2

Instructional Leafl et 

IL03901001E

Effective June 2009

DS6 series soft start controllers 

  
  

EATON CORPORATION

 www.eaton.com

Storage

It is recommended that the unit be stored in its original shipping 
box/crate until it is to be installed.

The unit should be stored in a location where:

• 

The ambient temperature is between –13°F to 140°F 
(–25°C to 60°C)

• 

The relative humidity is between 0% and 95%, noncondensing

• 

The environment is dry, clean, and noncorrosive

• 

The unit will not be subjected to high shock or 
vibration conditions

Mounting instructions

The DS6 solid-state soft start controller is easy to mount. It does not 
require any special tools. To aid you with panel layout, refer to the 
dimension drawings shown in 

Figure 1 

and 

Figure 2

. Drill and tap 

holes per mounting hole/slot locations as shown. To mount the unit, 
use all the hardware specified in 

Table 1

 of this leaflet. Tighten to 

the specified torque.

Figure 1.  25- to 75-Horsepower Models

Figure 2.  100- to 150-Horsepower Models

PE

1.18

(30.0)

PE

1.18

(30.0)

0.86

(22.5)

0.86

(22.5)

3.66

(93.0)

5.08

(129.0)

6.34

(161.0)

1.38

(35.0)

5.47

(139.0)

6.89

(175.0)

1.38

(35.0)

1.38

(35.0)

0.59

(15.0)

0.59

(15.0)

4.25

(108.0)

2.07

(52.5)

7.01

(178.0)

8.47

(215.0)

PE

PE

6.22

(158.0)

7.87

(200.0)

 DANGER—HIGH VOLTAGE 

HAZARDOUS VOLTAGE CAN CAUSE ELECTRIC SHOCK AND BURNS. TO 
AVOID SHOCK HAZARD, DISCONNECT ALL POWER TO THE CONTROLLER, 
MOTOR, OR OTHER CONTROL DEVICES BEFORE ANY WORK IS PERFORMED 
ON THIS EQUIPMENT. FAILURE TO DO SO WILL RESULT IN PERSONAL 
INJURY, DEATH, OR SUBSTANTIAL PROPERTY DAMAGE.

DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT 
START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN 
DISCONNECT SWITCH IS OPEN IS UTILIZED. OPENING THE DISCONNECT 
WHILE THE SOFT START CONTROLLER IS OPERATING MAY CAUSE A MAL-
FUNCTION. CLOSING THE DISCONNECT SWITCH WHILE THE SOFT START 
CONTROLLER IS OPERATING WILL RESULT IN  POTENTIAL EQUIPMENT 
DAMAGE AND PERSONNEL HAZARD.

Table 1.  Mounting Hardware and Torque Specifications

Frame Size

Screw Size + Flat 
and Lock Washer

Quantity

Torque 
Requirements

Unit Weight 
Lbs (kg)

25–75 hp

5 mm x 55 mm

2

80 lb-in (9 Nm)

4.0 (1.8)

100–150 hp

6 mm x 65 mm

2

123 lb-in (14 Nm)

8.2 (3.7)

Table 2.  Environmental Requirements

Description

Requirements

Operating temperature

32°F to 104°F (0°C to 40°C) up to 140°F (60°C) with derating 
of 1% of rated current per Kelvin

Storage temperature

–13°F to 140°F (–25°C to 60°C )

Elevation

Up to 1000m; up to 2000m with derating of 1% rated current 
for each 100m

Humidity

Functional to 95% noncondensing.

Operating orientation

Less than 30 degrees from horizontal

Minimum clearance—
upper and lower

2.165 inches (55 mm) to a wall, 0.984 inches (25 mm) to a 
NZM1 (size 1), 1.378 inches (35 mm) to a NZM2 (size 2), con-
sult documentation of the breaker used (ionization emissions)

Minimum clearance—sides

0.0 inches (0 mm)

Minimum clearance—face

0.198 inches (5 mm)

Shock resistance

8g for 11 ms in any direction.

Vibration resistance

2M2 EN 60721-3-2: 10g (3.5 mm amplitude, 9 to 200 Hz) 

Environment

Suitable for installation in a pollution Degree 2 environment

Emissions

The device is suitable for use in industrial environments in 
accordance with EN 55011/22 Class A

Содержание Cutler-Hammer DS6 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require furthe...

Страница 2: ...Y DEATH OR SUBSTANTIAL PROPERTY DAMAGE DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED...

Страница 3: ...llowable Fuse Size 200V 230V 460V hp hp hp DS6 34DSX041N0 N 40 10 10 30 HFD3150L 150A Class RK5 DS6 34DSX055N0 N 52 15 20 40 HFD3200L 200A Class RK5 DS6 34DSX068N0 N 65 20 25 50 HJD3250 200A Class RK5...

Страница 4: ...3 24 Ready status contacts NO 0V 24 TOR Ready A2 EN A1 13 14 24 24V 0V 23 0V 24 A2 EN A1 13 14 24 23 Q1 Control Wiring Terminal Block Figure 5 Direct Start With Soft Stop Table 7 DS6 Terminal Control...

Страница 5: ...soft start controller issues a START command by applying 24 Vdc to terminals EN and A1 Contacts 13 and 14 will close when the end of the ramp time is reached ote N Bypass contactors close at the end...

Страница 6: ...tarting torque Mixer dry materials 15s 56 75 Pelletizing machine 20s 64 100 Pump piston 25s 30s 82 175 Possible high starting torque Pump centrifugal 10s 30s 37 25 Moving pavement unloaded 20s 37 25 E...

Страница 7: ...heck for the following conditions verify proper motor cable connections and check for condi tion and security Verify installation and integrity of motor coupling to load Test motor for proper conditio...

Страница 8: ...Operation During Motor Start Run and Stop Conditions Condition Motor Status Ready Contacts TOR Contacts Error LED Run LED 24 Vdc applied and initialization complete Off Closed Open Flashing short pul...

Отзывы: