background image

5

Instructional Leafl et 

IL03901001E

Effective June 2009

DS6 series soft start controllers 
  
  

EATON CORPORATION

 www.eaton.com

24 Vdc power supply requirements

The 24 Vdc power supply for your DS6 soft start controller must 
meet or exceed the following requirements:

• 

Minimum steady-state current: 1W (35 mA)

• 

Minimum start command current: 2W (65 mA)

• 

Minimum bypass contactor inrush current: 600 mA for 50 ms

• 

Voltage stability: 24 Vdc +10%/–15%

Operations

• 

24 Vdc control voltage is applied to te24

• 

The status light will illuminate after the starter has completed 
initialization, closing contacts 23/24, and indicating READY status

• 

Line voltage is applied to the starter by closing the 
mains contactor

• 

The soft start controller issues a START command by applying 
+24 Vdc to terminals EN and +A1. Contacts 13 and 14 will close 
when the end of the ramp time is reached

ote: 

N

Bypass contactors close at the end of ramp time + ~0.18 seconds. 

It is important to correctly set the ramp time, so the bypass contactors will 
close within 5 seconds after the motor has achieved rated RPM. 

• 

To initiate a STOP command, 24 Vdc from terminal EN 
and +A1 or EN

• 

To initiate a RAMP STOP command, 24 Vdc from 
teA1

Adjusting the soft start controller parameters

There are three adjustments to the DS6 soft start controller:

• 

t-Start = ramp time

• 

u-Start = initial voltage (torque)

• 

t-Stop = stop ramp time

ote: 

N

In all cases, motor rotation should begin within 2–3 seconds after the 

START command is sent to the soft start controller.

Figure 6. DS6 Ramp Functions

u-Start

U

t-Start

t-Stop

t

t-Stop = 0

13 14

TOR

(Top of Ramp)

Содержание Cutler-Hammer DS6 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require furthe...

Страница 2: ...Y DEATH OR SUBSTANTIAL PROPERTY DAMAGE DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED...

Страница 3: ...llowable Fuse Size 200V 230V 460V hp hp hp DS6 34DSX041N0 N 40 10 10 30 HFD3150L 150A Class RK5 DS6 34DSX055N0 N 52 15 20 40 HFD3200L 200A Class RK5 DS6 34DSX068N0 N 65 20 25 50 HJD3250 200A Class RK5...

Страница 4: ...3 24 Ready status contacts NO 0V 24 TOR Ready A2 EN A1 13 14 24 24V 0V 23 0V 24 A2 EN A1 13 14 24 23 Q1 Control Wiring Terminal Block Figure 5 Direct Start With Soft Stop Table 7 DS6 Terminal Control...

Страница 5: ...soft start controller issues a START command by applying 24 Vdc to terminals EN and A1 Contacts 13 and 14 will close when the end of the ramp time is reached ote N Bypass contactors close at the end...

Страница 6: ...tarting torque Mixer dry materials 15s 56 75 Pelletizing machine 20s 64 100 Pump piston 25s 30s 82 175 Possible high starting torque Pump centrifugal 10s 30s 37 25 Moving pavement unloaded 20s 37 25 E...

Страница 7: ...heck for the following conditions verify proper motor cable connections and check for condi tion and security Verify installation and integrity of motor coupling to load Test motor for proper conditio...

Страница 8: ...Operation During Motor Start Run and Stop Conditions Condition Motor Status Ready Contacts TOR Contacts Error LED Run LED 24 Vdc applied and initialization complete Off Closed Open Flashing short pul...

Отзывы: