10.4   Signal contact S2-S/H

Rated voltage: 

 

 

up to 250V

Rated current: 

 

 

5A

Min.  switching capacity: 

 

0,1VA / 24V

Terminal cross section: 

 

2x 2,5mm² 

1.5 Nm

Flameproof module series, GHG 61. .... R....

10.3   Circuit breaker, with ELCB (RCD)

EC-Type Examination Certificate: 

PTB 98 ATEX 1087U

Explosion protection:  

 

Ex de IIC/IIB Gb

 

Rated voltage: 

 

 

Main contact 

 

Aux. contact

 

 

 

up to 440V AC 

up to 250V AC

Rated current:

ELCB 

 

 

up to 63A

Circuit breaker 

 

 

from 1.0A up to 32A (40A)

Aux. contact 

 

 

max. 5A

Short-circuit protection: 

 

up to 10 kA depend on circuit breaker

Back-up fuse:

ELCB 

 

 

max. 100 A gL

Circuit breaker 

 

 

dep. on rated current up to 100 A gL

Tripping current ELCB: 

 

30mA (300mA on request)

Terminal cross section: 

 

Main contact 

Aux./Signal  contact

 

 

 

max. 2x 10mm² 

max. 2x 2.5mm²

Test torques: 

 

 

3.5 Nm   

 

1.5 Nm

Component size: 

 

 

2* 

 

3* 

     4

Weight: 

 

               

approx. 0.95kg  approx. 1.27kg approx. 1.6kg

 

 

 

1-pole + N         

2-pole

The technical data relates to standard built-in apparatus.

- If other built-in apparatus is used, the technical data sheets 

   or the data on the type label shall be observed. 

*  ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.

Contact arrangement

ELCB with circuit breaker

1-pole + N

Contact arrangement

10.5   Aux. contact S2-S/H

Rated voltage: 

 

 

up to 250V

Rated current: 

 

 

5A

Terminal cross section: 

 

2x 2,5mm² 

1.5 Nm

  Signal contact S2-S/H

  Aux. contact S2-S/H

10.6   Current surge switch

EC-Type Examination Certificate: 

PTB 98 ATEX 1087U

Explosion protection:  

 

Ex de IIC/IIB Gb

 

Rated voltage: 

 

 

up to 400V AC

Rated operating voltage: 

 

8V to 275V* AC 

 

8V to 220V DC

 

  

(*further operating voltages on request)

Rated current: 

 

 

16A

Rated switching capacity: 

 

16A / 250V AC 

 

10A / 400V AC

Terminal cross section: 

 

 

Switching contacts 1, 2, 3, 4 

 

max. 2x  10mm² 

/ 3.0 Nm

Control contacts  A1, A2 

 

max. 2x 2.5mm² 

/ 1.5 Nm

Komponent size: 

 

 

0

Weight: 

 

               

approx. 0.55kg

The technical data relates to standard built-in apparatus.

- If other built-in apparatus is used, the technical data sheets 

   or the data on the type label shall be observed. 

Contact arrangement

Current surge switch

10.7   20 A installation contactor

EC-Type Examination Certificate: 

PTB 98 ATEX 1087U

Explosion protection:  

 

Ex de IIC/IIB Gb

 

Rated voltage: 

 

 

up to 250V AC

Control voltage: 

 

 

24V to 250V AC    

Rated current: 

 

 

20A

Rated switching capacity: 

 

AC 1  230V / 4,0kW         AC 3  230V / 1,3kW

Back-up fuse: 

 

 

20A gL

Terminal cross section: 

 

Switching contacs 1, 2, 3, 4 

 

max. 2x  10mm² 

/ 3.0 Nm

Control contacs     A1, A2 

 

max. 2x 2.5mm² 

/ 1.5 Nm

Component size: 

 

 

0

Weight: 

             

   

approx. 0.55kg

The technical data relates to standard built-in apparatus.

- If other built-in apparatus is used, the technical data sheets 

   or the data on the type label shall be observed.

Contact arrangement

20A installation contactor

  1NO + 1NC

  2NO

  2NC

2-pole

Содержание Crouse-Hinds GHG 61 R Series

Страница 1: ...jos i verstos J su gimt j kalb galite pareikalauti atsakingoje Cooper Crouse Hinds CEAG atstovyb je savo alyje LV o ekspluat cijas instrukciju valsts valod varat piepras t j su valsts atbild gaj Coope...

Страница 2: ...ng 5 10 Technische Daten kompletter Bausteine 6 14 Ausl sekennlinien 39 Konformit tsaussage separat beigelegt Contents Contents 2 Dimensional drawings 2 1 Technical details 15 2 Safety instructions 16...

Страница 3: ...nausf hrung AbweichendeTemperaturen sind bei Sonderversionen m glich Zul Lagertemperatur in Originalverpackung 50 C bis 60 C Anschlussquerschnitt Hauptklemmen Bausteingr e 0 max 2x 4 0 mm feindr htig...

Страница 4: ...Betriebsmittels zu beachten Pr fkriterium f r die Eigenerw rmung ist eine berlastung um 10 Die Temperaturklasse der kompletten Anlage oderVerteilung wird durch dieVerlustleistung aller eingebauten Bau...

Страница 5: ...rteiler kann zum Verlust der Garantie f hren 7 Instandhaltung Wartung Die f r dieWartung Instandhaltung von elektrischen Betriebsmitteln in explosionsgef hr deten Bereichen geltenden Bestimmungen der...

Страница 6: ...n Bei anderen Einbauten sind technische Datenbl tter bzw die Daten auf demTypenschild zu beachten Ausl sekennlinien siehe letzte Seite Leistungsschalter mit Signalkontakt werden in das n chst gr ere K...

Страница 7: ...Hilfskontakt S2 S H Bemessungsspannung bis 250V Bemessungsstrom 5A Anschlussquerschnitt 2x 2 5mm 1 5 Nm Signalkontakt S2 S H Hilfskontakt S2 S H 10 6 Stromstossschalter EG Baumusterpr fbescheinigung...

Страница 8: ...te Bausteine Serie GHG 61 R Anschlussbild Installationssch tz 24A Hilfskontakte 4S 1S 1 2S 10 9 Installationssch tz 32A EG Baumusterpr fbescheinigung PTB 98 ATEX 1087U Explosionsschutz Ex de IIC IIB G...

Страница 9: ...inbauten angegeben Bei anderen Einbauten sind technische Datenbl tter bzw die Daten auf demTypenschild zu beachten Anschlussbild Luftsch tz20A Hauptkontakte Hilfskontakte 3S 1S 1S 1 10 12 Stern Dreiec...

Страница 10: ...e bis 20A Hilfskontakte bis 6A Bemessungsschaltleistung Hauptkontakte AC 3 230V 2 2kW 400V 690V 4kW Bemessungsschaltleistung Hilfskontakte AC15 230V 4A Anschlussquerschnitt Schaltkontakte 1 2 3 4 5 6...

Страница 11: ...usterpr fbescheinigung PTB 99 ATEX 1007 U Bemessungsspannung 690 V 50 60 Hz 440V DC Bemessungsstrom bis 25A Kurzschlussvorsicherung siehe Punkt 10 17 4 und 10 17 5 Schaltverm gen AC 3 690V 25A Thermis...

Страница 12: ...20 00 A 25 00 A 20 kA 125 A 3 kA 50 A Einstellbereich 240 V AC Ics gL aM 400 V AC Ics gL aM 500 V AC Ics gL aM 690 V AC Ics gL aM 0 10 A 0 16 A 0 16 A 0 25 A Kurzschlussfest keine Vorsicherung notwen...

