
1% of Reading
Power Factor
±
2% of Full Scale
Frequency
±
0.1 Hz
Table 2.3 IQ 300 Metering Accuracy
ANSI C12 Note:
The IQ 300 has been designed and verified to meet ANSI C12
Class 10 Revenue metering accuracy. This classification makes the IQ 300 an ideal
choice for sub-metering and sub-billing applications.
Table 2.2 IQ 300 Operating Specifications (cont.)
Control Power
Input Range
IQ 310 Base
IQ 320 Base
IQ 300 Base
110-240 Vac
±
10%
90-600 Vac
±
10%
90-600 Vac
±
10%
125-250 Vdc
±
10%
48-250 Vdc
±
10%
48-250 Vdc
±
10%
Frequency Range
50/60 Hz
—
Burden
IQ 310 Base
IQ 320 Base
IQ 300 Base
7 W
180 mA
200 mA
7 W
7 W
8 W