IL17574C
Page 5-12
Effective Date: 2/04
IQ 300
Page 5-12
Effective Date: 2/04
For more information visit:
www.cutler-hammer.eaton.com
Field Name
Example
(Hex)
Slave Address
TBD
Function
04
Byte Count
0C
Data Hi (Register 6100)
00
Data Lo (Register 6100)
0A
:
:
:
:
Data Hi (Register 6106)
00
Data Lo (Register 6106)
0A
Error Check (LRC or CRC)
--
Table 5.10 Example Register Data
Response
The register data in the response message are packed as two bytes per register,
with binary contents right justified with in each byte. For each register, the first byte
contains the high-order bits and the second contains the low-order bits, see Table
5.10.