Table 9.  DS6 Basic Troubleshooting Guide

Possible Problem

Possible Solution

Fault LED illuminates during the operation of the DS6 soft start controller

Control voltage loss

Check for the following conditions: power supply failure and/or intermittent operation and volt-
age stability. Check all connections for condition and security. Verify proper size and capacity 
of the power supply.

EN and heat sink temperature less than 0°C

Verify that unit temperature is not below 0°C during application of control voltage or starter 
operation. 

Fault LED illuminates during start ramp, TOR, or stop ramp

Mains connection open or undervoltage

Check for the following conditions: verify presence and stability of mains voltage. Check sys-
tem for phase loss. Check main breaker and/or isolation contactor and/or reversing contactors 
are not open or have been cycled during starter operation, and verify proper operation. Verify 
all connections for condition and security. 

Motor connection open

Check for the following conditions: verify proper motor cable connections, and check for condi-
tion and security. Verify installation and integrity of motor coupling to load. Test motor for 
proper condition. Check that isolation and/or reversing contactors are not open.

Heat sink temperature less than 0°C or above 80°C

Verify that unit temperature is not below 0°C or above 80°C.

Bypass contactor(s) closed during start ramp or stop ramp time

Verify that bypass contactor(s) do not close when START command is initiated and remain 
open until top of ramp is achieved. Verify that bypass contactor(s) open when STOP command 
or STOP RAMP command are initiated.

Bypass contactor not closed after ramp time

Verify that bypass contactor(s) close at top of ramp and remain closed until STOP command or 
STOP RAMP command are initiated.

SCR fault

Verify that one or more of the SCRs are not open. Verify that one or more of the SCRs are 
not shorted. 

Faults

In the event of a motor stop due to a trip condition by the soft start 
controller, the FAULT status LED will be illuminated (flashing). In this 
case, one or more conditions found in 

Table 9

 may have occured.

Use standard troubleshooting techniques to determine the cause of 
the trip. The DS6 does not provide any specific method of identifying 
the cause of the trip.

Содержание Cutler-Hammer DS6 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require furthe...

Страница 2: ...Y DEATH OR SUBSTANTIAL PROPERTY DAMAGE DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED...

Страница 3: ...llowable Fuse Size 200V 230V 460V hp hp hp DS6 34DSX041N0 N 40 10 10 30 HFD3150L 150A Class RK5 DS6 34DSX055N0 N 52 15 20 40 HFD3200L 200A Class RK5 DS6 34DSX068N0 N 65 20 25 50 HJD3250 200A Class RK5...

Страница 4: ...3 24 Ready status contacts NO 0V 24 TOR Ready A2 EN A1 13 14 24 24V 0V 23 0V 24 A2 EN A1 13 14 24 23 Q1 Control Wiring Terminal Block Figure 5 Direct Start With Soft Stop Table 7 DS6 Terminal Control...

Страница 5: ...soft start controller issues a START command by applying 24 Vdc to terminals EN and A1 Contacts 13 and 14 will close when the end of the ramp time is reached ote N Bypass contactors close at the end...

Страница 6: ...tarting torque Mixer dry materials 15s 56 75 Pelletizing machine 20s 64 100 Pump piston 25s 30s 82 175 Possible high starting torque Pump centrifugal 10s 30s 37 25 Moving pavement unloaded 20s 37 25 E...

Страница 7: ...heck for the following conditions verify proper motor cable connections and check for condi tion and security Verify installation and integrity of motor coupling to load Test motor for proper conditio...

Страница 8: ...Operation During Motor Start Run and Stop Conditions Condition Motor Status Ready Contacts TOR Contacts Error LED Run LED 24 Vdc applied and initialization complete Off Closed Open Flashing short pul...

Отзывы: