9

Installation procedure 

INSTALLATION AND OPERATION INSTRUCTIONS

   MN280103EN   March 2023   www.eaton.com

Figure 8 .  Connection diagram shows complete  

surge protection and illustrates bypass and 

disconnect switches

Figure 9 .  Terminal identification of  

Type NOVA NX-STS recloser

Refer to 

Figure 8

 and 

Figure 9

 for terminal identification 

of the NOVA NX-STS recloser.
Terminal connection to copper conductors only are 

recommended.
To rotate a flat-pad or eyebolt bushing terminal prior to 

connecting power line leads, loosen the pinch bolt on 

the terminals. After rotating the terminal, retighten the 

pinch bolt as follows: torque 3/8-16 pinch bolts to  

20–23 Nm (15–17 ft lb); torque 1/2-13 pinch bolts to 

39–42 Nm (29–31 ft lb).

7. 

Block ground sensing via the control panel.

8. 

Close source and load disconnect switches.

9. 

Close reclosers via control signal.

10. 

Open bypass switches.

11. 

Enable ground sensing, if applicable.

Removing recloser from service

 WARNING

HAZARDOUS VOLTAGE. ALWAYS USE A HOTSTICK WHEN 

WORKING WITH THIS EQUIPMENT. FAILURE TO DO SO COULD 

RESULT IN CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE 

DEATH OR SEVERE PERSONAL INJURY.

 WARNING

HAZARDOUS VOLTAGE. DO NOT RELY ON THE OPEN POSITION OF 

THE YELLOW OPERATING HANDLE OR THE CONTACT POSITION 

INDICATOR; IT DOES NOT ENSURE THAT THE LINE HAS BEEN 

DE-ENERGIZED. ALWAYS ESTABLISH A VISIBLE DISCONNECT. 

FAILURE TO FOLLOW PROPER SAFETY PRACTICES CAN RESULT IN 

CONTACT WITH HIGH VOLTAGE, WHICH WILL CAUSE DEATH OR 

SEVERE PERSONAL INJURY.

1. 

Block ground tripping via the control panel. Refer 

to 

Service Information MN280095EN Form 7 

Microprocessor Based Pole Mount Recloser Control 

Installation and Operation Instructions

.

NOTICE

EQUIPMENT MISOPERATION. DISCONNECT ALL CONTROL POWER 

SOURCES PRIOR TO DISCONNECTING OR RECONNECTING THE 

CONTROL CABLE FROM THE CONTROL. FAILURE TO COMPLY 

CAN RESULT IN RECLOSER MISOPERATION AT THE TIME OF 

DISCONNECTION OR RECONNECTION OF THE CONTROL CABLE TO 

THE CONTROL.

2. 

Close all three bypass switches.

Note: 

If only one bypass switch is closed and the  

 

recloser is opened via the yellow operating  

 

handle, it is possible all three phases will trip  

 

based upon mode selection. 

3. 

Open the source and load disconnect switches.

4. 

Pull down all three yellow operating handles with a 

hotstick. The yellow operating handle is located under 

the recloser sleet hood.

 

If the recloser is set in single-phase trip/single-phase 

lockout mode, only one phase will open.

 

If the recloser is set in single-phase trip/three-phase 

lockout mode or three-phase trip/three-phase lockout 

mode, all three phases will open.

The control will sense that all three recloser phases  

are open.

NOTICE

DISCONNECT SWITCHES FOR AC SENSING AND POWER 

CONNECTIONS ARE NECESSARY TO ISOLATE THE CONTROL FOR 

TESTING AND SERVICING.

5. 

Disconnect the control battery.

6

4

2

5

3

1

Source

Load

Содержание Cooper Power NOVA NX-STS

Страница 1: ...NOVA NX STS single tank triple single electronically controlled recloser installation and operation instructions Reclosers MN280103EN Effective March 2023 New Issue COOPER POWER SERIES...

Страница 2: ...A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS...

Страница 3: ...2 DIMENSIONS 3 INSTALLATION PROCEDURE 7 Removing recloser from service 9 RECLOSER OPERATION 10 Vacuum interrupter 10 Mechanism tripping and closing 10 Electronic control 11 Manual operation of energi...

Страница 4: ...nts WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED COULD RESULT IN DEATH OR SERIOUS INJURY CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH IF NOT AVOIDED MAY RESULT...

Страница 5: ...for damage incurred during shipment If damage is discovered file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the NOVA NX STS recloser to minimi...

Страница 6: ...32 5 41 6 32 5 41 6 32 5 32 5 Rated duration of short circuit s 3 3 3 3 3 3 Rated short circuit breaking current kA sym 12 5 16 12 5 16 12 5 12 5 Rated symmetrical short circuit making current kA sym...

Страница 7: ...110 kV BIL inches mm 15 kV 125 kV BIL inches mm 27 kV 125 kV BIL inches mm 27 kV 150 kV BIL inches mm 38 kV 170 kV BIL inches mm Terminal to terminal 41 40 1052 0 41 40 1052 0 41 40 1052 0 41 40 1052...

Страница 8: ...0 38 0 170 kV BIL 58 20 1478 0 27 40 696 0 ote N All dimensions are in inches mm Dimensions shown are approximate 36 59 929 0 36 59 929 0 47 69 1211 0 A 15 24 387 0 42 87 1089 0 15 50 394 0 15 50 394...