Страница 13: ...1 92 A 15 0 s 9 0 s 6 5 s 4 8 s 3 2 s 0 16 A 0 25 A 3 00 A 16 0 s 10 0 s 6 8 s 5 2 s 3 6 s 0 25 A 0 40 A 4 80 A 16 0 s 9 7 s 6 5 s 5 0 s 3 3 s 0 40 A 0 63 A 7 56 A 17 0 s 10 2 s 7 3 s 5 7 s 3 9 s 0 63...

Страница 14: ...ontakte max 2x 2 5 mm 1 5 Nm Komponentengr e 3 Gewicht ca 0 210 kg Anschlie bare Betriebsmittel Gas Ex Zone 1 und Zone 2 EN IEC 60079 10 1 Staub Ex Zone 21 und Zone 22 EN IEC 60079 10 2 II 2 GD Eigens...

Страница 15: ...le size 3 IIC 20 C 60 C 110 C module size 3 IIB 55 C 60 C 110 C module size 3 4 IIC IIB 20 C 60 C 110 C standard version Other temperatures possible with special versions Perm storage temperature in o...

Страница 16: ...ules depends on the respective encapsulated switch unit Important When using these modules the technical data and the connection diagram on the type label shall be observed When circuit breakers and E...

Страница 17: ...ng The valid national regulations for the servicing maintenance of electrical apparatus for use in potentially explosive atmospheres shall be observed the IEC EN 60079 17 Prior to opening the enclosur...

Страница 18: ...r built in apparatus is used the technical data sheets or the data on the type label shall be observed Tripping characteristic of circuit breaker last page Circuit breakers with signal contacts are bu...

Страница 19: ...o 250V Rated current 5A Terminal cross section 2x 2 5mm 1 5 Nm Signal contact S2 S H Aux contact S2 S H 10 6 Current surge switch EC Type Examination Certificate PTB 98 ATEX 1087U Explosion protection...

Страница 20: ...series GHG 61 R Main contacts Aux contacts 4NO 1NO 1NC 2NO 10 9 32A installation contactor EC Type Examination Certificate PTB 98 ATEX 1087U Explosion protection Ex de IIC IIB Gb Rated voltage up to 4...

Страница 21: ...built in apparatus is used the technical data sheets or the data on the type label shall be observed Contact arrangement 20A air break contactor Main contacts Aux contacts 3NO 1NC 1NO 1NC 10 12 Star d...

Страница 22: ...60h Control functions 11 delayed pick up 12 delayed reset 16 delayed pick up and reset 21 cut in wiping 22 cut off wiping 42 blinking Terminal cross section Main contacts max 2x 10mm 3 0 Nm Control c...

Страница 23: ...on certificate PTB 99 ATEX 1007 U Rated voltage 690 V 50 60 Hz 440V DC Rated current up to 25 A Short circuit back up fuse see point 10 17 4 and 10 17 5 AC 3 switching capacity 690 V 25 A Thermal trip...

Страница 24: ...0 A 25 00 A 20 kA 125 A 3 kA 50 A Einstellbereich 240 V AC Ics gL aM 400 V AC Ics gL aM 500 V AC Ics gL aM 690 V AC Ics gL aM 0 10 A 0 16 A 0 16 A 0 25 A Short circuit proof no back up fuse required u...

Страница 25: ...old 5 fold 6 fold 8 fold 0 10 A 0 16 A 1 92 A 15 0 s 9 0 s 6 5 s 4 8 s 3 2 s 0 16 A 0 25 A 3 00 A 16 0 s 10 0 s 6 8 s 5 2 s 3 6 s 0 25 A 0 40 A 4 80 A 16 0 s 9 7 s 6 5 s 5 0 s 3 3 s 0 40 A 0 63 A 7 56...

Страница 26: ...ntacts max 2x 10 mm 3 0 Nm Aux contacts max 2x 2 5 mm 1 5 Nm Component size 3 Weight appr 0 210 kg Applicatable devices Gas Ex Zone 1 and Zone 2 EN IEC 60079 10 1 Dust Ex Zone 21 und Zone 22 EN IEC 60...

Страница 27: ...odul s 3 IIC 20 C 60 C 110 C Modul s 3 IIB 55 C 60 C 110 C Modul s 3 4 IIC IIB 20 C 60 C 110 C standard d autres valeurs sont possibles avec des mod les sp ciaux Temp rature de stockage dans l emballa...

Страница 28: ...modules d pend de chaque appareil de commande encapsul Important lors de l utilisation des modules il faut respecter les caract ristiques tech niques et le plan de connexion sur la plaque signal tique...

Страница 29: ...llation compl te ou des distributeurs 7 Maintenance Entretien Les prescriptions relatives la maintenance et l entretien d appareils lectriques install s en atmosph res explosibles CEI EN 60079 17 doiv...

Страница 30: ...standard Pour les autres les donn es des fiches techniques et des tiquettes type sont respecter Courbe de d clenchement du disjoncteur voir dernier c t Les disjoncteurs avec contact de signalisation...

Страница 31: ...S2 S H Tension d essai jusqu 250V Courant d essai 5A Diam tre de connexion 2x 2 5mm 1 5 Nm Contacts de signalisation S2 S H Contacts auxiliaires S2 S H 10 6 Interrupteur de coupure impulsion Attestati...

Страница 32: ...principaux Contacts auxiliaires 4NO 1NO 1NF 2NO 10 9 Contacteur d installation 32A Attestation d examen type CE PTB 98 ATEX 1087U Mode de protection Ex de IIC IIB Gb Tension d essai jusqu 415 V AC Ten...

Страница 33: ...s et des tiquettes type sont respecter Sch ma de raccordement Contacteur Contacts principaux Contacts auxiliaires 3NO 1NO 1NO 1NF 10 12 Relais temporis toile triangle Attestation d examen type CE PTB...

Страница 34: ...nde 11 r action retard e 12 r p tition retard e 16 r action et r p tition retard es 21 avec retour marche 22 avec retour arr t 42 clignotant Diam tre de connexion Contacts de coupure 2x 10mm maxi 3 0...

Страница 35: ...V DC Courant nominal jusqu 25 A Fusible de court circuit voir point 1 4 et 1 5 page 4 Puissance de coupure AC 3 jusqu 690 V 25 A Caract ristique du d clenchement thermique T II Temp s de d clenchement...

Страница 36: ...A 25 00 A 20 kA 125 A 3 kA 50 A Einstellbereich 240 V AC Ics gL aM 400 V AC Ics gL aM 500 V AC Ics gL aM 690 V AC Ics gL aM 0 10 A 0 16 A 0 16 A 0 25 A R sistant aux courts circuits fusible plac en a...

Страница 37: ...cit du r glage du 3 fois 4 fois 5 fois 6 fois 8 fois 0 10 A 0 16 A 1 92 A 15 0 s 9 0 s 6 5 s 4 8 s 3 2 s 0 16 A 0 25 A 3 00 A 16 0 s 10 0 s 6 8 s 5 2 s 3 6 s 0 25 A 0 40 A 4 80 A 16 0 s 9 7 s 6 5 s 5...

Страница 38: ...rseur O F Section des conducteurs Contacts de puissance max 2x 10 mm 3 0 Nm Contacts auxiliaires max 2x 2 5 mm 1 5 Nm Taille des composants 3 Poids env 0 210 kg Utilisation Gaz Ex Zone 1 and Zone 2 EN...

Страница 39: ...20 30 10 3 5 7 5 1 Grenzkennlinie aus dem kalten Zustand 1 1 S 280 UC UC B Charakteristik S280 AC DC I1 I2 I 1 13xI I 1 45xI J 30 C 1 2 r n n 0 01 0 02 0 04 0 06 0 1 0 2 0 4 0 6 1 2 4 6 10 20 40 1 2 4...

Страница 40: ...ct to prior approval by Eaton The same applies to Trademarks especially Eaton Moeller and Cutler Hammer The Terms and Conditions of Eaton apply as referenced on Eaton Internet pages and Eaton order co...

Отзывы: