Instructional Leafl et 

IL03901001E

Effective June 2009

DS6 series soft start controllers 

  
  

EATON CORPORATION

 www.eaton.com

Table 8.   DS6 Parameters

Application

t-Start

t-Stop

u-Start

Break-Away Torque

Remarks

Axial-flow compressor

25s

48%

50%

 

Bandsaw

10s

42%

35%

 

Drill, unloaded

10s

29%

10%

 

Crusher, empty at start

20s

56%

75%

Possible high inertia

Carding machine (combing cotton)

20s

64%

100%

 

Conveyor, horizontal, loaded

25s

30s

76%

150%

 

Conveyor, horizontal, unloaded

25s

30s

48%

50%

 

Conveyor, vertical, loaded

25s

30s

82%

175%

 

Conveyor, vertical, unloaded

25s

30s

59%

85%

 

Conveyor, vertical drop, loaded

25s

30s

37%

25%

 

Conveyor, vertical drop, unloaded

25s

30s

44%

40%

 

Crusher, swing hammer

25s

70%

125%

Eccentric load, high starting torque

Chiller

5s

37%

25%

 

Piston compressor, unloaded

10s

64%

100%

 

Circular saw

20s

48%

50%

Possible high inertia

Ball mill

20s

48%

50%

Eccentric load

Flour mill

20s

44%

50%

 

Mixer, liquids

10s

37%

40%

 

Mixer, plastic materials

10s

70%

125%

Possible high starting torque

Mixer, powder materials

10s

70%

125%

Possible high starting torque

Mixer, dry materials

15s

56%

75%

 

Pelletizing machine

20s

64%

100%

 

Pump, piston

25s

30s

82%

175%

Possible high starting torque

Pump, centrifugal

10s

30s

37%

25%

 

Moving pavement, unloaded

20s

37%

25%

 

Escalator

10s

48%

50%

 

Rotary compressor, unloaded

20s

42%

35%

 

Agitator

15s

42%

35%

 

Grinder, unloaded

10s

37%

25%

Possible high inertia

Feed screw

20s

82%

175%

Possible high starting torque

Compressor, screw, unloaded

25s

40%

30%

 

Press, flywheel

25s

76%

150%

Possible high starting torque

Drier, rotating

20s

64%

100%

 

Blower, axial fan, flaps closed

40s

37%

25%

 

Blower, axial fan, flaps open

30s

37%

25%

 

Blower, centrifugal fan, valve closed

40s

42%

35%

 

Blower, centrifugal fan, valve open

30s

35%

20%

 

Vibroconveyor

25s

76%

150%

Possible high starting torque

Vibrating screen

20s

51%

60%

Possible high starting torque

Rolling mill

25s

48%

 

Washing machine

25s

64%

100%

High transmission ratio

Centifuge

60s

61%

90%

High inertia, long ramp time

otes: 

N

u-Start % values are voltage settings, as the starting torque is dependent on the application.

Applications with high starting torque are not suitable for DS6 soft start controllers. In some cases, over-sizing to a larger unit may be a solution. 
Consult Eaton’s Technical Resource Center at (877) 386-2273.

Содержание Cutler-Hammer DS6 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require furthe...

Страница 2: ...Y DEATH OR SUBSTANTIAL PROPERTY DAMAGE DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED...

Страница 3: ...llowable Fuse Size 200V 230V 460V hp hp hp DS6 34DSX041N0 N 40 10 10 30 HFD3150L 150A Class RK5 DS6 34DSX055N0 N 52 15 20 40 HFD3200L 200A Class RK5 DS6 34DSX068N0 N 65 20 25 50 HJD3250 200A Class RK5...

Страница 4: ...3 24 Ready status contacts NO 0V 24 TOR Ready A2 EN A1 13 14 24 24V 0V 23 0V 24 A2 EN A1 13 14 24 23 Q1 Control Wiring Terminal Block Figure 5 Direct Start With Soft Stop Table 7 DS6 Terminal Control...

Страница 5: ...soft start controller issues a START command by applying 24 Vdc to terminals EN and A1 Contacts 13 and 14 will close when the end of the ramp time is reached ote N Bypass contactors close at the end...

Страница 6: ...tarting torque Mixer dry materials 15s 56 75 Pelletizing machine 20s 64 100 Pump piston 25s 30s 82 175 Possible high starting torque Pump centrifugal 10s 30s 37 25 Moving pavement unloaded 20s 37 25 E...

Страница 7: ...heck for the following conditions verify proper motor cable connections and check for condi tion and security Verify installation and integrity of motor coupling to load Test motor for proper conditio...

Страница 8: ...Operation During Motor Start Run and Stop Conditions Condition Motor Status Ready Contacts TOR Contacts Error LED Run LED 24 Vdc applied and initialization complete Off Closed Open Flashing short pul...