DS6 series soft start controllers 

  
  

EATON CORPORATION

 www.eaton.com

Control wiring

A minimum of 16 AWG should be used between the power supply 
and the 24 Vdc + and – terminals.

Terminal connections are to be secured to a torque value of 3.6 lb-in.

Control wiring is connected to the DS6 soft start controller by a 
9-pin terminal block located on the front of the unit. Use the wiring 
diagrams in 

Figure 4

Figure 5

, and the information in 

Table 7 

as guides.

Figure 4.  Direct Start

Table 6.   Terminal Designations

Terminal

Description

OV

Control ground or power supply common

+24

Plus 24 Vdc from power supply

–A2

Common with 0V, connected externally

EN

Start command enable/stop command

+A1

Start command/ramp stop command

13, 14

Top of ramp contacts—NO

23, 24

Ready status contacts—NO

0V +24

TOR

Ready

–A2 EN +A1 13

14

24

+24V

0V

23

0V +24 –A2 EN +A1 13 14

24

23

Q1

Control Wiring Terminal Block

Figure 5.  Direct Start With Soft Stop 

Table 7.  DS6 Terminal Control Block Wiring

Name

Block 
Designation

Input

Connections

Circuit 
common

0V

Common

Common

Power

+24

24 Vdc nominal (see 24 Vdc power 
supply requirements) section for 
sizing of power supply

+24 Vdc power from 
power supply

–A2

–A2

Control power common

Common

Enable

EN

24 Vdc maintained

START command with 
+A1 energized. Remove 
for STOP command

+A1

+A1

24 Vdc maintained

START command 
with EN energized. 
Remove for STOP 
RAMP command

Relay

13

NO contact rated @ 250 Vac, 
3A resistive, 1A inductive

Top of ramp signal–
in bypass

14

NO contact rated  @ 250 Vac, 
3A resistive, 1A inductive

Top of ramp signal–
in bypass

Relay

23

NO contact rated @ 250 Vac, 
3A resistive, 1A inductive

READY status signal

24

NO contact rated @ 250 Vac, 
3A resistive, 1A inductive

READY status signal

0V  +24

TOR

Ready

-A2 EN +A1 13 14

24

+24V

0V

23

Q1

S3

Содержание Cutler-Hammer DS6 Series

Страница 1: ...specifications set forth by UL 508 IEC 60947 4 2 CE C Tick and CSA This leaflet covers basic installation and setup No publication can take into account every possible situation If you require furthe...

Страница 2: ...Y DEATH OR SUBSTANTIAL PROPERTY DAMAGE DO NOT APPLY A DISCONNECT DEVICE ON THE OUTPUT OF THE DS6 SOFT START CONTROLLER UNLESS A MEANS TO TURN OFF THE DEVICE WHEN DISCONNECT SWITCH IS OPEN IS UTILIZED...

Страница 3: ...llowable Fuse Size 200V 230V 460V hp hp hp DS6 34DSX041N0 N 40 10 10 30 HFD3150L 150A Class RK5 DS6 34DSX055N0 N 52 15 20 40 HFD3200L 200A Class RK5 DS6 34DSX068N0 N 65 20 25 50 HJD3250 200A Class RK5...

Страница 4: ...3 24 Ready status contacts NO 0V 24 TOR Ready A2 EN A1 13 14 24 24V 0V 23 0V 24 A2 EN A1 13 14 24 23 Q1 Control Wiring Terminal Block Figure 5 Direct Start With Soft Stop Table 7 DS6 Terminal Control...

Страница 5: ...soft start controller issues a START command by applying 24 Vdc to terminals EN and A1 Contacts 13 and 14 will close when the end of the ramp time is reached ote N Bypass contactors close at the end...

Страница 6: ...tarting torque Mixer dry materials 15s 56 75 Pelletizing machine 20s 64 100 Pump piston 25s 30s 82 175 Possible high starting torque Pump centrifugal 10s 30s 37 25 Moving pavement unloaded 20s 37 25 E...

Страница 7: ...heck for the following conditions verify proper motor cable connections and check for condi tion and security Verify installation and integrity of motor coupling to load Test motor for proper conditio...

Страница 8: ...Operation During Motor Start Run and Stop Conditions Condition Motor Status Ready Contacts TOR Contacts Error LED Run LED 24 Vdc applied and initialization complete Off Closed Open Flashing short pul...

Отзывы: