Instructional Leafl et
IL03901001E
Effective June 2009
DS6 series soft start controllers
EATON CORPORATION
www.eaton.com
Storage
It is recommended that the unit be stored in its original shipping
box/crate until it is to be installed.
The unit should be stored in a location where:
•
The ambient temperature is between –13°F to 140°F
(–25°C to 60°C)
•
The relative humidity is between 0% and 95%, noncondensing
•
The environment is dry, clean, and noncorrosive
•
The unit will not be subjected to high shock or
vibration conditions
Mounting instructions
The DS6 solid-state soft start controller is easy to mount. It does not
require any special tools. To aid you with panel layout, refer to the
dimension drawings shown in
Figure 1
and
Figure 2
. Drill and tap
holes per mounting hole/slot locations as shown. To mount the unit,
use all the hardware specified in
Table 1
of this leaflet. Tighten to
the specified torque.
Figure 1. 25- to 75-Horsepower Models
Figure 2. 100- to 150-Horsepower Models
PE
1.18
(30.0)
PE
1.18
(30.0)
0.86
(22.5)
0.86
(22.5)
3.66
(93.0)
5.08
(129.0)
6.34
(161.0)
1.38
(35.0)
5.47
(139.0)
6.89
(175.0)
1.38
(35.0)
1.38
(35.0)
0.59
(15.0)
0.59
(15.0)
4.25
(108.0)
2.07
(52.5)
7.01
(178.0)
8.47
(215.0)
PE
PE
6.22
(158.0)
7.87
(200.0)
DANGER—HIGH VOLTAGE
HAZARDOUS VOLTAGE CAN CAUSE ELECTRIC SHOCK AND BURNS. TO
AVOID SHOCK HAZARD, DISCONNECT ALL POWER TO THE CONTROLLER,
MOTOR, OR OTHER CONTROL DEVICES BEFORE ANY WORK IS PERFORMED
ON THIS EQUIPMENT. FAILURE TO DO SO WILL RESULT IN PERSONAL
INJURY, DEATH, OR SUBSTANTIAL PROPERTY DAMAGE.
DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT
START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN
DISCONNECT SWITCH IS OPEN IS UTILIZED. OPENING THE DISCONNECT
WHILE THE SOFT START CONTROLLER IS OPERATING MAY CAUSE A MAL-
FUNCTION. CLOSING THE DISCONNECT SWITCH WHILE THE SOFT START
CONTROLLER IS OPERATING WILL RESULT IN POTENTIAL EQUIPMENT
DAMAGE AND PERSONNEL HAZARD.
Table 1. Mounting Hardware and Torque Specifications
Frame Size
Screw Size + Flat
and Lock Washer
Quantity
Torque
Requirements
Unit Weight
Lbs (kg)
25–75 hp
5 mm x 55 mm
2
80 lb-in (9 Nm)
4.0 (1.8)
100–150 hp
6 mm x 65 mm
2
123 lb-in (14 Nm)
8.2 (3.7)
Table 2. Environmental Requirements
Description
Requirements
Operating temperature
32°F to 104°F (0°C to 40°C) up to 140°F (60°C) with derating
of 1% of rated current per Kelvin
Storage temperature
–13°F to 140°F (–25°C to 60°C )
Elevation
Up to 1000m; up to 2000m with derating of 1% rated current
for each 100m
Humidity
Functional to 95% noncondensing.
Operating orientation
Less than 30 degrees from horizontal
Minimum clearance—
upper and lower
2.165 inches (55 mm) to a wall, 0.984 inches (25 mm) to a
NZM1 (size 1), 1.378 inches (35 mm) to a NZM2 (size 2), con-
sult documentation of the breaker used (ionization emissions)
Minimum clearance—sides
0.0 inches (0 mm)
Minimum clearance—face
0.198 inches (5 mm)
Shock resistance
8g for 11 ms in any direction.
Vibration resistance
2M2 EN 60721-3-2: 10g (3.5 mm amplitude, 9 to 200 Hz)
Environment
Suitable for installation in a pollution Degree 2 environment
Emissions
The device is suitable for use in industrial environments in
accordance with EN 55011/22 Class A