Effective Date: 2/04
IL17574C
Page 1-3
IQ 300
Effective Date: 2/04
Page 1-3
For more information visit:
www.cutler-hammer.eaton.com
The IQ 300 series includes four variations of the IQ 300 Base Module and a single
IQ 300 Display Module that functions with any Base type. The IQ 310 Base Module
is a reduced function variation, while the IQ 320, the IQ 330 and the IQ 330M Base
Modules have additional capabilities.
The IQ 320 includes a wider ranging power supply, PowerNet communication, by
way of the INCOM port, which provides information to the network master device
and a KYZ Pulse output proportional to the energy consumed by the system being
monitored.
The IQ 330 includes a wider ranging power supply. PowerNet communication, by
way of the INCOM port, provides information to the network master device. A KYZ
Pulse output proportional to the energy consumed by the system being monitored, 2
digital outputs (form A contacts), 2 digital inputs, that read and count transitional
edges (that occur as often as 8ms) and 1 analog input to read 4 to 20 ma signal and
display a percentage of 0 to 100.
While the IQ 330M includes everything the IQ 330 Base Module includes, the
INCOM communication is replaced with MODBUS.
IQ300 Series Features:
Meter
Model
Display
Size
(in inches)
Pow er
Supply
Comm
KYZ
Output
Digital
Inputs
Digital
Outputs
Analog
Input
Utility
Sealing
IQ310 10.25x6.72
110-240 Vac
125-250 Vdc
NO
NO
NO
NO
NO
NO
IQ320 10.25x6.72
90-600 Vac
48-250 Vdc
INCOM
YES
NO
NO
NO
NO
IQ330 10.25x6.72
90-600 Vac
48-250 Vdc
INCOM
YES
2
2
1
YES
IQ330M 10.25x6.72
90-600 Vac
48-250 Vdc Modbus YES
2
2
1
YES