Страница 9: ...s mm Dimensions shown are approximate Ground lug Grounding connection 0 50 mounting bolts 3 for outboard mounting 3 for inboard mounting 5 94 151 0 29 88 759 0 15 54 395 0 5 38 137 0 29 88 759 0 15 54...

Страница 10: ...8 70 1999 0 Dry 81 10 2060 0 ote N All dimensions are in inches mm Dimensions shown are approximate B B 28 13 715 0 28 18 716 0 29 34 745 0 21 99 559 0 14 23 361 0 Center of gravity for reference only...

Страница 11: ...ic condition of the recloser or the vacuum integrity of the interrupter WARNING FALLING EQUIPMENT USE THE LIFTING LUGS PROVIDED AND FOLLOW ALL LOCALLY APPROVED SAFETY PRACTICES WHEN LIFTING AND MOUNTI...

Страница 12: ...TO COMPLY COULD CAUSE SEVERE INJURY OR DEATH ote N Control is interlocked such that during normal operation voltage cannot appear unless correct 52a b status is reported by the recloser To ensure pro...

Страница 13: ...ED ALWAYS ESTABLISH A VISIBLE DISCONNECT FAILURE TO FOLLOW PROPER SAFETY PRACTICES CAN RESULT IN CONTACT WITH HIGH VOLTAGE WHICH WILL CAUSE DEATH OR SEVERE PERSONAL INJURY 1 Block ground tripping via...

Страница 14: ...o the Form 7 recloser control The recloser responds to trip and close commands from the control per the settings programmed in the control Refer to Service Information MN280095EN Form 7 Microprocessor...

Страница 15: ...the main contacts of the recloser Contact position is indicated by the OPEN flag of the contact position indicator located on the bottom of the recloser The yellow operating handle will remain down in...

Страница 16: ...NG HAZARDOUS VOLTAGE IF TERMINAL CONNECTIONS ARE REVERSED VOLTAGE SENSING MAY INDICATE ERRONEOUS VOLTAGES WHEN THE CONTACTS ARE OPEN DO NOT RELY ON VOLTAGE SENSING TO ENSURE THAT THE VOLTAGE IS ZERO A...

Страница 17: ...RFACES ARE CLEAN AND DRY BEFORE CONNECTING CABLES VOLTAGE SENSING ERRORS CAN RESULT FROM CONTAMINATION FAILURE TO COMPLY CAN RESULT IN CONTROL AND RECLOSER MISOPERATION The electrical connectors of th...

Страница 18: ...ION HAZARDOUS VOLTAGE DO NOT TOUCH THE RECEPTACLE CONNECTIONS OF THE CONTROL VOLTAGE SENSING CABLE IF THE RECLOSER IS ENERGIZED AND THE CONTROL VOLTAGE SENSING CABLE IS DISCONNECTED FROM THE RECLOSER...

Страница 19: ...ounting hanger Pole mounting accessory One pole mounting hanger which allows a variety of add on components to be mounted such as arresters and PTs dry or oil type is available for pole mount installa...

Страница 20: ...full rated ambient temperature range of the recloser and control The accuracy for this system applies when the following conditions are met Voltage range is greater than 50 to 100 of the rated maximum...

Страница 21: ...THE SWITCHGEAR APPARATUS AND CONTROL AND HIGH VOLTAGE TRANSFORMER MUST BE IN A TEST CAGE OR SIMILAR PROTECTED AREA TO PREVENT ACCIDENTAL CONTACT WITH THE HIGH VOLTAGE PARTS SOLIDLY GROUND ALL EQUIPMEN...

Страница 22: ...ply test voltage to terminals 1 3 and 5 for 60 seconds 9 The recloser should withstand the test voltage for 60 seconds Withstand test results The high potential withstand tests provide information on...

Страница 23: ...for damage Check the module surface and major and minor sheds for cracks holes and major chips If damage is present the module must be replaced Contact your Eaton representative 7 If no damage is fou...

Страница 24: ...rip Alt COIL Vendor Specific Close Trip COIL Close Trip Aux 52a Aux 52b Aux COM 69b combined SWITCH COM 52a 52b 69a Source VS Load VS VS Neutral PRESENT ONLY IF AUX SWITCH IS ORDERED THESE SIGNALS TER...

Страница 25: ...re 17 for typical configuration Phase C Internal Wiring See Figure 17 for typical configuration E SHIELD f VS Shield C CT C M Coil PhC Standard Interface Close Trip P Coil PhC Close Trip Y 52a PhC b 5...

Страница 26: ...S MN280103EN March 2023 www eaton com Figure 19 Auxiliary switch accessory wiring Phase A Phase B Phase C B1 F5 F3 F4 Aux 52a Aux 52b Aux Sw Com Aux 52a Aux 52b Aux Sw Com Customer connection B1 F5 F3...

Страница 27: ...23 Service information INSTALLATION AND OPERATION INSTRUCTIONS MN280103EN March 2023 www eaton com This page is intentionally left blank...

Страница 28: ...aton com cooperpowerseries 2023 Eaton All Rights Reserved Printed in USA Publication No MN280103EN Z27254 March 2023 KA2048 0774 Rev 00 Eaton is a registered trademark All trademarks are property of t...

Отзывы: